Plan Review Details - Permit 17100775
Plan Review Stops For Permit 17100775
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-02-23 Cont ID  
Sent By jwitmer Date 2018-02-23 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2018-02-23 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-01-26 Cont ID  
Sent By jwitmer Date 2018-01-26 Time 08:50 Rev Time 0.00
Received By jwitmer Date 2018-01-26 Time 07:31 Sent To  
Notes
2018-01-26 08:50:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100775
 ADD: 525 25TH ST.
 CONT: TOU INC.
 TEL: 561-255-1417
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. JAN. 26/2018
 ACTION: DENIED
  
 HOLD ON PERMIT!!!!! STILL NEED OWNERS SIGNATURE ON THE
 PERMIT APPLICATION!!!!
  
 1-3) COMPLIED.
  
 4) PROVISO: SHEET AE-1.0 ALSO INDICATES A RECEPTIONIST/
 CASHIER SERVICE COUNTER BUT THERE ARE NO DETAILS
 PROVIDING CODE COMPLIANCE FOR THE 2014
 FBC-ACCESSIBILITY CODE SECTIONS:
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 3RD REQUEST. THE SHEET AE 3.0 STILL DOES NOT SHOW
 COMPLIANCE WITH THE MECHANICAL CODE, I DISCUSSED THIS
 WITH THE MECHANICAL PLANS EXAMINER, DEPENDING ON THE
 NEXT GENERATION OF PLANS THIS COMMENT STILL STANDS.
 THERE MAY BE SOFFITS TO BE BUILT TO HIDE EXHAUST AIR
 DUCTWORK AND OR ROOF TOP PENETRATIONS.
  
 THE MANICURES AND PEDICURES HAVE TO CATCH THE FUMES AT
 THE SOURCE, PLEASE REVIEW THE MECHANICAL COMMENT # 4
 WILL NEED TO COMPLY WITH 2014 FBC-M TABLE 403,
 FOOTNOTES B & H, DEPENDING WHERE YOU BRING IN THE
 MAKE-UP AIR AND EXHAUST AIR YOU WILL HAVE EITHER WALL
 OR ROOF PENETRATIONS FOR THE NEW INTAKE AND EXHAUST
 FANS. PLEASE NOTE THERE MAYBE ADDITIONAL COMMENTS ABOUT
 ROOF TOP CURBS, INTAKE AND EXHAUST FANS AND THE
 ANCHORING OF THESE UNITS TO THE CURRENT WIND LOADS
 BECAUSE OF CODE REQUIREMENTS UNDER THE MECHANICAL CODE.
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-19 Cont ID  
Sent By jwitmer Date 2017-12-19 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2017-12-19 Time 10:50 Sent To  
Notes
2017-12-19 10:46:172014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100775
 ADD: 525 25TH ST.
 CONT: TOU INC.
 TEL: 561-255-1417
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 19/2017
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET AE-1.0 AN ARCHITECTS PLAN THAT IS
 SIGNED AND SEALED HAS BLACK PIN DRAWN ON TOP OF THE
 SIGNED AND SEALED PLANS. PLEASE NOTE THE REAR COLUMN
 FROM THE ? SCALE TO THE 3/8 INCH SCALE IS NOT DRAWN IN
 THE SAME LOCATION A 6 FOOT DIFFERENCE IN CENTER TO
 CENTER, THE 2ND SET OF PLANS THE 2ND COLUMN IS MISSING
 ON THE 3/8 INCH SCALED PLANS. PLANS CANNOT BE ALTERED
 ONCE THE DESIGN PROFESSIONAL SIGNS AND SEALS THE PLANS.
  
 FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 2) COMPLIED.
  
 3)SEMI-COMPLIED SEE COMMENT # 1. SHEET AE-1.0 INDICATES
 THE REMOVAL OF WALLS BETWEEN TENANT SPACES CREATING A
 SINGLE TENANT SPACE. THE PLANS ARE SILENT ABOUT THE
 WALL BEING REMOVED, IF THE WALL IS A LOAD BEARING WALL
 REQUIRING HEADERS, AND JACK STUDS OR IF THE SECTION OF
 WALL BEING REMOVED IS NON-LOADBEARING WALL? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) PROVISO: SHEET AE-1.0 ALSO INDICATES A RECEPTIONIST/
 CASHIER SERVICE COUNTER BUT THERE ARE NO DETAILS
 PROVIDING CODE COMPLIANCE FOR THE 2014
 FBC-ACCESSIBILITY CODE SECTIONS:
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 2ND REQUEST. THE MANICURES AND PEDICURES HAVE TO
 CATCH THE FUMES AT THE SOURCE, PLEASE REVIEW THE
 MECHANICAL COMMENT # 4 WILL NEED TO COMPLY WITH 2014
 FBC-M TABLE 403, FOOTNOTES B & H, DEPENDING WHERE YOU
 BRING IN THE MAKE-UP AIR AND EXHAUST AIR YOU WILL HAVE
 EITHER WALL OR ROOF PENETRATIONS FOR THE NEW INTAKE AND
 EXHAUST FANS. PLEASE NOTE THERE MAYBE ADDITIONAL
 COMMENTS ABOUT ROOF TOP CURBS, INTAKE AND EXHAUST FANS
 AND THE ANCHORING OF THESE UNITS TO THE CURRENT WIND
 LOADS BECAUSE OF CODE REQUIREMENTS UNDER THE MECHANICAL
 CODE. FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C
 STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK
 AS WELL AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT
 ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-23 Cont ID  
Sent By jwitmer Date 2017-10-23 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2017-10-23 Time 11:40 Sent To  
Notes
2017-10-23 13:33:172014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100775
 ADD: 525 25TH ST.
 CONT: TOU INC.
 TEL: 561-255-1417
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 23/2017
 ACTION: DENIED
  
 1) SHEET AE-1.0 AN ARCHITECTS PLAN THAT IS SIGNED AND
 SEALED HAS BLUE PIN DRAWN ON TOP OF THE SIGNED AND
 SEALED PLANS. PLANS CANNOT BE ALTERED ONCE THE DESIGN
 PROFESSIONAL SIGNS AND SEALS THE PLANS.
  
 FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 2) SHEET AE-1.0 UNDER THE HEADING OF GENERAL NOTES # 1
 INDICATES ALL WORK SHALL BE IN ACCORDANCE WITH
 FBC-SECTION 44 THE HIGH VELOCITY HURRICANE ZONE. PLEASE
 BE ADVISED ONLY BROWARD AND MIAMI-DADE COUNTY ARE UNDER
 THE HIGH VELOCITY HURRICANE SECTIONS REQUIRED BY THE
 CODE, PLEASE CORRECT.
  
 3) SHEET AE-1.0 INDICATES THE REMOVAL OF WALLS BETWEEN
 TENANT SPACES CREATING A SINGLE TENANT SPACE.
 THE PLANS ARE SILENT ABOUT THE WALL BEING REMOVED, IF
 THE WALL IS A LOAD BEARING WALL REQUIRING HEADERS, AND
 JACK STUDS OR IF THE SECTION OF WALL BEING REMOVED IS
 NON-LOADBEARING WALL? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) SHEET AE-1.0 ALSO INDICATES A RECEPTIONIST/ CASHIER
 SERVICE COUNTER BUT THERE ARE NO DETAILS PROVIDING CODE
 COMPLIANCE FOR THE 2014 FBC-ACCESSIBILITY CODE
 SECTIONS:
 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED, CHECK
 WRITING SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) PLEASE NOTE THERE MAYBE ADDITIONAL COMMENTS ABOUT
 ROOF TOP CURBS, INTAKE AND EXHAUST FANS AND THE
 ANCHORING OF THESE UNITS TO THE CURRENT WIND LOADS
 BECAUSE OF CODE REQUIREMENTS UNDER THE MECHANICAL CODE.
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2018-04-26 Cont ID  
Sent By jpearson Date 2018-04-26 Time 08:11 Rev Time 0.00
Received By jpearson Date 2018-04-26 Time 08:11 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2018-04-16 Cont ID  
Sent By jpearson Date 2018-04-16 Time 16:49 Rev Time 0.00
Received By jpearson Date 2018-04-16 Time 16:49 Sent To I
Notes
2018-04-16 16:49:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH
 REVIEW)(STILL NOT PROVIDED ON 6TH REVIEW)(7TH REVIEW -
 SOME OCCUPANCY SENSORS WERE ADDED, BUT NOT ALL LIGHTS
 SHOW THE AUTOMATIC CONTROL REQUIRED PER CODE.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD
 CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)(STILL
 NOT CORRECT ON 6TH REVIEW. THE WATER HEATER LOAD CAN
 NOT BE CALCULATED AT 50%. WHEN CALCULATED AT 100%, THE
 EXISTING SERVICE IS TOO SMALL. PROVIDE CORRECTION.)(7TH
 REVIEW - LOAD CALCULATION STILL NOT CORRECT. A FEEDER
 MUST BE SIZED TO HANDLE 125% OF THE CONTINUOUS LOAD
 PLUS 100% OF THE NON-CONTINUOUS LOAD. YOU HAVE NOT
 CORRECTLY ADDED ALL CONTINUOUS LOADS. PANEL B IS SHOWN
 WITH A LOAD THAT EXCEEDS THE FEEDER SIZE AND OCP SIZE.
 MAIN SERVICE LOAD MAY ALSO EXCEED THE FEEDER SIZE AND
 OCP WHEN COMPLETED CORRECTLY. WHEN LOAD CALCULATION IS
 ACCURATE, THIS WILL BE USED TO SIZE FEEDERS AND OCP FOR
 PANELS.)
 7. CORRECTED.
 8. CORRECTED.
 9. FEE ADDED.
 10. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2018-04-03 Cont ID  
Sent By jpearson Date 2018-04-03 Time 15:13 Rev Time 0.00
Received By jpearson Date 2018-04-03 Time 15:13 Sent To I
Notes
2018-04-03 15:13:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH
 REVIEW)(STILL NOT PROVIDED ON 6TH REVIEW)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD
 CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)(STILL
 NOT CORRECT ON 6TH REVIEW. THE WATER HEATER LOAD CAN
 NOT BE CALCULATED AT 50%. WHEN CALCULATED AT 100%, THE
 EXISTING SERVICE IS TOO SMALL. PROVIDE CORRECTION.)
 7. CORRECTED.
 8. CORRECTED.
 9. FEE ADDED.
 10. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2018-03-16 Cont ID  
Sent By jpearson Date 2018-03-16 Time 16:40 Rev Time 0.00
Received By jpearson Date 2018-03-16 Time 16:40 Sent To P
Notes
2018-03-16 16:40:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. CORRECTED.
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5 (MUST BE ON PLAN)(NOT PROVIDED ON
 5TH REVIEW.)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)(NOT PROVIDED ON 5TH REVIEW)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)(LOAD
 CALCULATION STILL NOT PER CODE ON 5TH REVIEW.)
 7. CORRECTED.
 8. CORRECTED.
 9. FEE ADDED.
 10. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2018-02-28 Cont ID  
Sent By jpearson Date 2018-02-28 Time 09:53 Rev Time 0.00
Received By jpearson Date 2018-02-28 Time 08:42 Sent To  
Notes
2018-02-28 09:53:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH
 DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC
 PREFACE (MUST BE CORRECTED TO CURRENT CODE)
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5 (MUST BE ON PLAN)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)
 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 (INDICATE NEW OR EXISTING CIRCUITS,)
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 (NOT PROVIDED)
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)
 7. CORRECTED.
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8 (NOT CORRECTED.)
 9. FEE ADDED.
 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC C405.2.4 (NOT PROVIDED)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-02-02 Cont ID  
Sent By jpearson Date 2018-02-02 Time 10:28 Rev Time 0.00
Received By jpearson Date 2018-02-02 Time 09:22 Sent To  
Notes
2018-02-02 10:28:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS, 3RD REVIEW: DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH
 DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC
 PREFACE (MUST BE CORRECTED TO CURRENT CODE)
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5 (MUST BE ON PLAN)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2 (NOT PROVIDED)
 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 (INDICATE NEW OR EXISTING CIRCUITS,)
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 (NOT PROVIDED)
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (LOAD CALCULATION
 PROVIDED SHOWS DEMAND FACTORS THAT ARE NOT PERMITTED
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION.)
 7. CORRECTED.
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8 (NOT CORRECTED.)
 9. PLEASE BE ADVISED THAT SOME COMMENT HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
 (BE ADVISED THAT AN ADDITIONAL FEE OF $450 HAS BEEN
 ADDED FOR COMMENTS THAT HAVE NOT BEEN ADDRESSED. THIS
 FEE WILL BE ADDED EACH TIME THE PREVIOUS COMMENTS ARE
 NOT ADDRESSED.)
  
 NEW COMMENT:
  
 10. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC C405.2.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-29 Cont ID  
Sent By jpearson Date 2017-12-29 Time 12:27 Rev Time 0.00
Received By jpearson Date 2017-12-29 Time 12:27 Sent To  
Notes
2017-12-29 11:05:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS ADDRESSED SATISFACTORILY HAVE BEEN
 NOTED AS CORRECTED. ITEMS REMAINING HAVE NOT BEEN
 ADDRESSED OR NEED FURTHER CORRECTION. SEE ADDITIONAL
 COMMENTS IN PARENTHESES.
  
 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH
 DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC
 PREFACE
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5 (MUST BE ON PLAN)
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2
 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 (INDICATE NEW OR EXISTING CIRCUITS)
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 7. CORRECTED.
  
 NEW COMMENTS:
 8. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 WITHIN 6 FEET OF A SINK. NEC 210.8
 9. PLEASE BE ADVISED THAT SOME COMMENT HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By jpearson Date 2017-11-07 Time 09:03 Rev Time 0.00
Received By jpearson Date 2017-11-07 Time 09:03 Sent To  
Notes
2017-11-07 09:03:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTES REFERENCES THE 2009 NEC, WHICH
 DOESN'T EXIST. PROVIDE CORRECT CODE REFERENCE. FBC
 PREFACE
 2. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 3. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC CE 405.2.2,
 405.2.2.2
 4. PROVIDE PANEL SCHEDULES INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 5. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 7. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-02-14 Cont ID  
Sent By pleduc Date 2018-02-14 Time   Rev Time 0.00
Received By pleduc Date 2018-02-14 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-01-23 Cont ID  
Sent By pleduc Date 2018-01-23 Time   Rev Time 0.00
Received By pleduc Date 2018-01-23 Time 12:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-18 Cont ID  
Sent By pleduc Date 2017-12-18 Time   Rev Time 0.00
Received By pleduc Date 2017-12-18 Time 11:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-10-20 Cont ID  
Sent By pleduc Date 2017-10-20 Time   Rev Time 0.00
Received By pleduc Date 2017-10-20 Time 10:12 Sent To  
Notes
2017-10-20 10:58:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET AE 1.0 & LS 1.0 - THERE IS ARE INDICATIONS
 THAT THIS IS A MERCANTILE OCCUPANCY WITH AND OCCUPANCY
 LOAD OF 30ST/PERSON OR 27 TOTAL OCCUPANTS.
  
 ACCORDING TO THE FFPC, NPFA 101, THIS IS A BUSINESS
 OCCUPANCY.WITH AN OCCUPANCY LOAD OF 100 SF/PERSON, OR
 10.
  
 PER CHAPTER 3, DEFINITIONS - 3.3.188.3* BUSINESS
 OCCUPANCY. AN OCCUPANCY USED FOR THE TRANSACTION OF
 BUSINESS OTHER THAN MERCANTILE.
  
 FOR GUIDANCE PURPOSES, ACCORDING TO THE APPENDIX -
  
 A.3.3.188.3 BUSINESS OCCUPANCY. BUSINESS OCCUPANCIES
 INCLUDE THE FOLLOWING:
 (1) AIR TRAFFIC CONTROL TOWERS (ATCTS)
 (2) CITY HALLS
 (3) COLLEGE AND UNIVERSITY INSTRUCTIONAL BUILDINGS,
 CLASSROOMS
 UNDER 50 PERSONS, AND INSTRUCTIONAL LABORATORIES
 (4) COURTHOUSES
 (5) DENTISTS? OFFICES
 (6) DOCTORS? OFFICES
 (7) GENERAL OFFICES
 (8) OUTPATIENT CLINICS (AMBULATORY)
 (9) TOWN HALLS
  
 SERVICE FACILITIES COMMON TO CITY OFFICE BUILDINGS,
 SUCH AS NEWSSTANDS, LUNCH COUNTERS SERVING FEWER THAN
 50 PERSONS, BARBER SHOPS, AND BEAUTY PARLORS ARE
 INCLUDED IN THE BUSINESS OCCUPANCY GROUP.
  
 A NAIL SALON, THIS OCCUPANCY, FALLS UNDER THIS
 OCCUPANCY DEFINITION.
  
 ACCORDING TO CHAPTER 7, MEANS OF EGRESS,
  
 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY
 BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE
 NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA
 ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR
 THAT USE AS SPECIFIED IN TABLE 7.3.1.2, FIGURE
 7.3.1.2(A), AND FIGURE 7.3.1.2(B). WHERE BOTH GROSS AND
 NET AREA FIGURES ARE GIVEN FOR THE SAME OCCUPANCY,
 CALCULATIONS SHALL BE MADE BY APPLYING THE GROSS AREA
 FIGURE TO THE GROSS AREA OF THE PORTION OF THE BUILDING
 DEVOTED TO THE USE FOR WHICH THE GROSS AREA FIGURE IS
 SPECIFIED AND BY APPLYING THE NET AREA FIGURE TO THE
 NET AREA OF THE PORTION OF THE BUILDING DEVOTED TO THE
 USE FOR WHICH THE NET AREA FIGURE IS SPECIFIED.
  
 TABLE 7.3.1.2 OCCUPANT LOAD FACTOR INDICATES AN
 OCCUPANCY LOAD FACTOR OF 100 SQ FT/PERSON.
  
 PLEASE REVIEW AND CORRECT OR PROVIDED DETAIL
 JUSTIFICATION.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2018-04-26 Cont ID  
Sent By jpearson Date 2018-04-26 Time 08:12 Rev Time 0.00
Received By jpearson Date 2018-04-24 Time 15:05 Sent To  
Notes
2018-04-25 15:05:52RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2018-04-16 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-09 Time 11:54 Sent To  
Notes
2018-04-10 11:54:30RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status F Date   Cont ID  
Sent By   Date 2018-04-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-30 Time 11:48 Sent To  
Notes
2018-04-02 11:48:28RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 08:18 Rev Time 0.00
Received By gjohnson Date 2018-03-15 Time 13:00 Sent To  
Notes
2018-03-16 13:00:23RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 08:37 Rev Time 0.00
Received By gjohnson Date 2018-02-12 Time 14:22 Sent To  
Notes
2018-02-13 14:22:14B17

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-07 Cont ID  
Sent By cpuell Date 2018-02-07 Time 13:15 Rev Time 0.00
Received By cpuell Date 2018-01-19 Time 18:45 Sent To  
Notes
2018-01-22 18:46:07B08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-19 Cont ID  
Sent By eschneid Date 2018-01-19 Time 10:14 Rev Time 0.00
Received By eschneid Date 2017-12-14 Time 14:12 Sent To  
Notes
2017-12-15 14:12:31B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-14 Cont ID  
Sent By eschneid Date 2017-11-14 Time 17:22 Rev Time 0.00
Received By eschneid Date 2017-10-18 Time 15:58 Sent To  
Notes
2017-10-19 15:59:05B08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-23 Cont ID  
Sent By jwitmer Date 2017-10-23 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2017-10-23 Time 11:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-02-22 Cont ID  
Sent By ccole Date 2018-02-22 Time 14:10 Rev Time 0.00
Received By ccole Date 2018-02-22 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-01-29 Cont ID  
Sent By ccole Date 2018-01-29 Time 14:40 Rev Time 0.00
Received By ccole Date 2018-01-29 Time 14:37 Sent To  
Notes
2018-01-29 15:04:193RD REVIEW FBC-2014 MECHANICAL
 FBC-14 ENERGY CONSERVATION CODE
 FBC-14 EXISTING BUILDING CODE
 PERMIT #17100775
 1/19/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED MECHANICAL PLANS ARE NOT IN COMPLIANCE.
 I HAVE REPRINTED THE COMMENTS FROM THE 1ST AND 2ND
 REVIEWS BELOW. THE ISSUE IS THE REQUIRED SOURCE CAPTURE
 SYSTEM AT EACH NAIL STATION HAS NOT YET BEEN PROVIDED.
 THE EXHAUST IN THE SOFFIT AND IN THE CEILING OVER THE
 PEDICURES DOES NOT MEET COMPLIANCE FOR CAPTURING AT THE
 SOURCE. IN ADDITION, THE REQUIRED BEAUTY SALON
  
 EXHAUST SYSTEM FOR THE SALON AT A RATE OF 0.60 CFMS PER
 SQ. FT., AND THE REQUESTED EXHAUST CALCULATION FOR THE
 SALON HAVE NOT BEEN PROVIDED.
  
 2ND REVIEW FBC-2014 MECHANICAL
 FBC-14 ENERGY CONSERVATION CODE
 FBC-14 EXISTING BUILDING CODE
 PERMIT #17100775
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #4 FROM THE 1ST REVIEW WAS NOT ADDRESSED AND
 STILL EXISTS. I HAVE REPRINTED IT BELOW. PLEASE REVISE
 THE PLANS TO SHOW COMPLIANCE.
  
 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND
 BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST
 AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY
 WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE
 SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF
 EXHAUSTING NOT LESS THAN 50 CFM PER STATION.
 ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY
 TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 10:07 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 09:58 Sent To  
Notes
2017-12-27 10:11:172ND REVIEW FBC-2014 MECHANICAL
 FBC-14 ENERGY CONSERVATION CODE
 FBC-14 EXISTING BUILDING CODE
 PERMIT #17100775
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #4 FROM THE 1ST REVIEW WAS NOT ADDRESSED AND
 STILL EXISTS. I HAVE REPRINTED IT BELOW. PLEASE REVISE
 THE PLANS TO SHOW COMPLIANCE.
  
 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND
 BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST
 AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY
 WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE
 SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF
 EXHAUSTING NOT LESS THAN 50 CFM PER STATION.
 ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY
 TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By ccole Date 2017-11-01 Time 11:51 Rev Time 0.00
Received By ccole Date 2017-11-01 Time 10:57 Sent To  
Notes
2017-11-01 12:54:011ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY
 CONSERVATION CODES.
 PERMIT #17100775
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET AE-1.0: APPLICABLE CODES MISSING INCLUDE- THE
 FBC-14 FIFTH EDITION MECHANICAL, PLUMBING, ENERGY, AND
 EXISTING BUILDING CODES.
  
 2) AE-1.0: THE PROPOSED PROJECT IS CLASSIFIED AS A
 CHANGE OF OCCUPANCY IN COMPLIANCE WITH SECTION 202
 FBC-14 EXISITNG BUILDING CODE. PLEASE INCLUDE THIS
 DESCRIPTION UNDER PROJECT/OCCUPANCY DATA.
  
 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION
 AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR
 THE CHANGE OF OCCUPANCY. SEE SECTIONS C101.5 & C401.2
 FOR SUBMITTALS AND COMPLIANCE PATH INFORMATION.
  
 4) REFER TO TABLE 403.3 FBC-14 MECHANICAL AND PROVIDE
 EXHAUST VENTILATION CALCULATIONS FOR THE NAIL SALON AND
 BEAUTY SALON. EACH IS REQUIRED TO HAVE AN EXHAUST
 AIRFLOW RATE OF 0.60 CFMS PER SQ. FT., AND MUST COMPLY
 WITH FOOTNOTES B & H: RECIRCULATION OF AIR FROM THE
 SPACES IS PROHIBITED, AND EACH NAIL STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM CAPABLE OF
 EXHAUSTING NOT LESS THAN 50 CFM PER STATION.
 ADDITIONALLY, PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 FOR THE OCCUPANTS IN THE TENANT SPACE AS REQUIRED BY
 TABLE 403.3: PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 DUE TO THE DEFICIENCIES IN THE PLANS LISTED ABOVE, THE
 1ST REVIEW IS STOPPED PENDING RESUBMITTAL OF CORRECTED
 CODE-COMPLIANT PLANS. PLEASE NOTE THAT PLANS DESIGNED
 BY A QUALIFIED FL. LICENSED MECHANICAL ENGINEER WOULD
 HELP EXPEDITE THE REVIEW AND PERMITTING PROCESS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2018-03-17 Cont ID  
Sent By gjohnson Date 2018-03-17 Time 08:06 Rev Time 0.00
Received By gjohnson Date 2018-03-17 Time 08:06 Sent To  
Notes
2018-03-17 08:13:19PLUMBING PROVISO:
 REQUIRED BEFORE FIRST ROUGH INSPECTION.
 1. PROVIDE A SERVICE SINK PER FBC EX 1010.1 AND FBC PL
 TABLE 403.1
 2. PROVIDE A WATER FOUNTAIN FBC PL TABLE 403.1 SHALL
 COMPLY WITH FBC ACC 211.2
 3. WATER HEATER SHALL BE SIZED TO PROVIDE HOT WATER TO
 ALL FIXTURES AT PEAK LOAD PROVIDE MANUFACTURE
 SPECIFICATIONS ON JOBSITE FOR INSPECTIONS. PER WPB
 AMEND TO FBC 107.2.1 AND FBC PL 607.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2018-03-03 Cont ID  
Sent By gjohnson Date 2018-03-03 Time 08:33 Rev Time 0.00
Received By gjohnson Date 2018-03-03 Time 08:33 Sent To  
Notes
2018-03-03 08:36:304TH REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED. 4TH
 REQUEST
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 7. THE DRAIN TO THE WASHING MACHINE SHALL BE 3" PER FBC
 PL 406.2 SHOW TRAP AND STAND PIPE ON ISOMETRIC DRAWING.
  
 8. A LENT TRAP IS REQUIRED ON WASHING MACHINE DRAIN.
 PER FBC PL 1003.6
  
 12. THE SANITARY RISER DIAGRAM IS MISSING THE SIZE ON
 SOME OF THE PIPES PLEASE SIZE ALL PIPES ON RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENTS : 3RD REQUEST
  
 1. BACKFLOW PROTECTION IS REQUIRED FOR PEDICURE CHARS
 AND SHAMPO SINKS. PER FBC PL 608.2
  
 2. IT APPEARS THERE IS A 1/2" WATER MAIN SUPPLING SPACE
 THEN INCREASING SIZE TO 3/4 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE WATER HEATER HAS A INLET AND OUTLET PIPE OF 1/2"
 IS THIS CORRECT YOUR SUPPLING ALL FIXTURES WITH 1/2"
 HOT WATER SUPPLY. PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. THE PEDICURE CHAIR DRAINS SHALL BE TRAPPED. PER FBC
 PL 1002.1
  
 PROVIDE 2 COPY OF THE PEDICURE CHAIRS MANUFACTURE
 INSTALL MANUAL. WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-02-07 Cont ID  
Sent By gjohnson Date 2018-02-07 Time 09:54 Rev Time 0.00
Received By gjohnson Date 2018-02-06 Time 12:08 Sent To  
Notes
2018-02-06 12:10:363RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED. 3RD
 REQUEST
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 7. THE DRAIN TO THE WASHING MACHINE SHALL BE 3" PER FBC
 PL 406.2 SHOW TRAP AND STAND PIPE ON ISOMETRIC DRAWING.
  
 8. A LENT TRAP IS REQUIRED ON WASHING MACHINE DRAIN.
 PER FBC PL 1003.6
  
 12. THE SANITARY RISER DIAGRAM IS MISSING THE SIZE ON
 SOME OF THE PIPES PLEASE SIZE ALL PIPES ON RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 PREVIOUS COMMENTS : 2ND REQUEST
  
 1. BACKFLOW PROTECTION IS REQUIRED FOR PEDICURE CHARS
 AND SHAMPO SINKS. PER FBC PL 608.2
  
 2. IT APPEARS THERE IS A 1/2" WATER MAIN SUPPLING SPACE
 THEN INCREASING SIZE TO 3/4 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE WATER HEATER HAS A INLET AND OUTLET PIPE OF 1/2"
 IS THIS CORRECT YOUR SUPPLING ALL FIXTURES WITH 1/2"
 HOT WATER SUPPLY. PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. THE PEDICURE CHAIR DRAINS SHALL BE TRAPPED. PER FBC
 PL 1002.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-04 Cont ID  
Sent By gjohnson Date 2018-01-04 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2018-01-04 Time 10:37 Sent To  
Notes
2018-01-04 11:09:212ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED.
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 6. PLEASE PROVIDE THE DIMENSIONS OF ACCESSIBLE BATHROOM
 TO CHECK LEVEL OF ACCESSIBILITY. PER WPB AMEND TO FBC
 107.2.1 PARTIALLY COMPLIED PLEASE PROVIDE MOUNTING
 DETAILS FOR GRAB BARS, SINK, TOILET AND MIRROR, TOILET
 PAPER DISPENSER.
  
 7. THE DRAIN TO THE WASHING MACHINE SHALL BE 3" PER FBC
 PL 406.2 SHOW TRAP AND STAND PIPE ON ISOMETRIC DRAWING.
  
 8. A LENT TRAP IS REQUIRED ON WASHING MACHINE DRAIN.
 PER FBC PL 1003.6
  
 9. PLEASE PROVIDE MANUFACTURE INSTALLATION GUIDES FOR
 PEDICURE CHAIRS AND SHAMPOOOO SINKS. PER WPB AMEND TO
 FBC 107.2.1 PARTIALLY COMPLIED INSTALL DETAILS FOR
 PEDICURE CHAIRS ARE NOT LEGIBLE. INSTALLATION GUIDE FOR
 SHAMPO SINK NOT PROVIDED PAPER WORK THAT WAS PROVIDED
 DID NOT GIVE ANY INFORMATION ON PLUMBING CONNECTIONS.
 PROVIDE TWO COPY'S OF BOTH.
  
 10. PROVIDE A DETAIL FOR THE CONNECTIONS ON THE
 PEDICURE CHAIRS. PER WPB AMEND TO FBC 107.2.1
  
 11. THE SHAMPOO SINKS ARE LABELED AS HAND SINKS ON THE
 SANITARY RISER DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 12. THE SANITARY RISER DIAGRAM IS MISSING THE SIZE ON
 SOME OF THE PIPES PLEASE SIZE ALL PIPES ON RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS
  
 1. BACKFLOW PROTECTION IS REQUIRED FOR PEDICURE CHARS
 AND SHAMPO SINKS. PER FBC PL 608.2
  
 2. IT APPEARS THERE IS A 1/2" WATER MAIN SUPPLING SPACE
 THEN INCREASING SIZE TO 3/4 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 3. THE WATER HEATER HAS A INLET AND OUTLET PIPE OF 1/2"
 IS THIS CORRECT YOUR SUPPLING ALL FIXTURES WITH 1/2"
 HOT WATER SUPPLY. PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. THE PEDICURE CHAIR DRAINS SHALL BE TRAPPED. PER FBC
 PL 1002.1
  
 5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By gjohnson Date 2017-11-03 Time 14:53 Rev Time 0.00
Received By gjohnson Date 2017-11-03 Time 13:51 Sent To  
Notes
2017-11-03 15:32:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLUMBING FLOOR PLAN UNCLEAR IT IS TO LIGHT TO BE
 SEEN WHEN RESUBMITTING PLEASE PROVIDE FULLSIZE SHEETS
 TO MATCH THE REST OF THE PLAN. PER WPB AMEND TO FBC
 107.2.1.4
  
 2. THE SEAL AND SIGNATURE OF DESIGN PROFESSIONAL SHALL
 BE AN ORIGINAL NOTE A COPY. PER FS 61G15-23.003
  
 3. THIS SHALL BE A CHANGE OF OCCUPANCY FROM MERCANTILE
 TO BUSINESS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. A DRINKING FOUNTAIN IS REQUIRED PER FBC PL TABLE
 403.1
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1
  
 6. PLEASE PROVIDE THE DIMENSIONS OF ACCESSIBLE BATHROOM
 TO CHECK LEVEL OF ACCESSIBILITY. PER WPB AMEND TO FBC
 107.2.1
  
 7. THE DRAIN TO THE WASHING MACHINE SHALL BE 3" PER FBC
 PL 406.2
  
 8. A LENT TRAP IS REQUIRED ON WASHING MACHINE DRAIN.
 PER FBC PL 1003.6
  
 9. PLEASE PROVIDE MANUFACTURE INSTALLATION GUIDES FOR
 PEDICURE CHAIRS AND SHAMPOO SINKS. PER WPB AMEND TO FBC
 107.2.1
  
 10. PROVIDE A DETAIL FOR THE CONNECTIONS ON THE
 PEDICURE CHAIRS. PER WPB AMEND TO FBC 107.2.1
  
 11. THE SHAMPOO SINKS ARE LABELED AS HAND SINKS ON THE
 SANITARY RISER DIAGRAM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 12. THE SANITARY RISER DIAGRAM IS MISSING THE SIZE ON
 SOME OF THE PIPES PLEASE SIZE ALL PIPES ON RISER. PER
 WPB AMEND TO FBC 107.2.1
  
 13. PLEASE PROVIDE DETAIL ON THE SIZE AND PIPING OF THE
 WATER HEATER. PER WPB AMEND TO FBC 107.2.1 TO COMPLY
 WITH FBC PL 502
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-02-22 Cont ID  
Sent By eschneid Date 2018-02-22 Time 15:32 Rev Time 0.25
Received By eschneid Date 2018-02-22 Time 15:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-02-07 Cont ID  
Sent By ES Date 2018-02-07 Time 11:13 Rev Time 0.50
Received By eschneid Date 2018-02-07 Time 10:51 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-19 Cont ID  
Sent By ES Date 2018-01-19 Time 10:13 Rev Time 0.25
Received By eschneid Date 2018-01-09 Time 12:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-11-14 Cont ID  
Sent By ES Date 2017-11-14 Time 17:22 Rev Time 0.50
Received By eschneid Date 2017-11-14 Time 17:22 Sent To  
Notes
***NONE***