Plan Review Details - Permit 17100937
Plan Review Stops For Permit 17100937
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-05-15 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2018-05-11 Time 17:32 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By rmcdouga Date 2018-04-02 Time 18:37 Rev Time 0.00
Received By rmcdouga Date 2018-04-02 Time 13:53 Sent To I
Notes
2018-04-02 17:43:52PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE
 TO CLERICAL ERROR.
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR NOA
 NO. 14-1030.02 ARE INCORRECT. THE FASTENER SPACINGS OF
 9 INCHES ON CENTER FOR ROOF ZONE 2 AND 6 INCHES O.C.
 FOR ROOF ZONE 3 ON THE BALCONY DO NOT MEET THE UPLIFTS
 FOR -65.9 PSF AND -109.1 PSF RESPECTIVELY. PLEASE
 CORRECT. FBC 107.2.1.3
  
 2) THE PRODUCT APPROVALS FOR NOA NO. 14-1003.02 WERE
 NOT SUBMITTED. BASED ON THE INFORMATION PROVIDED IN THE
 RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR THAT NOA
 THE FASTENER SPACINGS FOR ROOF ZONES 2 AND 3 ARE
 INCORRECT. PLEASE CORRECT AND SUBMIT THE PRODUCT
 APPROVALS. FBC 107.2.1.3 & 107.3.4.1
  
 3) SUBMIT PLANS AND STRUCTURAL DETAILS FOR THE CORRIDOR
 FROM THE MAIN HOUSE TO THE TWO STORY GARAGE/GAME ROOM
 STRUCTURE. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-02-13 Time   Rev Time  
Received By   Date 2018-02-12 Time   Sent To  
Notes
2018-02-16 13:37:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014) AND NEC 2010. THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017) AND NEC 2014. SEE THE COVER SHEET AND PAGES 3.0,
 7.0 AND 9.0.
  
 2) FBC R302.6 REQUIRES NOT LESS THAN 5/8" TYPE X GYPSUM
 BOARD OR EQUIVALENT TO SEPARATE THE GARAGE FROM
 HABITABLE ROOMS ABOVE. THE WALL SECTION 1 ON PAGE 7.0
 DOES NOT SPECIFY 5/8 ' TYPE X DRYWALL ON THE CEILING.
  
 3) REVISE THE EXTERIOR GLAZING NOTES ON SHEET 7.0 TO
 REFERENCE THE 2017 FBC-R.
  
 4) SPECIFY THE SIZE OF THE ATTIC ACCESS OPENING ON THE
 PLANS. FBC-R 807.1
  
 5) SUBMIT TWO SETS OF A FLORIDA ENERGY CODE COMPLIANCE
 FORM AS REQUIRED BY FBC ENERGY CONSERVATION SECTION
 R101.5.1. THE PREPARER'S NAME AND OWNER/AGENT'S
 SIGNATURE IS REQUIRED ON THE FORM.
  
 6) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING OF THE CORNER AND
 PERIMETER ROOF AREAS AS REQUIRED BY LIMITATION #7 OF
 NOA NO. 14-1030.02 FOR THE GAF MODIFIED ROOFING SYSTEM.
  
 7) NOA NO. 12-0716.04 THAT WAS SUBMITTED FOR THE 12'
 WIDE SECTIONAL GARAGE DOOR IS EXPIRED. THE NEGATIVE
 DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS -52.0 PSF
 WHICH DOES NOT MEET THE REQUIREMENTS OF THE THE DOOR
 SCHEDULE AND ELEVATIONS WHICH SPECIFY -53.2 PSF. SUBMIT
 TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE DESIGNER
 OF RECORD'S REVIEW. FBC 107.3.4.1
  
 8) THE PRODUCT APPROVALS FOR THE "CAST CRETE" LINTELS
 NOA NO. 17-0227.15, HAS BEEN SUPERSEDED BY 17-0821.19.
 SUBMIT TWO SETS OF CURRENT PRODUCT APPROVALS WITH THE
 DESIGNER OF RECORD'S REVIEW. FBC 107.3.4.1
  
 9) SUBMIT TWO SETS OF THE 2017 CODE VERSION OF THE
 PRODUCT APPROVALS FOR THE JELD-WEN DOOR, FL 11136 WITH
 THE DESIGNER OF RECORD'S REVIEW. THE ONES THAT WERE
 SUBMITTED ARE FOR THE 2014 FBC. FBC 107.3.4.1
  
 10) FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. THE
 PERMIT VALUATION HAS BEEN INCREASED FROM $40,000.00 TO
 $ 165,028.00 BASED ON CURRENT ICC VALUATION DATA.
  
 11) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-30 Cont ID  
Sent By jpearson Date 2018-03-30 Time 09:51 Rev Time 0.00
Received By jpearson Date 2018-03-30 Time 09:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-02-08 Time   Rev Time  
Received By   Date 2018-02-08 Time   Sent To  
Notes
2018-02-16 13:37:47CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE
 CURRENT CODE ABOVE)
 2. PERMIT APPLICATION STATES THIS IS A REAR STRUCTURE
 ON THE LOT. DUE TO THE FACT THAT ONLY ONE SERVICE PER
 RESIDENTIAL ADDRESS IS PERMITTED, HOW WILL THE MAIN
 STRUCTURE RECEIVE POWER? THE SERVICE DOES NOT APPEAR TO
 BE SIZED TO ACCOMMODATE THE FRONT STRUCTURE. PROVIDE
 CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 3. NOTE 12 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. NOTE FOR AFCI PROTECTION DOES NOT COVER ALL AREAS
 THAT REQUIRE THIS PROTECTION PER THE CURRENT CODE:
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-13 Cont ID  
Sent By rmcdouga Date 2018-06-13 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2018-06-05 Time 14:12 Sent To  
Notes
2018-06-06 14:12:36RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-05-15 Time 18:00 Rev Time 0.00
Received By rmcdouga Date 2018-04-25 Time 15:07 Sent To  
Notes
2018-04-26 15:07:51RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-02 Cont ID  
Sent By rmcdouga Date 2018-04-02 Time 18:38 Rev Time 0.00
Received By rmcdouga Date 2018-03-13 Time 15:15 Sent To  
Notes
2018-03-14 15:15:47R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-02-13 Time   Rev Time  
Received By   Date 2018-01-16 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-06-27 Cont ID  
Sent By cthroop Date 2018-06-27 Time 13:56 Rev Time 0.00
Received By cthroop Date 2018-06-27 Time 13:56 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-02-12 Time   Rev Time 0.00
Received By rmcdouga Date 2018-02-12 Time   Sent To  
Notes
2018-04-02 17:45:53BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-06-13 Cont ID  
Sent By rmcdouga Date 2018-06-13 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2018-06-13 Time 09:21 Sent To  
Notes
2018-06-13 10:02:58APPROVED WITH EXCEPTIONS.
 SUBMIT REVISED MECHANICAL PLANS WITH EQUIPMENT SCHEDULE
 THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. FBCR-M
 1401.3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-11 Cont ID  
Sent By rmcdouga Date 2018-05-11 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2018-05-11 Time 17:32 Sent To  
Notes
2018-05-11 18:55:49PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE
 TO CLERICAL ERROR.
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATION. FBC
 ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR
 REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN
 EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM
 REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION
 WHERE THE EQUIPMENT IS INSTALLED.
 NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND
 ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON
 THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION
 OF THE FBC.
  
 2) SUBMIT TWO SETS OF 2014 ENERGY CODE COMPLIANCE FORMS
 FOR THE NEW GARAGE, OFFICE AND GAME ROOM STRUCTURE. FBC
 ENERGY CONSERVATION - SECT. R103.1.1.2 CODE COMPLIANCE
 CERTIFICATION.
 NEW COMMENT: THE EQUIPMENT SIZING CALCULATIONS AND
 ENERGY CODE COMPLIANCE FORMS THAT WERE SUBMITTED ARE ON
 THE 2017 FORMS. THIS PROJECT IS UNDER THE 2014 EDITION
 OF THE FBC.
  
 3) NEW COMMENT: THE CODE COMPLIANCE FORMS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT. FBC ENERGY
 CONSERVATION - SECT. R103.1.1.2
  
 4) NEW COMMENT: THE ENERGY CODE COMPLIANCE FORMS LIST 1
 BEDROOM AND THERE ARE NOT ANY BEDROOMS IN THIS
 STRUCTURE SHOWN ON THE PLANS. REVISE. FBC 107.2.1
  
 5) NEW COMMENT: THE EQUIPMENT SIZING CALULATIONS AND
 ENERGY FORMS DO NOT MATCH THE EQUIPMENT SCHEDULE ON THE
 PLANS. THE SIZING CALCULATIONS SPECIFY 2.2 TONS AND
 23,200 BTUH AND THE PLANS LIST 3 TONS AND 36,000 BTUH.
 PLEASE CORRECT FBC 107.2.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-02 Cont ID  
Sent By rmcdouga Date 2018-04-02 Time 16:21 Rev Time 0.00
Received By rmcdouga Date 2018-04-02 Time 13:54 Sent To  
Notes
2018-04-02 16:13:13PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THE FIRST REVIEW WAS DONE UNDER THE 2017 FBC DUE
 TO CLERICAL ERROR.
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATION. FBC
 ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR
 REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN
 EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM
 REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION
 WHERE THE EQUIPMENT IS INSTALLED.
  
 2) SUBMIT TWO SETS OF 2014 ENERGY CODE COMPLIANCE FORMS
 FOR THE NEW GARAGE, OFFICE AND GAME ROOM STRUCTURE. FBC
 ENERGY CONSERVATION - SECT. R103.1.1.2 CODE COMPLIANCE
 CERTIFICATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-02-13 Time   Rev Time  
Received By   Date 2018-02-13 Time   Sent To  
Notes
2018-02-16 13:39:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS.
 FBC ENERGY CONSERVATION - SECT. R403.7.1 EQUIPMENT
 SIZING. HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS. NEW OR
 REPLACEMENT HEATING AND COOLING EQUIPMENT SHALL HAVE AN
 EFFICIENCY RATING EQUAL TO OR GREATER THAN THE MINIMUM
 REQUIRED BY FEDERAL LAW FOR THE GEOGRAPHIC LOCATION
 WHERE THE EQUIPMENT IS INSTALLED.
  
 3) PROVIDE A MECHANICAL EQUIPMENT SCHEDULE ON THE
 PLANS. FBC 107.3.5.1.4
  
 4) SPECIFY THE LOCATION OF THE THERMOSTAT ON THE PLANS.
 FBC 107.3.5.1.4
  
 5) SHOW COMPLIANCE WITH FBC M1507.2, WHICH REQUIRES THE
 BATH EXHAUST AIR TO BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 6) BLOWER DOOR TESTING IS REQUIRED FOR RESIDENTIAL
 BUILDINGS PERMITTED ON OR AFTER JULY 1, 2017.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-16 Cont ID  
Sent By lcrespo Date 2018-03-16 Time 17:53 Rev Time 0.00
Received By lcrespo Date 2018-03-16 Time 17:53 Sent To  
Notes
2018-03-16 17:56:2503/16/18 APPROVED BY PLUMBING AND PUT BACK IN R12, LAC

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-02-12 Time   Rev Time  
Received By   Date 2018-02-12 Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By rmcdouga Date 2018-05-15 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2018-05-15 Time 17:45 Sent To  
Notes
2018-05-15 17:47:31ROOFING MATERIALS
 GAF RUBEROID MODIFIED BITUMEN, NOA NO. 14-1030.02

Review Stop Z ZONING
Rev No 4 Status P Date 2020-12-22 Cont ID  
Sent By ajones Date 2020-12-22 Time 15:36 Rev Time 0.00
Received By ajones Date 2020-12-22 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-05-02 Cont ID  
Sent By ajones Date 2018-05-02 Time 11:52 Rev Time 0.00
Received By ajones Date 2018-05-02 Time 11:52 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-03-29 Cont ID  
Sent By AV Date 2018-03-29 Time 16:26 Rev Time 0.00
Received By ajones Date 2018-03-29 Time 16:26 Sent To  
Notes
2018-03-29 16:30:423/29/18- FAILED- THE SETBACK FOR THE NEW STRUCTURE
 NEEDS TO BE 10% OF THE DEPTH OF THE LOT FROM THE CENTER
 OF THE LOT, DUE TO THE FACT THAT THIS LOT IS NOT OF
 EQUAL DIMENSIONS.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-02-02 Time   Rev Time  
Received By   Date 2018-01-24 Time   Sent To  
Notes
2018-02-16 13:41:042/2/18- FAILED.
 1. WHAT IS THE CONNECTION BETWEEN THE ACCESSORY
 STRUCTURE AND THE PRIMARY HOUSE?
 2. ACCESSORY STRUCTURES, IF NOT CONNECTED TO THE
 PRIMARY STRUCTURE, CAN NOT EXCEED 1, 000 SQ. FT.
  
 ANGELLA VANN
 [email protected]
 561-822-1441