Plan Review Stops For Permit 17100937 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-15 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-11 |
Time |
17:32 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-02 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-02 |
Time |
13:53 |
Sent To |
I |
|
Notes |
2018-04-02 17:43:52 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE | | TO CLERICAL ERROR. | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR NOA | | NO. 14-1030.02 ARE INCORRECT. THE FASTENER SPACINGS OF | | 9 INCHES ON CENTER FOR ROOF ZONE 2 AND 6 INCHES O.C. | | FOR ROOF ZONE 3 ON THE BALCONY DO NOT MEET THE UPLIFTS | | FOR -65.9 PSF AND -109.1 PSF RESPECTIVELY. PLEASE | | CORRECT. FBC 107.2.1.3 | | | | 2) THE PRODUCT APPROVALS FOR NOA NO. 14-1003.02 WERE | | NOT SUBMITTED. BASED ON THE INFORMATION PROVIDED IN THE | | RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THAT NOA | | THE FASTENER SPACINGS FOR ROOF ZONES 2 AND 3 ARE | | INCORRECT. PLEASE CORRECT AND SUBMIT THE PRODUCT | | APPROVALS. FBC 107.2.1.3 & 107.3.4.1 | | | | 3) SUBMIT PLANS AND STRUCTURAL DETAILS FOR THE CORRIDOR | | FROM THE MAIN HOUSE TO THE TWO STORY GARAGE/GAME ROOM | | STRUCTURE. FBC 107.2.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-13 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-02-12 |
Time |
|
Sent To |
|
|
Notes |
2018-02-16 13:37:00 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH | | EDITION (2014) AND NEC 2010. THE FBC SIXTH EDITION | | (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW | | PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED | | TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION | | (2017) AND NEC 2014. SEE THE COVER SHEET AND PAGES 3.0, | | 7.0 AND 9.0. | | | | 2) FBC R302.6 REQUIRES NOT LESS THAN 5/8" TYPE X GYPSUM | | BOARD OR EQUIVALENT TO SEPARATE THE GARAGE FROM | | HABITABLE ROOMS ABOVE. THE WALL SECTION 1 ON PAGE 7.0 | | DOES NOT SPECIFY 5/8 ' TYPE X DRYWALL ON THE CEILING. | | | | 3) REVISE THE EXTERIOR GLAZING NOTES ON SHEET 7.0 TO | | REFERENCE THE 2017 FBC-R. | | | | 4) SPECIFY THE SIZE OF THE ATTIC ACCESS OPENING ON THE | | PLANS. FBC-R 807.1 | | | | 5) SUBMIT TWO SETS OF A FLORIDA ENERGY CODE COMPLIANCE | | FORM AS REQUIRED BY FBC ENERGY CONSERVATION SECTION | | R101.5.1. THE PREPARER'S NAME AND OWNER/AGENT'S | | SIGNATURE IS REQUIRED ON THE FORM. | | | | 6) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING OF THE CORNER AND | | PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION #7 OF | | NOA NO. 14-1030.02 FOR THE GAF MODIFIED ROOFING SYSTEM. | | | | 7) NOA NO. 12-0716.04 THAT WAS SUBMITTED FOR THE 12' | | WIDE SECTIONAL GARAGE DOOR IS EXPIRED. THE NEGATIVE | | DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS -52.0 PSF | | WHICH DOES NOT MEET THE REQUIREMENTS OF THE THE DOOR | | SCHEDULE AND ELEVATIONS WHICH SPECIFY -53.2 PSF. SUBMIT | | TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE DESIGNER | | OF RECORD'S REVIEW. FBC 107.3.4.1 | | | | 8) THE PRODUCT APPROVALS FOR THE "CAST CRETE" LINTELS | | NOA NO. 17-0227.15, HAS BEEN SUPERSEDED BY 17-0821.19. | | SUBMIT TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE | | DESIGNER OF RECORD'S REVIEW. FBC 107.3.4.1 | | | | 9) SUBMIT TWO SETS OF THE 2017 CODE VERSION OF THE | | PRODUCT APPROVALS FOR THE JELD-WEN DOOR, FL 11136 WITH | | THE DESIGNER OF RECORD'S REVIEW. THE ONES THAT WERE | | SUBMITTED ARE FOR THE 2014 FBC. FBC 107.3.4.1 | | | | 10) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE | | PERMIT VALUATION HAS BEEN INCREASED FROM $40,000.00 TO | | $ 165,028.00 BASED ON CURRENT ICC VALUATION DATA. | | | | 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT | | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-03-30 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-03-30 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-03-30 |
Time |
09:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-08 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-02-08 |
Time |
|
Sent To |
|
|
Notes |
2018-02-16 13:37:47 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE | | CURRENT CODE ABOVE) | | 2. PERMIT APPLICATION STATES THIS IS A REAR STRUCTURE | | ON THE LOT. DUE TO THE FACT THAT ONLY ONE SERVICE PER | | RESIDENTIAL ADDRESS IS PERMITTED, HOW WILL THE MAIN | | STRUCTURE RECEIVE POWER? THE SERVICE DOES NOT APPEAR TO | | BE SIZED TO ACCOMMODATE THE FRONT STRUCTURE. PROVIDE | | CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; NEC | | 230.2; FBC RE E3601.2 | | 3. NOTE 12 STATES THAT RECEPTACLES SHALL BE TAMPER | | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT | | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | CORRECTION. NEC 406.12; FBC RE E4002.14 | | 4. NOTE FOR AFCI PROTECTION DOES NOT COVER ALL AREAS | | THAT REQUIRE THIS PROTECTION PER THE CURRENT CODE: | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC | | 210.12; FBC RE E3902.16 | | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | FBC EC R404.1 | | 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE | | E3706.2, E3902 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2018-06-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-13 |
Time |
09:32 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-05 |
Time |
14:12 |
Sent To |
|
|
Notes |
2018-06-06 14:12:36 | RESUB ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-15 |
Time |
18:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-25 |
Time |
15:07 |
Sent To |
|
|
Notes |
2018-04-26 15:07:51 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-02 |
Time |
18:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-03-13 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-13 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-01-16 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2018-06-27 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-06-27 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-06-27 |
Time |
13:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-02-12 |
Time |
|
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-02-12 |
Time |
|
Sent To |
|
|
Notes |
2018-04-02 17:45:53 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2018-06-13 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-06-13 |
Time |
09:32 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-06-13 |
Time |
09:21 |
Sent To |
|
|
Notes |
2018-06-13 10:02:58 | APPROVED WITH EXCEPTIONS. | | SUBMIT REVISED MECHANICAL PLANS WITH EQUIPMENT SCHEDULE | | THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. FBCR-M | | 1401.3 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2018-05-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-11 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-11 |
Time |
17:32 |
Sent To |
|
|
Notes |
2018-05-11 18:55:49 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE | | TO CLERICAL ERROR. | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATION. FBC | | ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT SIZING. | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, | | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF | | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE | | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING | | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN | | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY | | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER | | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING | | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL | | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD | | KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR | | REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN | | EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM | | REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION | | WHERE THE EQUIPMENT IS INSTALLED. | | NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND | | ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON | | THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION | | OF THE FBC. | | | | 2) SUBMIT TWO SETS OF 2014 ENERGY CODE COMPLIANCE FORMS | | FOR THE NEW GARAGE, OFFICE AND GAME ROOM STRUCTURE. FBC | | ENERGY CONSERVATION - SECT. R103.1.1.2 CODE COMPLIANCE | | CERTIFICATION. | | NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND | | ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON | | THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION | | OF THE FBC. | | | | 3) NEW COMMENT: THE CODE COMPLIANCE FORMS ARE REQUIRED | | TO BE SIGNED BY THE OWNER/AGENT. FBC ENERGY | | CONSERVATION - SECT. R103.1.1.2 | | | | 4) NEW COMMENT: THE ENERGY CODE COMPLIANCE FORMS LIST 1 | | BEDROOM AND THERE ARE NOT ANY BEDROOMS IN THIS | | STRUCTURE SHOWN ON THE PLANS. REVISE. FBC 107.2.1 | | | | 5) NEW COMMENT: THE EQUIPMENT SIZING CALULATIONS AND | | ENERGY FORMS DO NOT MATCH THE EQUIPMENT SCHEDULE ON THE | | PLANS. THE SIZING CALCULATIONS SPECIFY 2.2 TONS AND | | 23,200 BTUH AND THE PLANS LIST 3 TONS AND 36,000 BTUH. | | PLEASE CORRECT FBC 107.2.1. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-04-02 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-04-02 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-04-02 |
Time |
13:54 |
Sent To |
|
|
Notes |
2018-04-02 16:13:13 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE | | TO CLERICAL ERROR. | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATION. FBC | | ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT SIZING. | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, | | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF | | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE | | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING | | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN | | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY | | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER | | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING | | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL | | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD | | KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR | | REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN | | EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM | | REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION | | WHERE THE EQUIPMENT IS INSTALLED. | | | | 2) SUBMIT TWO SETS OF 2014 ENERGY CODE COMPLIANCE FORMS | | FOR THE NEW GARAGE, OFFICE AND GAME ROOM STRUCTURE. FBC | | ENERGY CONSERVATION - SECT. R103.1.1.2 CODE COMPLIANCE | | CERTIFICATION. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-13 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-02-13 |
Time |
|
Sent To |
|
|
Notes |
2018-02-16 13:39:57 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. | | THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE | | 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT | | DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC | | FIFTH EDITION. | | | | 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS. | | FBC ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT | | SIZING. HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, | | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF | | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE | | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING | | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN | | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY | | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER | | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING | | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL | | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD | | KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR | | REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN | | EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM | | REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION | | WHERE THE EQUIPMENT IS INSTALLED. | | | | 3) PROVIDE A MECHANICAL EQUIPMENT SCHEDULE ON THE | | PLANS. FBC 107.3.5.1.4 | | | | 4) SPECIFY THE LOCATION OF THE THERMOSTAT ON THE PLANS. | | FBC 107.3.5.1.4 | | | | 5) SHOW COMPLIANCE WITH FBC M1507.2, WHICH REQUIRES THE | | BATH EXHAUST AIR TO BE EXHAUSTED DIRECTLY TO THE | | OUTDOORS. | | | | 6) BLOWER DOOR TESTING IS REQUIRED FOR RESIDENTIAL | | BUILDINGS PERMITTED ON OR AFTER JULY 1, 2017. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-03-16 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2018-03-16 |
Time |
17:53 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2018-03-16 |
Time |
17:53 |
Sent To |
|
|
Notes |
2018-03-16 17:56:25 | 03/16/18 APPROVED BY PLUMBING AND PUT BACK IN R12, LAC |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-12 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-02-12 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2018-05-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-05-15 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-05-15 |
Time |
17:45 |
Sent To |
|
|
Notes |
2018-05-15 17:47:31 | ROOFING MATERIALS | | GAF RUBEROID MODIFIED BITUMEN, NOA NO. 14-1030.02 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2020-12-22 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2020-12-22 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2020-12-22 |
Time |
15:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-05-02 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2018-05-02 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2018-05-02 |
Time |
11:52 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
Sent By |
AV |
Date |
2018-03-29 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2018-03-29 |
Time |
16:26 |
Sent To |
|
|
Notes |
2018-03-29 16:30:42 | 3/29/18- FAILED- THE SETBACK FOR THE NEW STRUCTURE | | NEEDS TO BE 10% OF THE DEPTH OF THE LOT FROM THE CENTER | | OF THE LOT, DUE TO THE FACT THAT THIS LOT IS NOT OF | | EQUAL DIMENSIONS. | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-02-02 |
Time |
|
Rev Time |
|
Received By |
|
Date |
2018-01-24 |
Time |
|
Sent To |
|
|
Notes |
2018-02-16 13:41:04 | 2/2/18- FAILED. | | 1. WHAT IS THE CONNECTION BETWEEN THE ACCESSORY | | STRUCTURE AND THE PRIMARY HOUSE? | | 2. ACCESSORY STRUCTURES, IF NOT CONNECTED TO THE | | PRIMARY STRUCTURE, CAN NOT EXCEED 1, 000 SQ. FT. | | | | ANGELLA VANN | | [email protected] | | 561-822-1441 |
|
|