Plan Review Details - Permit 17100919
Plan Review Stops For Permit 17100919
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 08:40 Rev Time 0.00
Received By shill Date 2017-11-02 Time 08:40 Sent To  
Notes
2017-11-02 08:56:44****PROVISO****
 ****PROVIDE REVISED ELEVATION CERTIFICATE WITHIN SEVEN
 WORKING DAYS****
 ****APPROVED AT CONTRACTOR'S / SURVEYOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 ALL ELEVATIONS FOR THIS PROJECT EXCEED THE MINIMUM
 REQUIREMENTS. HOWEVER, THE FOLLOWING REVISIONS ARE
 REQUIRED:
  
 1. PAGE 2 OF 6, COMMENTS SECTION D, THE TEXT (EL 7)
 SHOULD INCLUDE VERTICAL DATUM (EL 7 NGVD29).
  
 2. COMMENTS SECTION D, SEE ELEVATION CERTIFICATE
 INSTRUCTIONS, CONVERSION IS REQUIRED AS PROJECT WAS
 PERMITTED UNDER A MAP WHICH UTILIZED NGVD29 DATUM. FOR
 ALL ELEVATIONS IN SECTION C2, INCLUDE A CONVERSION TO
 NGVD29.
  
 PLEASE NOTE THAT, AS OF 2017, FOR COMMUNITY RATING
 SYSTEM (FEMA) AUDIT, ALL ELEVATION CERTIFICATES FOR NEW
 CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS WILL BE
 REVIEWED BY THE AUDITOR IN A DIFFERENT STATE AND
 REGION. THE PROJECT'S COMPLIANCE WITH FBC FLOOD
 PROVISIONS AND NFIP (FEMA) REQUIREMENTS ARE DOCUMENTED
 BY THE ELEVATION CERTIFICATE.
  
 THIS REVIEW IS PASSED WITH THE UNDERSTANDING AND
 AGREEMENT THAT THE ELEVATION CERTIFICATE WILL BE
 REVISED AND PROVIDED TO ME OR JULIO GOMEZ WITHIN SEVEN
 BUSINESS DAYS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jgomez Date 2017-10-31 Time 17:41 Rev Time 0.00
Received By jgomez Date 2017-10-31 Time 14:06 Sent To  
Notes
2017-10-31 17:54:01RESIDENTIAL (R3) SUBMITTAL, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ELEVATION CERTIFICATE SUBMITTED: SINCE THE FLOOD MAP
 (FIRM) IN EFFECT AT THE TIME OF THE BUILDING'S
 CONSTRUCTION IS OTHER THAN THE CURRENT FLOOD MAP (FIRM)
 , THEN THE SURVEYOR NEEDS TO PROVIDE THE PAST MAP
 INFORMATION PERTAINING TO THE BUILDING. SURVEYOR TO
 PROVIDE THIS INFORMATION IN THE COMMENTS AREA OF
 SECTION D AS REQUIRED BY THE FEMA ELEVATION CERTIFICATE
 AND INSTRUCTIONS 2015 EDITION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-02 Cont ID  
Sent By shill Date 2017-11-02 Time 08:40 Rev Time 0.00
Received By shill Date 2017-11-02 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-31 Cont ID  
Sent By jgomez Date 2017-10-31 Time 17:54 Rev Time 0.00
Received By jgomez Date 2017-10-23 Time 10:27 Sent To  
Notes
2017-10-24 10:27:34SUBMITTAL ROUTED TO JWITMER