 |
Plan Review Details - Permit 17100767
Plan Review Stops For Permit 17100767 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-12-16 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-12-15 |
Time |
10:30 |
Sent To |
|
|
Notes |
2019-12-16 11:43:06 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | 4TH BUILDING REVIEW DENIED: | | | | 1. FAIL, FBC B 107.2.1,THIS PERMIT APPLICATION TYPE IS | | FOR A COMMERCIAL REMODEL AS THERE WAS A PRIOR PERMIT | | (1110497) FOR THE 20' X 30' CAROLINA CARPORT, BUT THIS | | APPLICATION REQUIRES A CHANGE OF OCCUPANCY. A SURVEY | | AND ELEVATION CERTIFICATE ARE REQUIRED. | | | | 2A. OK. | | 2B. FAIL, FBC B 1603.1.4(4), SHEET A-1 DESIGN | | INFORMATION NEEDS TO SHOW INTERNAL PRESSURE COEFFICIENT | | AS THIS IS PART OF THE FORMULA OF THE WIND DESIGN | | CRITERIA FOR PRESSURES BOTH POSITIVE AND NEGATIVE. | | 2C. FAIL, FBC B 107.2.1, SHEET A-1 DESIGN INFORMATION | | NEEDS TO BE CORRECTED AND SHOW THAT THIS IS A CHANGE OF | | OCCUPANCY. | | 2D. FAIL, FBC EB 1001.1, THE PLANS NEED TO BE UPDATED | | AND SHOW COMPLIANCE WITH THE REQUIREMENTS OF CHANGE OF | | OCCUPANCY PER CHAPTER 10 OF THE FBC (EXISTING). | | | | 3. OK. | | | | 4. FAIL, FBC A 206.4.1 - FBC A 206.4.9 & FBC A 404, THE | | PLANS DO NOT SHOW COMPLIANCE WITH ACCESSIBLE ENTRANCES | | (DOORWAYS). SUBMITTED WITH THE PLANS WAS A PHOTO OF A | | SIDE DOOR WITH A BOTTOM PLATE GOING THROUGH OF THE | | DOOR. IN ADDITION TO THE ACCESSIBLE DOORWAY | | REQUIREMENTS, 60% OF ALL PUBLIC ENTRANCES SHALL COMPLY | | WITH THE BARRIER REQUIREMENTSAT COMMON OR EMERGENCY | | ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS. | | | | 5. FAIL, FBC EC C 402 - C 406/ANSI/ASHRAE/IESNA 90.1, | | PROVIDE COMPLIANCE WITH THE ENERGY REQUIREMENTS FOR | | COMMERCIAL BUILDINGS INCLUDING THE BUILDING ENERGY | | COSTS WHICH SHALL BE EQUAL TO OR LESS THAN 85% OF THE | | STANDARD REFERENCE DESIGN BUILDING. | | | | 6. FAIL, FBC B 107.3.5, AS THIS IS A CHANGE OF | | OCCUPANCY, PROVIDE ALL INFORMATION SHOWING COMPLIANCE | | WITH SECTION 107.3.5 (ITEMS 1 -12) OF THE FBC FOR | | COMMERCIAL BUILDINGS. | | | | 7. FAIL, FBC B 107.2.1, ADDITIONAL INFORMATION AND | | CLARIFICATION IS REQUIRED. UNDER THE CITY BUSINESS TAX | | LICENSE FOR THIS FACILITY, IT IS LISTED AS RESIDENTIAL | | CARE FACILITY WHICH IS A GENERAL TERM UNDER BUSINESS | | LICENSING THAT CAN COVER THE FOLLOWING: ALCOHOL AND | | DRUG CENTERS, ASSISTED LIVING FACILITIES, CONVALESCENT | | FACILITIES, CONGREGATE CARE FACILITIES, GROUP HOMES, | | HALFWAY HOUSES, RESIDENTIAL BOARD AND CUSTODIAL CARE | | FACILITIES, AND SOCIAL REHABILITATION FACILITIES. IF | | THE OFFICE IS ONE OF THE ABOVE USAGES THE PLANS WILL | | NEED TO DECLARE THE OFFICE IS PART OF ONE OF THESE | | TYPES OF FACILITIES, ADDITIONAL COMMENTS MAY APPEAR | | WHEN DECLARED. | | | | 8. FAIL, FBC B 107.2.1, FBC B TABLE 602, AND FBC B | | TABLE 705.8, PROVIDE A SITE PLAN SHOWING THE LOCATION | | OF THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF | | THIS STRUCTURE, OCCUPANCY TYPE, AND MINIMUM | | CONSTRUCTION TYPE. IN ADDITION PROVIDE THE DISTANCE | | BETWEEN THE STRUCTURES AND THE PROPERTY LINE IN | | COMPLIANCE WITH TABLES 602 AND 705.8 (FIRE SEPERATION & | | ALLOWABLE OPENINGS) OF THE FBC BUILDING CODE. | | | | 9. FAIL, FBC B 107.3.5/FBC B 1801.1, PROVIDE FOUNDATION | | DESIGN FOR THE BUILDING. THE DESIGN/CALCULATION NEEDS | | TO INCLUDE THE ADDITIONAL LOADS OF THE FRONT | | WALL/FACADE. | | | | 10. OK PER PROVISO, AS PER FBC B 2510.6, PROVIDE WATER | | RESISTIVE BARRIERS AS PER SECTION 2510.6 OF THE FBC | | (BUILDING). | | | | 11. FAIL, FBC B 107.2.1, PROVIDE EXPLANATION FOR THE | | LETTER FROM DESIGNER OF RECORD, JOHN NOSSAL, COMMENT # | | 2 ABOUT THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO | | HAVE A PRODUCT APPROVAL (FL 12769) FOR A JELD-WEN | | EXTERIOR DOOR. | | | | | | NOTE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE ANY | | PAGES AS NECESSARY, COLLATE AND STAPLE INTO SETS OF | | PLANS. | | | | PLEASE PROVIDE A TRANSMITTAL LETTER LISTING THE REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND. THIS WILL HELP EXPEDITE YOUR | | PERMIT. | | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2019-06-25 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-06-25 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-06-25 |
Time |
09:57 |
Sent To |
|
|
Notes |
2019-06-25 10:16:12 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 3RD BUILDING REVIEW DENIED: | | | | FBC 107. THE DENIED REVIEW COMMENTS FROM THE FIRST | | REVIEW STILL HAVE NOT BEEN ADDRESSED. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | AND IDENTIFY ANY VOIDED SHEETS. A RESPONSE LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDENTIFYING WHERE THE | | CHANGES CAN BE FOUND ON THE PLAN WILL HELP TO EXPEDITE | | YOUR PERMIT. | | | | FOR THIS RESUBMITTAL, IT APPEARS THAT THERE ARE NO | | RESPONSES TO THE PRIOR PLAN REVIEW COMMENTS. THE ONLY | | CHANGE APPEARS TO BE A REVISED BATHROOM LAYOUT. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-12-09 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2018-12-09 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2018-12-09 |
Time |
13:39 |
Sent To |
|
|
Notes |
2018-12-09 13:56:41 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | THE SURVEY(1 COPY) APPEARS TO BE THE SAME THAT WAS | | SUBMITTED LAST TIME WITH NO CHANGES AND NO INDICATION | | OF THE ACCESSORY STRUCTURE ON THE LOT. | | | | PLEASE SEE THE NOTES FROM THE LAST REVIEW DATED | | 10/27/17. | | REVIEW ALL THIRTEEN NOTES AND SUBMIT THE NEW PERMIT | | APPLICATION PACKAGE INCLUDING THE REQUIRED MISSING | | INFORMATION AS NOTED ON THE LAST REVIEW DATED | | 10/27/2017. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-10-27 |
Time |
11:05 |
Rev Time |
|
Received By |
jwitmer |
Date |
2017-10-27 |
Time |
|
Sent To |
|
|
Notes |
2017-10-27 11:05:23 | 2014 FBC- BUILDING PLAN REVIEW | | W. P. B. PERMIT: 17100767 | | ADD: 4012 GARDEN AVE. | | CONT: ABACOA CONSTRUCTION LLC | | TEL: 561-722-3890 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: FRI. OCT. 27/ 2017 | | ACTION: DENIED | | | | 1) THE PERMIT APPLICATION INDICATES UNDER THE | | DESCRIPTION OF WORK REMODEL EXISTING ACCESSORY | | STRUCTURE. | | THE SUBMITTED SHEET INDICATES AN EXISTING 20 X 30 FEET | | EXISTING METAL BUILDING. PLEASE NOTE THE SUBMITTED | | SURVEY DATED 03-12-15 DOES NOT INDICATE A BUILDING SIZE | | 20 X 30 FEET. IN MARCH 2015 THE APPLICANT FILED FOR | | PERMIT (15030114) FOR A 10F X 12F METAL SHED. THIS | | PERMIT WAS NEVER ISSUED AND REVOKED, SITE VISIT NO WORK | | COMPLETED AND REVOKED. | | | | THE 20F X 30F METAL SHED IS TO BE CONSIDERED NEW WORK | | SINCE THERE HAS BEEN NO PERMIT PULLED, NO | | DOCUMENTATION, NO INSPECTIONS. PLEASE ALSO NOTE THE | | APPLICANT HAS BEEN LICENSED FOR 4 RENTAL UNITS SO THIS | | REVIEW WILL TAKE PLACE UNDER THE 2014 FBC-BUILDING | | CODE, NOT THE RESIDENTIAL CODE. | | | | 2A) SHEET A-1, DESIGN INFORMATION. THE PROPOSED USE | | INDICATES OCCUPANCY GROUP R2. THE PLAN SHOWS 2 | | RESTROOMS, OFFICE AND GARAGE. IT WOULD APPEAR THIS IS A | | MIXED USE BUILDING BETWEEN BUSINESS AND STORAGE | | OCCUPANCY SINCE BOTH OCCUPANCY GROUPS ARE OVER 10% OF | | THE FLOOR AREA. | | 107.2.1.3. ADDITIONAL DATA REQUIRED. PLEASE DECLARE IF | | THE GARAGE IS TO BE AN S1 OR S2 USED FOR PARKING | | VEHICLES. | | 2014 FBC-B TABLE 508.4 HOUR FIRE RATINGS. | | FBC-B MIXED USE: 508.1 | | FBC-B 508.3. NON-SEPARATED OCCUPANCIES | | FBC-B 508.4 SEPARATED OCCUPANCIES. | | | | 2B) SHEET A-1, DESIGN INFORMATION. APPLIED INTERNAL | | PRESSURE COEFFICIENT IS MARKED N/A, NOT APPLICABLE. | | PLEASE NOTE FOR EITHER A NEW STRUCTURE OR A SHED THAT | | WAS DESIGN AS A STORAGE RESIDENTIAL SHED IT IS | | IMPORTANT IN THE CONSIDERATION OF THE DESIGN. | | RESIDENTIAL STORAGE SHEDS COULD BE DESIGNED WITH A | | BUILDING RISK FACTOR I WITH A WIND LOAD/ ZONE | | REQUIREMENT OF 160 MPH/ VULT WHEREAS WHEN YOU CHANGE | | THE OCCUPANCY TYPE TO OCCUPIABLE SPACE OR HABITABLE | | SPACE, BUSINESS OCCUPANCY THE BUILDINGS RISK FACTOR HAS | | BEEN CHANGED TO II AND WIND ZONE CATEGORY TO 170 VULT | | MPH. | | FOR THE ENCLOSED BUILDINGS THE INTERNAL PRESSURE | | COEFFICIENT IS REQUIRED SINCE IT IS PART OF THE FORMULA | | OF THE WIND DESIGN CRITERIA FOR PRESSURES BOTH POSITIVE | | AND NEGATIVE. 2014 FBC-B 1603.1.4(4). | | | | 2C) SHEET A-1, DESIGN INFORMATION. THE PLANS INDICATE | | THIS TO BE A LEVEL II ALTERATION. PLEASE NOTE WE ARE | | CONSIDERING THIS NEW CONSTRUCTION SINCE NO PERMIT WAS | | PULLED AND THE SURVEY DATED MARCH 12/2015 DOES NOT SHOW | | A BUILDING THIS SIZE ON THE SURVEY. UPDATE PLANS. | | | | 2D) UNDER THE SCOPE UPDATE TO NEW CONSTRUCTION. | | | | 3) WITHIN THE OFFICE THE RESTROOM # 1 IS ONLY 6 FEET IN | | LENGTH. PLEASE BE AWARE THAT THIS IS CONSIDERED NEW | | CONSTRUCTION SINCE NO PERMIT WAS PULLED FOR THIS | | STORAGE UNIT. WILL NEED TO SHOW COMPLIANCE WITH THE | | 2014 ACCESSIBILITY CODE FIGURE 604.8.1.6 SINGLE USER | | TOILET ROOMS FOR NEW CONSTRUCTION, ALSO REVIEW 604.3.2. | | PLEASE NOTE THE PLANS DO NOT SHOW ANY GRAB BARS PER | | 604.5 FOR THE REAR AND SIDE OF THE WATER CLOSET. PLANS | | ARE ALSO DEFICIENT IN THE WATER CLOSET HEIGHT SEE | | 604.4. | | | | 4) THE PLANS DO NOT SHOW COMPLIANCE WITH AN ACCESSIBLE | | ENTRANCE. SUBMITTED WITH THE PLANS IS A PHOTO OF THE | | SIDE DOOR WHERE HAS A BOTTOM PLATE GOING THROUGH THE | | BOTTOM OF THE DOOR. PLEASE PROVIDE COMPLIANCE WITH: | | 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES. | | (DOORWAYS) | | IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH | | 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES | | SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY | | ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS | | CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE | | EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR | | CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING | | SUCH ENTRANCES OR EXITS SHALL BE REMOVED. | | | | 5) PLEASE PROVIDE COMPLIANCE WITH THE ENERGY CODE | | SECTIONS: COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF | | THE FOLLOWING: | | 5.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. | | 5.2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND | | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY | | WITH EITHER SECTION C406.2, C406.3 OR C406.4. | | 5.3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, | | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE | | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 | | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. | | | | 6) PLEASE NOTE WE ARE CONSIDERING THIS NEW CONSTRUCTION | | SINCE NO PERMIT WAS PULLED AND THE SURVEY DATED MARCH | | 12/2015 DOES NOT SHOW A BUILDING THIS SIZE ON THE | | SURVEY. PLEASE SUBMIT EITHER A FULL SET OF PLANS | | INDICATING COMPLIANCE WITH MINIMUM PLAN REVIEW CRITERIA | | FOR NEW BUILDINGS 107.3.5.1.1 COMMERCIAL BUILDINGS/ | | BUILDING SECTIONS 1-12 FOR THE BUILDING REVIEW OR IF | | THE SHED IS A PREMANUFACTURED SHED WITH STATE APPROVAL, | | SUBMIT THE STATE APPROVED PLANS, WITH APPROVAL NUMBER | | ON THE PLANS. | | INCLUSIVE OF (8) | | ( 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE: | | SOIL CONDITIONS/ANALYSIS | | TERMITE PROTECTION | | DESIGN LOADS | | WIND REQUIREMENTS | | BUILDING ENVELOPE | | STRUCTURAL CALCULATIONS (IF REQUIRED) | | FOUNDATION | | WALL SYSTEMS | | FLOOR SYSTEMS | | ROOF SYSTEMS | | | | 7) ADDITIONAL INFORMATION AND CLARIFICATION IS | | REQUIRED. UNDER THE CITY BUSINESS TAX LICENSE FOR THIS | | FACILITY IT IS LISTED AS RESIDENTIAL CARE FACILITY, | | UNDER THE BUSINESS LICENSING THIS IS A GENERIC TERM | | THAT | | CAN COVER, ALCOHOL AND DRUG CENTERS, ASSISTED LIVING | | FACILITIES, CONGREGATE CARE FACILITIES, CONVALESCENT | | FACILITIES, GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL | | BOARD AND CUSTODIAL CARE FACILITIES, & SOCIAL | | REHABILITATION FACILITIES. IF THE OFFICE IS ONE OF THE | | ABOVE USAGES THE PLANS WILL NEED TO DECLARE THE OFFICE | | IS PART OF ONE OF THIS TYPE OF FACILITIES, ADDITIONAL | | COMMENTS MAY APPEAR WHEN DECLARED. | | | | 8) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF | | THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF THIS | | STRUCTURE, OCCUPANCY TYPE AND MINIMUM CONSTRUCTION TYPE | | PLEASE ALSO PROVIDE THE DISTANCES BETWEEN THE | | STRUCTURES AND THE PROPERTY LINE IN COMPLIANCE WITH | | TABLE 602 OF THE FBC-B AND TABLE 705.8 FIRE SEPARATION | | AND ALLOWABLE OPENINGS. | | | | 9) SHEET A-1 SHOWS A NEW FRONT FA?ADE BUT THERE IS NO | | FOUNDATION DESIGN FOR THE ADDITIONAL WEIGHT OR | | ANCHORING TO THE FOUNDATION TO BE PART OF THE MAIN WIND | | FORCE RESISTING SYSTEM. 107.3.5.1.1 COMMERCIAL | | BUILDINGS/ BUILDING SECTION 8 FOUNDATIONS. | | | | 10) SHEET A-1 INDICATES THE USE OF EXTERIOR GRADE | | PLYWOOD AND P. B. METAL LATH. PLEASE REVIEW FBC-B | | 2510.6 FOR SLIP SHEET PLUS A WATER RESISTANT BARRIER. | | | | 11) PLEASE PROVIDE AN EXPLANATION FOR THE LETTER FROM | | THE DESIGNER OF RECORD JOHN NOSSAL COMMENT # 2 ABOUT | | THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO HAVE A | | SUBMITTED PRODUCT APPROVAL FL 12769 FOR A JELD-WEN | | EXTERIOR DOOR. | | | | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES | | AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE | | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR | | ON SUBSEQUENT REVIEWS. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-12-16 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-12-16 |
Time |
14:56 |
Sent To |
|
|
Notes |
2019-12-16 15:09:37 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE | | COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT | | PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE | | SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND | | REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL | | CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION | | PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT | | COMPLETE, PROVIDE CORRECTION.) | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP | | PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES | | THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT? | | CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL | | OR DISCONNECT AS PREVIOUSLY STATED.) | | 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.) | | 6. CORRECTED. | | 7. CORRECTED. | | 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC | | 110.3 (NOT PROVIDED.) | | 9. CORRECTED. | | 10. CORRECTED. | | 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 | | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN | | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | RE3902.12 (NOT PROVIDED.) | | | | NEW COMMENT: | | | | 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE | | NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW | | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) | | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $ 420.00, | | BASED ON CURRENT VALUE OF PROJECT | | 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2019-06-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-06-25 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-06-25 |
Time |
08:50 |
Sent To |
|
|
Notes |
2019-06-25 08:50:42 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE | | COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM, | | SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND | | OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE | | AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, | | RE3609.3; FBC 107.2.1 (NOT PROVIDED) | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT | | PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE | | SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND | | REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL | | CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION | | PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT | | COMPLETE, PROVIDE CORRECTION.) | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP | | PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES | | THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT? | | CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL | | OR DISCONNECT AS PREVIOUSLY STATED.) | | 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.) | | 6. CORRECTED. | | 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM | | 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE | | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC | | RE3703.4 (NOT CORRECTED.) | | 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC | | 110.3 (NOT PROVIDED.) | | 9. CORRECTED. | | 10. CORRECTED. | | 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 | | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN | | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | RE3902.12 (NOT PROVIDED.) | | | | NEW COMMENT: | | | | 12. NOTE 1 OF ELECTRICAL SPECIFICATIONS STATES THE | | DESIGN IS BASED ON THE 2011 NEC, WHICH IS NOT THE | | CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE, ALSO SEE | | ABOVE. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-11-13 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-11-13 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-11-13 |
Time |
15:21 |
Sent To |
|
|
Notes |
2018-11-13 15:46:20 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM, | | SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND | | OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE | | AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, | | RE3609.3; FBC 107.2.1 (NOT PROVIDED) | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT | | PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE | | SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND | | REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL | | CALCULATED LOAD.) | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP | | PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES | | THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT? | | CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL | | OR DISCONNECT AS PREVIOUSLY STATED.) | | 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.) | | 6. CORRECTED. | | 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM | | 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE | | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC | | RE3703.4 (NOT CORRECTED.) | | 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC | | 110.3 (NOT PROVIDED.) | | 9. CORRECTED. | | 10. CORRECTED. | | 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 | | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN | | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | RE3902.12 (NOT PROVIDED.) | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-11-28 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-11-28 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-11-28 |
Time |
10:19 |
Sent To |
|
|
Notes |
2017-11-28 10:19:19 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ACCURATE LOAD CALCULATION. ANY FEEDER THAT | | IS LESS THAN 100 AMPS IS NOT PERMITTED TO USE THE | | DEMAND LOADS FOUND IN THE NEC AND FBC RESIDENTIAL. | | PANEL AND FEEDERS MUST BE SIZED TO HANDLE ALL LOADS. | | PROVIDE CORRECTION. NEC 220.82 | | 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM, | | SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND | | OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE | | AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1, | | RE3609.3; FBC 107.2.1 | | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | 225.32 | | 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED | | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL | | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON | | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE | | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), | | FBC RE3903.3 | | 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM | | 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE | | OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC | | RE3703.4 | | 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC | | 110.3 | | 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C | | EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12 | | 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | FBC CE R404.1 | | 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15 | | AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN | | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, | | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS | | OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC | | RE3902.12 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2019-11-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-11-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-11-22 |
Time |
13:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2019-05-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2019-05-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2019-05-28 |
Time |
14:36 |
Sent To |
|
|
Notes |
2019-05-28 14:39:22 | 5/28/19 | | | | THE PREVIOUS PROVISO COMMENTS ARE RESUBMITTED: | | | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) THE EXIT DOOR HARWARE SHALL COMPLY WITH NFPA 101, | | CHAP[TER 7, MEANS OF EGRESS. | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE EGRESS SIDE. | | | | 7.2.1.5.5 KEY-OPERATED LOCKS. | | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED | | TO HAVE KEY OPERATED LOCKS FROM THE EGRESS SIDE, | | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: | | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 | | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. | | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS | | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND | | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE | | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE | | BUILDING IS OCCUPIED. | | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY | | DISTINGUISHABLE AS LOCKED. | | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT | | INSIDE THE BUILDING WHEN IT IS LOCKED | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-10-24 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-10-24 |
Time |
11:07 |
Sent To |
|
|
Notes |
2018-10-24 11:10:30 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) THE EXIT DOOR HARWARE SHALL COMPLY WITH NFPA 101, | | CHAP[TER 7, MEANS OF EGRESS. | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE EGRESS SIDE. | | | | 7.2.1.5.5 KEY-OPERATED LOCKS. | | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED | | TO HAVE KEY OPERATED LOCKS FROM THE EGRESS SIDE, | | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: | | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 | | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. | | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS | | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND | | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE | | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE | | BUILDING IS OCCUPIED. | | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY | | DISTINGUISHABLE AS LOCKED. | | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT | | INSIDE THE BUILDING WHEN IT IS LOCKED | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-10-20 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-10-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-10-20 |
Time |
10:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-12-16 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-11-12 |
Time |
14:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-06-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2019-06-26 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2019-05-23 |
Time |
13:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-20 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-12-20 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-10-23 |
Time |
15:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-11-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-11-28 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-10-18 |
Time |
14:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2018-12-20 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2018-12-20 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2018-12-20 |
Time |
11:24 |
Sent To |
|
|
Notes |
2018-12-20 11:28:22 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY PALM | | BEACH COUNTY AND A COPY OF THE PAID RECEIPT ATTACHED TO | | THE PERMIT APPLICATION MUST BE SUBMITTED TO THE CITY OF | | WEST PALM BEACH FOR APPROVAL OF IMPACT FEES. PLEASE | | CALL 561 233 5025 FOR MORE INFORMATION. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-10-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-10-27 |
Time |
11:06 |
Rev Time |
|
Received By |
jwitmer |
Date |
2017-10-27 |
Time |
06:16 |
Sent To |
|
|
Notes |
2017-10-27 11:06:05 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2019-12-10 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-12-10 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-12-10 |
Time |
15:17 |
Sent To |
|
|
Notes |
2019-12-10 15:34:31 | 4TH REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | WPB AMENDMENTS TO THE FBC. | | PERMIT #17100767 | | 12/10/19 | | | | PLAN REVIEW RESULTS: FAILED. | | | | | | REVISED PLANS HAVE BEEN SUBMITTED. THE GARAGE HAS BEEN | | CHANGED TO A CONFERENCE ROOM. | | | | THE REMAINING COMMENTS FROM THE THE PREVOUS THREE | | REVIEWS ARE LISTED BELOW- PLEASE COMPLY | | | | 1) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER | | THERE IS A NEW AC SYSTEM ON THE FLOOR PLAN DRAWINGS- | | SHEET A-1. | | | | A) PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE. | | | | B) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | ROOMS AND SPACES EITHER USING NATURAL OR MECHANICAL | | MEANS- SEE SECTIONS 402, 403 AND TABLE 403.3. | | | | C) PROVIDE AC COOLING AND HEATING CALCULATIONS- | | C403.3.2 FBC-14 ENERGY COMPLIANCE. | | | | D) PROVIDE ENERGY CALCULATIONS- SECTION C101 AND | | C401.2. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2019-06-13 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-06-13 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-06-13 |
Time |
09:26 |
Sent To |
|
|
Notes |
2019-06-13 09:30:41 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | WPB AMENDMENTS TO THE FBC. | | PERMIT #17100767 | | 6/13/19 | | | | PLAN REVIEW RESULTS: FAILED. | | PLEASE NOTE THIS IS THE 3RD REVIEW OF THE PLANS. | | COMMENTS FROM THE 2ND REVIEW WITH RESULTS ARE PRINTED | | BELOW. COMMENTS WITH RESULTS NOT INDICATED AS "OK" MUST | | STILL BE ADDRESSED. | | | | THE COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT | | ADDRESSED AND STILL EXIST- PLEASE COMPLY. | | | | 1) OK | | | | 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER | | THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE | | OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING: | | | | A) AC EQUIPMENT SCHEDULE. | | | | B) OK | | | | C) AIR DEVICE SCHEDULE. | | | | D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND | | RESISTANCE COMPLIANCE. | | | | 3) CALCULATIONS REQUIRED: | | | | A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED | | AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE | | SECTIONS 402, 403 AND TABLE 403.3 | | | | B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14 | | ENERGY COMPLIANCE. | | | | C) ENERGY CALCULATIONS- SECTION C101 AND C401.2. | | | | D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE - | | SEE TABLE 403.3 AND SECTION 404 | | | | 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE | | GARAGE- SEE SECTION 404. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-11-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-11-21 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-11-21 |
Time |
12:18 |
Sent To |
|
|
Notes |
2018-11-21 12:19:19 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | WPB AMENDMENTS TO THE FBC. | | PERMIT #17100767 | | 11/21/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | THE COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT | | ADDRESSED AND STILL EXIST- PLEASE COMPLY. | | | | 1) THE BUILDING PLAN REVIEWER HAS DETERMINED THAT NO | | PERMIT EXISTS FOR THE BUILDING AND AS A RESULT IT WILL | | BE REVIEWED AS A NEW BUILDING. | | | | 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER | | THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE | | OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING: | | | | A) AC EQUIPMENT SCHEDULE. | | | | B) DUCT LAYOUT PLAN. | | | | C) AIR DEVICE SCHEDULE. | | | | D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND | | RESISTANCE COMPLIANCE. | | | | 3) CALCULATIONS REQUIRED: | | | | A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED | | AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE | | SECTIONS 402, 403 AND TABLE 403.3 | | | | B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14 | | ENERGY COMPLIANCE. | | | | C) ENERGY CALCULATIONS- SECTION C101 AND C401.2. | | | | D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE - | | SEE TABLE 403.3 AND SECTION 404 | | | | 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE | | GARAGE- SEE SECTION 404. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-11-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-15 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-15 |
Time |
17:42 |
Sent To |
|
|
Notes |
2017-11-15 17:52:41 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, | | WPB AMENDMENTS TO THE FBC. | | PERMIT #17100767 | | 11/15/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE BUILDING PLAN REVIEWER HAS DETERMINED THAT NO | | PERMIT EXISTS FOR THE BUILDING AND AS A RESULT IT WILL | | BE REVIEWED AS A NEW BUILDING. | | | | 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER | | THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE | | OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING: | | | | A) AC EQUIPMENT SCHEDULE. | | | | B) DUCT LAYOUT PLAN. | | | | C) AIR DEVICE SCHEDULE. | | | | D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND | | RESISTANCE COMPLIANCE. | | | | 3) CALCULATIONS REQUIRED: | | | | A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED | | AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE | | SECTIONS 402, 403 AND TABLE 403.3 | | | | B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14 | | ENERGY COMPLIANCE. | | | | C) ENERGY CALCULATIONS- SECTION C101 AND C401.2. | | | | D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE - | | SEE TABLE 403.3 AND SECTION 404 | | | | 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE | | GARAGE- SEE SECTION 404. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-12-16 |
Time |
06:39 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-12-16 |
Time |
06:39 |
Sent To |
|
|
Notes |
2019-12-16 06:59:18 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | NATIONAL FLOOD INSURANCE PROGRAM REVIEW DENIED: | | | | IT APPEARS THAT REQUIRED FLOOD INFORMATION HAS NOT BEEN | | CONSIDERED. | | FOR THIS STRUCTURE A BREAK DOWN OF THE VALUATION IS | | REQUIRED AS IT APPEARS TO BE A SUBSTANTIAL IMPROVEMENT. | | | | MORE INFORMATION IS REQUIRED: | | | | 1. FBC B 107.2.1, PROVIDE THE SURVEYOR'S ELEVATION | | CERTIFICATE. | | 2. FBC B 107.2.1, PROVIDE A COMPLETED FORM BOARD SURVEY | | FOR THIS STRUCTURE. | | 3. FBC B 107.2.1/FBC B 109.3, PROVIDE A BREAK DOWN OF | | THE VALUATION, AS THIS APPEARS TO BE A SUBSTANTIAL | | IMPROVEMENT PER FEMA'S DEFINITION. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2019-12-10 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2019-12-10 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2019-12-05 |
Time |
16:05 |
Sent To |
|
|
Notes |
2019-12-10 11:38:14 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2014 | | 5TH ED, CHAPTER 1. | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | MANUAL REVISED 2017 | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION | | FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | | | 4TH REVIEW | | PLUMBING COMMENTS: DENIED | | | | 1. IT APPEARS THAT THERE HAS NOT BEEN A PLUMBING PERMIT | | APPLIED FOR OR EXECUTED FOR THIS STRUCTURE. | | | | 2. PROVIDE AS REQUIRED BY THE PLUMBING OFFICIAL, ANY | | DOCUMENTATION INCLUDING OPENING OF WALLS, SLAB AND/OR | | VIDEO OF EXISTING PLUMBING INFRASTRUCTURE TO SHOW | | COMPLIANCE WITH THE 2014 FLORIDA PLUMBING CODE | | | | 3. PLUMBING RISER NOTED AS EXISTING IS NOT CODE | | COMPLIANT. | | A. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY SHOW | | ALL FIXTURE DRAINS AND THEIR RESPECTIVE TRAPS (SEE THE | | SHOWER) AND ACTUAL LAYOUT OF WET VENT AND BUILDING | | DRAIN. | | B. IN ACCORDANCE WITH FBC PL 904.1, A MINIMUM OF ONE | | (1) VENT SHALL EXTEND TO THE OUTSIDE. | | | | 3. PER WPB FBC 107.2.1, PROVIDE DETAILS AS NOTED IN THE | | FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION THE | | FOLLOWING; | | 603.3 MIRRORS, 604.2 LOCATION, 604.3 CLEARANCE, 604.5.1 | | SIDE WALL GRAB BARS, 604.5.2 REAR WALL GRAB BARS, 604.6 | | FLUSH CONTROLS, 604.7 DISPENSERS, 606.2 LAVATORY CLEAR | | FLOOR SPACE, 606.3 LAVATOTY HEIGHT, 608.2.2 STD ROLL-IN | | SHOWERS, 608.3.2 GRAB BARS FOR STD ROLL-IN SHOWERS, | | 608.5.2 SHOWER CONTROLS, 608.7 THRESHOLDS. | | | | 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S | | SPECIFICATION SHEETS AND MANUFACTURER?S INSTALLATION | | REQUIREMENTS FOR THE NOTED INSTA-HOT WATER HEATER. | | INDICATE MODEL NUMBER, ELECTRICAL CHARACTERISTICS, | | MOUNTING DETAILS AND TYPE (TANK TYPE OR TANKLESS). IF | | TANKLESS, PROVIDE THE GPM. TANKLESS SHALL BE INSTALLED | | IN ACCORDANCE WITH MANUFACTURER?S RECOMMENDATION AND | | APPLICABLE REQUIREMENTS OF FBC PL CHAPTER 5. IF TANK | | TYPE, PROVIDE STORAGE CAPACITY AND TYPE AND SIZE OF | | THERMAL EXPANSION CONTROL AS REQIRED BY FBC PL 607.3. | | TANK TYPE SHALL BE INSTALLED IN ACCORDANCE WITH | | MANUFACTURER?S RECOMMENDATION AND SHALL BE PROVIDED | | WITH VALVES AND SAFETY DEVICES AS REQUIRED BY FBC PL | | 503.1, 504.1, 504.2, 504.3, 504.4, 504.4.1, 504.5, | | 504.6 (1-13), 504.7, 504.7.1, 504.7.2 AND FBC PL 607.3. | | | | 5. TEMPERED WATER SHALL BE DELIVERED FROM THE LAVATORY | | THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE | | THAT CONFORMS TO ASSE 1070. | | PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S | | SPECIFICATION FOR A TEMPERATURE LIMITING DEVICE FOR THE | | LAVATORY. | | | | 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW ON THE | | FLOOR PLAN, THE ROUTING OF THE UNDERGROUND SANITARY TO | | THE EXTERIOR OF THE BUILDING. | | | | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A WATER | | RISER DIAGRAM SHOWING THE COLD WATER SERVICE, COLD | | WATER DISTRIBUTION AND HOT WATER DISTRIBUTION. WATER | | HEATER SHALL BE SHOWN. PROVIDE SIZES TO SATISFY FIXTURE | | DEMAND TO COMPLY WITH FBC PL 604.3, 604.4 AND 604.5. | | MINIMUM SIZE OF DISTRIBUTION PIPING SHALL BE ? INCH | | NOMINAL IN ACCORDANCE WITH INDUSTRY STANDARDS. MINIMUM | | SIZE OF WATER SERVICE SHALL BE 3/4"INCH PIPING AND | | SHALL BE PROVIDED WITH A FULL SIZED VALVE AT THE | | ENTRANCE TO THE STRUCTURE PER FBC PL 606.1(2). SPECIFY | | AND PROVIDE A BACKFLOW PREVENTOR FOR THE WATER SERVICE | | IN ACCORDANCE WITH FBC PL 608.1. | | | | 8. PER WPB FBC 107.2.1, SUBMIT A SITE PLAN SHOWING THE | | FOLLOWING: | | A. THE BUILDING SEWER ROUTING AND CONNECTION TO | | EXISTING SANITARY BUILDING DRAIN/SEWER COMPLYING WITH | | FBC PL 703.4, OR TO AN APPROVED CITY LATERAL. | | B. THE WATER SERVICE ROUTING AND CONNECTION TO EXISTING | | SITE WATER. | | | | | | END OF COMMENTS. | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED | | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. | | | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 | | | | 17100767 4012 GARDEN AVE | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2019-06-14 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-06-14 |
Time |
17:11 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-06-14 |
Time |
17:05 |
Sent To |
|
|
Notes |
2019-06-14 17:17:52 | 3RD REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS THEIR HAS BEEN NO | | RESPONSE TO PREVIOUS COMMENTS YOU WILL NEED TO MEET | | WITH PLAN REVIEWER BEFORE RESUBMITTING PLEASE SEE | | CONTACT INFO BELOW. | | | | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC | | | | 603.3 MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | ABOVE THE FINISH FLOOR OR GROUND. | | | | 604.2 LOCATION. | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR | | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY | | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. | | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR | | RIGHT-HAND APPROACH. | | | | 604.3.1 SIZE. | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | PERPENDICULAR FROM THE REAR WALL. | | | | 604.4 SEATS. | | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. | | | | 604.5.1 SIDE WALL. | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) | | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM | | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM | | FROM THE REAR WALL. | | | | 604.5.2 REAR WALL. | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | | | 609.4 POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, | | | | 606.2 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | 606.3 HEIGHT. | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | 604.6 FLUSH CONTROLS. | | FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE | | COMPARTMENTS COMPLYING WITH 604.8.2. | | | | 604.7 DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | NOT ALLOW CONTINUOUS PAPER FLOW. | | | | 2. THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL | | HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE | | OUTDOORS. PER FBC PL 904.1 | | | | 3. PLEASE PROVIDE WATER RISER DIAGRAM SHOWING LOCATION | | OF WATER HEATER. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-12-20 |
|
|
Cont ID |
|
Sent By |
jesmith |
Date |
2018-12-20 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
jesmith |
Date |
2018-12-18 |
Time |
15:06 |
Sent To |
|
|
Notes |
2018-12-20 08:50:01 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012 | | 5TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION | | FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH | | EDITION | | FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION | | FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION | | FAC= FLORIDA ADMINISTRATIVE CODE | | FS = FLORIDA STATUTES | | | | 2ND REVIEW | | | | PLUMBING COMMEMTS: DENIED | | | | 1. PLEASE SEE THE NOTES FROM THE LAST REVIEW DATED | | 10/28/17. | | 2. REVIEW ALL NOTES AND SUBMIT THE NEW PERMIT | | APPLICATION PACKAGE INCLUDING THE REQUIRED MISSING | | INFORMATION AS NOTED ON THE LAST REVIEW DATED | | 10/28/2017. | | 3. NEW COMMENT: TEMPERED WATER SHALL BE DELIVERED FROM | | LAVATORIES THROUGH AN APPROVED WATER-TEMPERATURE | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA | | B125.3 TO COMPLY WITH FBC PL 416.5 | | | | JERALD SMITH | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | EMAIL [email protected] | | PHONE 561-805-6715 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-11-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-11-28 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-11-28 |
Time |
13:25 |
Sent To |
|
|
Notes |
2017-11-28 14:01:18 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE SHOW COMPLIANCE WITH FBC ACC | | | | 603.3 MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES | | OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE | | OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM | | ABOVE THE FINISH FLOOR OR GROUND. | | | | 604.2 LOCATION. | | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR | | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE | | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM | | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR | | PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 | | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM | | FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY | | ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. | | WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR | | RIGHT-HAND APPROACH. | | | | 604.3.1 SIZE. | | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES | | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE | | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED | | PERPENDICULAR FROM THE REAR WALL. | | | | 604.4 SEATS. | | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH | | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES | | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS | | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. | | | | 604.5.1 SIDE WALL. | | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) | | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM | | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM | | FROM THE REAR WALL. | | | | 604.5.2 REAR WALL. | | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG | | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER | | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 | | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. | | | | 609.4 POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, | | | | 606.2 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR | | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | 606.3 HEIGHT. | | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT | | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES | | (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | 604.6 FLUSH CONTROLS. | | FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. | | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. | | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE | | WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE | | COMPARTMENTS COMPLYING WITH 604.8.2. | | | | 604.7 DISPENSERS. | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE | | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 | | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND | | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL | | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES | | NOT ALLOW CONTINUOUS PAPER FLOW. | | | | 2. THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL | | HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE | | OUTDOORS. PER FBC PL 904.1 | | | | 3. PLEASE PROVIDE WATER RISER DIAGRAM SHOWING LOCATION | | OF WATER HEATER. PER WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2019-11-20 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-11-20 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2019-11-20 |
Time |
|
Sent To |
|
|
Notes |
2019-11-20 14:54:15 | ***********************ZONING REVIEW | | FAILED*************************** | | | | PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL | | STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED | | IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW | | RESUBMITTAL. | | | | THANKS, | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2019-06-21 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2019-06-21 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2019-06-21 |
Time |
|
Sent To |
|
|
Notes |
2019-06-21 15:38:23 | ***********************ZONING REVIEW FAILED | | (REPEAT)*************************** | | | | PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL | | STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED | | IS FOR 827 BRIGGS STREET. IS THE FOOTPRINT OF THE | | ACCESSORY BUIDLING INCREASING/CHANGING? FURTHER | | COMMENTS MAY FOLLOW RESUBMITTAL. | | | | THANKS, | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-10-30 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2018-10-29 |
Time |
13:33 |
Sent To |
|
|
Notes |
2018-10-30 10:18:23 | ***********************ZONING REVIEW | | FAILED*************************** | | | | PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL | | STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED | | IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW | | RESUBMITTAL. | | | | THANKS, | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-10-29 |
|
|
Cont ID |
|
Sent By |
AW |
Date |
2017-11-27 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2017-10-27 |
Time |
15:02 |
Sent To |
|
|
Notes |
2017-11-27 14:07:55 | ***********************ZONING REVIEW | | FAILED*************************** | | | | PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL | | STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED | | IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW | | RESUBMITTAL. | | | | THANKS, | | ALANA WOOTEN | | ASSOCIATE PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |