Plan Review Details - Permit 17100794
Plan Review Stops For Permit 17100794
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-28 Cont ID  
Sent By rmcdouga Date 2017-11-28 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2017-11-28 Time 17:01 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-08 Cont ID  
Sent By rmcdouga Date 2017-11-08 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2017-11-08 Time 18:03 Sent To G
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By rmcdouga Date 2017-11-01 Time 07:00 Rev Time 0.00
Received By rmcdouga Date 2017-11-01 Time 06:53 Sent To E
Notes
2017-11-01 06:55:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED, SEALED AND DATED
 GENERATOR PAD AND ANCHORING DETAILS FOR EXPOSURE
 CATEGORY C AND A 170 MPH VULT WIND SPEED. THE DOCUMENTS
 ARE REQUIRED TO HAVE THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002
  
 2) THE ENGINEER THAT IS ON THE SLAB ANCHORING PLANS,
 RONALD H. WILSON P.E. LICENSE NO. 9710, HAS HAD HIS FL
 ENGINEERING LICENSE REVOKED SINCE 2/28/2017. SUBMIT
 PLANS FROM A CURRENTLY LICENSED FL ENGINEER. FS 471
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-27 Cont ID  
Sent By jleahy Date 2017-11-27 Time 17:48 Rev Time 0.00
Received By jleahy Date 2017-11-27 Time 17:48 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-08 Cont ID  
Sent By jleahy Date 2017-11-08 Time 12:28 Rev Time 0.00
Received By jleahy Date 2017-11-08 Time 12:28 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By jleahy Date 2017-11-01 Time 07:57 Rev Time 0.00
Received By jleahy Date 2017-11-01 Time 07:57 Sent To  
Notes
2017-11-01 07:58:27FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED CUT SHEETS FOR THE TRANSFER SWITCH (ATS)

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2017-12-06 Cont ID  
Sent By thunt Date 2017-12-06 Time 13:38 Rev Time 0.00
Received By thunt Date 2017-12-06 Time 13:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2017-11-28 Cont ID  
Sent By thunt Date 2017-11-28 Time 14:20 Rev Time 0.00
Received By thunt Date 2017-11-28 Time 14:20 Sent To I
Notes
2017-11-28 14:20:5511/28/2017 GAS 3RD REVIEW **DENIED**
  
  
 COMMENTS FROM LAST REVIEW HAVE NOT BEEN ADDRESSED. IT
 IS RECOMMENED YOU CONTRACT THIS PLAN REVIEWER. A 4TH
 DENIED PLAN REVIEW WILL RESULT IN A 4XFEE FOR PLAN
 REVIEW
  
  
 1) A PROPER GAS ISOMETRIC RISER DIAGRAM SHOWING THE TIE
 IN SIZE TO THE EXISTING SYSTEM WITH THE CONNECTION TO
 THE GAS VALVE, REGULATOR AND DRIP LEG AT THE GENERATOR.
 FBC 107.3.5.THE PLANS INDICATE AN EXISTING GAS METER.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION
  
 2) YOUR SIZING TABLE IS THE INCORRECT CHART. IT SHOULD
 BE SCH 40 METALLIC PIPING AT .5 LBS FGC 402.3. SUBMIT
 TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE
 THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-11-14 Cont ID  
Sent By thunt Date 2017-11-14 Time 15:34 Rev Time 0.00
Received By thunt Date 2017-11-14 Time 15:34 Sent To  
Notes
2017-11-14 15:35:4511/14/2017 GAS 2ND REVIEW**DENIED**COMMENTS #2 AND #3
 HAVE NOT BEEN ADDRESSED.
  
 1) YOU MUST INCLUDE EXISTING BTU LOADS ON THE SYSTEM
 AND INCLUDE THEM ON THE ISOMETRIC DRAWNING. THE PLANS
 INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION.. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 2) YOU MUST INCLUDE ALL SIZING TABLES (2 COPIES) FOR
 EACH PIPING MATERIAL BEING USED OR EXISTING. YOU HAVE
 ONLY PROVIDED THE SIZING TABLE FOR P.E PIPING. SUBMIT
 TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE
 THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By thunt Date 2017-10-31 Time 14:43 Rev Time 0.00
Received By thunt Date 2017-10-31 Time 14:43 Sent To  
Notes
2017-10-31 14:56:4110/31/2017 1ST GAS REVIEW**DENIED**
  
 1) SLAB DETAIL DRAWNING IS REQUIRED TO HAVE A WET SIGN/
 SEAL PER FL ADMIN RULE 61G15-23.001. ALSO YOUR P.E
 RONALD WILSON LICENSE #9710 PER (MYFLORIDALICENSE.COM)
 HAS BEEN REVOKED SINCE FEB,2017 AND THIS REVIEWER HAS
 ALREADY ADVISED YOU OF SUCH PAST REVIEWS.
  
 2) YOU MUST INCLUDE EXISTING BTU LOADS ON THE SYSTEM
 AND INCLUDE THEM ON THE ISOMETRIC DRAWNING. THE PLANS
 INDICATE AN EXISTING GAS METER. THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION.. FGC SECS. 401.4, 401.8, 402.1, 402.2,
 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
  
 3) YOU MUST INCLUDE ALL SIZING TABLES (2 COPIES) FOR
 EACH PIPING MATERIAL BEING USED OR EXISTING. YOU HAVE
 ONLY PROVIDED THE SIZING TABLE FOR P.E PIPING. SUBMIT
 TWO COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE
 THE GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS. 401.4,
 401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2014 FBC-RES. SEC. G2412.4, G2412.8, G2413.1,
 G2413.2, & G2413.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-06 Cont ID  
Sent By thunt Date 2017-12-06 Time 13:38 Rev Time 0.00
Received By thunt Date 2017-12-04 Time 14:47 Sent To I
Notes
2017-12-05 14:48:15RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-28 Cont ID  
Sent By rmcdouga Date 2017-11-28 Time 17:38 Rev Time 0.00
Received By rmcdouga Date 2017-11-20 Time 13:06 Sent To  
Notes
2017-11-21 13:06:22RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-14 Cont ID  
Sent By cpuell Date 2017-11-14 Time 16:20 Rev Time 0.00
Received By cpuell Date 2017-11-02 Time 13:05 Sent To  
Notes
2017-11-03 13:05:36RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-03 Cont ID  
Sent By lmarchan Date 2017-11-03 Time 13:03 Rev Time 0.00
Received By lmarchan Date 2017-10-19 Time 13:00 Sent To  
Notes
2017-10-20 13:01:22ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By PG Date 2017-10-26 Time   Rev Time 0.00
Received By ajones Date 2017-10-24 Time 15:12 Sent To  
Notes
2017-10-26 14:23:51PAUL GREILICH, SENIOR PLANNER