Plan Review Details - Permit 17100808
Plan Review Stops For Permit 17100808
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By cthroop Date 2018-07-10 Time 08:13 Rev Time 0.00
Received By cthroop Date 2018-07-10 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-30 Cont ID  
Sent By aclange Date 2017-10-30 Time 14:50 Rev Time 0.00
Received By aclange Date 2017-10-30 Time 14:37 Sent To  
Notes
2017-10-30 14:59:26 
  
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
  
 INSUFFICIENT INFORMATION SUBMITTED FOR PLAN REVIEW.
 SUBMIT PLANS SHOWING THE LOCATIONS AND TYPE OF WORK TO
 BE COMPLETED. PROVIDE ALSO GUARD RAILING DETAILS. SEE
 ALSO ADA PARKING DETAIL PROVIDED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
 T
 HIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By pleduc Date 2018-07-05 Time   Rev Time 0.00
Received By pleduc Date 2018-07-05 Time 12:29 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By pleduc Date 2017-10-27 Time   Rev Time 0.00
Received By pleduc Date 2017-10-27 Time 12:42 Sent To B
Notes
2017-10-27 15:14:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO DIMENSIONS INDICATED OF THE WIDTH OF
 THE DRIVE LANESOF THE SOUTH GATE. FIRE DEPARTMENT
 VEHICLES SHALL HAVE UNRESTRICTED ACCESS WIDTH OF A
 MINIMUM 12'.
  
 PLEASE PROVIDE THE DIMENSION TO THE EDGE OF THE BOLLARD
 FROM BOTH CURBS.
  
  
  
 2) THERE IS NO INDICATIONS OF HOW THE FIRE DEPARTMENT
 WILL GAIN ACCESS THROUGH THESE GATES; 24 HOUR EMERGENCY
 ACCESS IS REQUIRED. A KNOX KEY SWITCH IS REQUIRED FOR
 ACCESS.
  
 PLEASE PROVIDE DETAILS ON HOW THE FD WILL GAIN ACCESS
 THRU THESE GATES AND/ OR PROVIDE A KNOX KEY SWITCH AT
 EACH LOCATION.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-10 Cont ID  
Sent By cthroop Date 2018-07-10 Time 08:13 Rev Time 0.00
Received By cthroop Date 2018-06-20 Time 12:42 Sent To I
Notes
2018-06-21 12:42:55RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-30 Cont ID  
Sent By aclange Date 2017-10-30 Time 14:59 Rev Time 0.00
Received By aclange Date 2017-10-19 Time 10:13 Sent To  
Notes
2017-10-20 10:13:56ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By llouie Date 2018-07-03 Time   Rev Time 0.00
Received By llouie Date 2018-07-03 Time   Sent To FIRE
Notes
2018-07-03 15:36:42ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) FENCE/GATE SHALL NOT EXCEED 6 FT. IN HEIGHT WITHIN
 THE REQUIRED SIDE OR FRONT SETBACK OF 5 FT.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-25 Cont ID  
Sent By LL Date 2017-10-25 Time   Rev Time 0.00
Received By llouie Date 2017-10-24 Time 15:29 Sent To FIRE
Notes
2017-10-25 11:44:59** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SURVEY OF THE PROPERTY REQUIRED. PLEASE
 PROVIDE.
  
 2.) THERE DOES NOT SEEM TO BE A BYPASS LANE AT THE
 PROPOSED GATES. WHAT IS THE REMEDY FOR THOSE
 RESIDENTS/GUESTS THAT MAY BE CAUGHT AT THE GATE WITHOUT
 ACCESS? (I.E. ARE CARS REQUIRED TO BACK OUT? WHAT IF
 THERE ARE OTHER VEHICLES IN LINE TO GET IN?)
  
 3.) THE GATE SHALL NOT EXCEED 6 FT. IN HEIGHT WITHIN
 THE REQUIRED SIDE SETBACK OF 5 FT. [ZLDR S.94-302]
  
  
 NOTES:
  
 * REVISIONS MAY RESULT IN ADDITIONAL COMMENT.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * Z = MF32
  
 * FIRE STOP ADDED FOR CALL BOX AND ENTRANCE GATE
 REVIEW.
  