Plan Review Stops For Permit 17100767
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-12-16 Cont ID  
Sent By pvalenti Date 2019-12-16 Time 08:11 Rev Time 0.00
Received By pvalenti Date 2019-12-15 Time 10:30 Sent To  
Notes
2019-12-16 11:43:06***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 4TH BUILDING REVIEW DENIED:
  
 1. FAIL, FBC B 107.2.1,THIS PERMIT APPLICATION TYPE IS
 FOR A COMMERCIAL REMODEL AS THERE WAS A PRIOR PERMIT
 (1110497) FOR THE 20' X 30' CAROLINA CARPORT, BUT THIS
 APPLICATION REQUIRES A CHANGE OF OCCUPANCY. A SURVEY
 AND ELEVATION CERTIFICATE ARE REQUIRED.
  
 2A. OK.
 2B. FAIL, FBC B 1603.1.4(4), SHEET A-1 DESIGN
 INFORMATION NEEDS TO SHOW INTERNAL PRESSURE COEFFICIENT
 AS THIS IS PART OF THE FORMULA OF THE WIND DESIGN
 CRITERIA FOR PRESSURES BOTH POSITIVE AND NEGATIVE.
 2C. FAIL, FBC B 107.2.1, SHEET A-1 DESIGN INFORMATION
 NEEDS TO BE CORRECTED AND SHOW THAT THIS IS A CHANGE OF
 OCCUPANCY.
 2D. FAIL, FBC EB 1001.1, THE PLANS NEED TO BE UPDATED
 AND SHOW COMPLIANCE WITH THE REQUIREMENTS OF CHANGE OF
 OCCUPANCY PER CHAPTER 10 OF THE FBC (EXISTING).
  
 3. OK.
  
 4. FAIL, FBC A 206.4.1 - FBC A 206.4.9 & FBC A 404, THE
 PLANS DO NOT SHOW COMPLIANCE WITH ACCESSIBLE ENTRANCES
 (DOORWAYS). SUBMITTED WITH THE PLANS WAS A PHOTO OF A
 SIDE DOOR WITH A BOTTOM PLATE GOING THROUGH OF THE
 DOOR. IN ADDITION TO THE ACCESSIBLE DOORWAY
 REQUIREMENTS, 60% OF ALL PUBLIC ENTRANCES SHALL COMPLY
 WITH THE BARRIER REQUIREMENTSAT COMMON OR EMERGENCY
 ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS.
  
 5. FAIL, FBC EC C 402 - C 406/ANSI/ASHRAE/IESNA 90.1,
 PROVIDE COMPLIANCE WITH THE ENERGY REQUIREMENTS FOR
 COMMERCIAL BUILDINGS INCLUDING THE BUILDING ENERGY
 COSTS WHICH SHALL BE EQUAL TO OR LESS THAN 85% OF THE
 STANDARD REFERENCE DESIGN BUILDING.
  
 6. FAIL, FBC B 107.3.5, AS THIS IS A CHANGE OF
 OCCUPANCY, PROVIDE ALL INFORMATION SHOWING COMPLIANCE
 WITH SECTION 107.3.5 (ITEMS 1 -12) OF THE FBC FOR
 COMMERCIAL BUILDINGS.
  
 7. FAIL, FBC B 107.2.1, ADDITIONAL INFORMATION AND
 CLARIFICATION IS REQUIRED. UNDER THE CITY BUSINESS TAX
 LICENSE FOR THIS FACILITY, IT IS LISTED AS RESIDENTIAL
 CARE FACILITY WHICH IS A GENERAL TERM UNDER BUSINESS
 LICENSING THAT CAN COVER THE FOLLOWING: ALCOHOL AND
 DRUG CENTERS, ASSISTED LIVING FACILITIES, CONVALESCENT
 FACILITIES, CONGREGATE CARE FACILITIES, GROUP HOMES,
 HALFWAY HOUSES, RESIDENTIAL BOARD AND CUSTODIAL CARE
 FACILITIES, AND SOCIAL REHABILITATION FACILITIES. IF
 THE OFFICE IS ONE OF THE ABOVE USAGES THE PLANS WILL
 NEED TO DECLARE THE OFFICE IS PART OF ONE OF THESE
 TYPES OF FACILITIES, ADDITIONAL COMMENTS MAY APPEAR
 WHEN DECLARED.
  
 8. FAIL, FBC B 107.2.1, FBC B TABLE 602, AND FBC B
 TABLE 705.8, PROVIDE A SITE PLAN SHOWING THE LOCATION
 OF THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF
 THIS STRUCTURE, OCCUPANCY TYPE, AND MINIMUM
 CONSTRUCTION TYPE. IN ADDITION PROVIDE THE DISTANCE
 BETWEEN THE STRUCTURES AND THE PROPERTY LINE IN
 COMPLIANCE WITH TABLES 602 AND 705.8 (FIRE SEPERATION &
 ALLOWABLE OPENINGS) OF THE FBC BUILDING CODE.
  
 9. FAIL, FBC B 107.3.5/FBC B 1801.1, PROVIDE FOUNDATION
 DESIGN FOR THE BUILDING. THE DESIGN/CALCULATION NEEDS
 TO INCLUDE THE ADDITIONAL LOADS OF THE FRONT
 WALL/FACADE.
  
 10. OK PER PROVISO, AS PER FBC B 2510.6, PROVIDE WATER
 RESISTIVE BARRIERS AS PER SECTION 2510.6 OF THE FBC
 (BUILDING).
  
 11. FAIL, FBC B 107.2.1, PROVIDE EXPLANATION FOR THE
 LETTER FROM DESIGNER OF RECORD, JOHN NOSSAL, COMMENT #
 2 ABOUT THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO
 HAVE A PRODUCT APPROVAL (FL 12769) FOR A JELD-WEN
 EXTERIOR DOOR.
  
  
 NOTE: WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION AND REMOVE ANY VOIDED SHEETS AND REPLACE ANY
 PAGES AS NECESSARY, COLLATE AND STAPLE INTO SETS OF
 PLANS.
  
 PLEASE PROVIDE A TRANSMITTAL LETTER LISTING THE REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND. THIS WILL HELP EXPEDITE YOUR
 PERMIT.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-06-25 Cont ID  
Sent By pvalenti Date 2019-06-25 Time 09:57 Rev Time 0.00
Received By pvalenti Date 2019-06-25 Time 09:57 Sent To  
Notes
2019-06-25 10:16:12***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD BUILDING REVIEW DENIED:
  
 FBC 107. THE DENIED REVIEW COMMENTS FROM THE FIRST
 REVIEW STILL HAVE NOT BEEN ADDRESSED.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND IDENTIFY ANY VOIDED SHEETS. A RESPONSE LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING WHERE THE
 CHANGES CAN BE FOUND ON THE PLAN WILL HELP TO EXPEDITE
 YOUR PERMIT.
  
 FOR THIS RESUBMITTAL, IT APPEARS THAT THERE ARE NO
 RESPONSES TO THE PRIOR PLAN REVIEW COMMENTS. THE ONLY
 CHANGE APPEARS TO BE A REVISED BATHROOM LAYOUT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-09 Cont ID  
Sent By pvalenti Date 2018-12-09 Time 13:39 Rev Time 0.00
Received By pvalenti Date 2018-12-09 Time 13:39 Sent To  
Notes
2018-12-09 13:56:41****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE SURVEY(1 COPY) APPEARS TO BE THE SAME THAT WAS
 SUBMITTED LAST TIME WITH NO CHANGES AND NO INDICATION
 OF THE ACCESSORY STRUCTURE ON THE LOT.
  
 PLEASE SEE THE NOTES FROM THE LAST REVIEW DATED
 10/27/17.
 REVIEW ALL THIRTEEN NOTES AND SUBMIT THE NEW PERMIT
 APPLICATION PACKAGE INCLUDING THE REQUIRED MISSING
 INFORMATION AS NOTED ON THE LAST REVIEW DATED
 10/27/2017.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By jwitmer Date 2017-10-27 Time 11:05 Rev Time  
Received By jwitmer Date 2017-10-27 Time   Sent To  
Notes
2017-10-27 11:05:232014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100767
 ADD: 4012 GARDEN AVE.
 CONT: ABACOA CONSTRUCTION LLC
 TEL: 561-722-3890
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 27/ 2017
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK REMODEL EXISTING ACCESSORY
 STRUCTURE.
 THE SUBMITTED SHEET INDICATES AN EXISTING 20 X 30 FEET
 EXISTING METAL BUILDING. PLEASE NOTE THE SUBMITTED
 SURVEY DATED 03-12-15 DOES NOT INDICATE A BUILDING SIZE
 20 X 30 FEET. IN MARCH 2015 THE APPLICANT FILED FOR
 PERMIT (15030114) FOR A 10F X 12F METAL SHED. THIS
 PERMIT WAS NEVER ISSUED AND REVOKED, SITE VISIT NO WORK
 COMPLETED AND REVOKED.
  
 THE 20F X 30F METAL SHED IS TO BE CONSIDERED NEW WORK
 SINCE THERE HAS BEEN NO PERMIT PULLED, NO
 DOCUMENTATION, NO INSPECTIONS. PLEASE ALSO NOTE THE
 APPLICANT HAS BEEN LICENSED FOR 4 RENTAL UNITS SO THIS
 REVIEW WILL TAKE PLACE UNDER THE 2014 FBC-BUILDING
 CODE, NOT THE RESIDENTIAL CODE.
  
 2A) SHEET A-1, DESIGN INFORMATION. THE PROPOSED USE
 INDICATES OCCUPANCY GROUP R2. THE PLAN SHOWS 2
 RESTROOMS, OFFICE AND GARAGE. IT WOULD APPEAR THIS IS A
 MIXED USE BUILDING BETWEEN BUSINESS AND STORAGE
 OCCUPANCY SINCE BOTH OCCUPANCY GROUPS ARE OVER 10% OF
 THE FLOOR AREA.
 107.2.1.3. ADDITIONAL DATA REQUIRED. PLEASE DECLARE IF
 THE GARAGE IS TO BE AN S1 OR S2 USED FOR PARKING
 VEHICLES.
 2014 FBC-B TABLE 508.4 HOUR FIRE RATINGS.
 FBC-B MIXED USE: 508.1
 FBC-B 508.3. NON-SEPARATED OCCUPANCIES
 FBC-B 508.4 SEPARATED OCCUPANCIES.
  
 2B) SHEET A-1, DESIGN INFORMATION. APPLIED INTERNAL
 PRESSURE COEFFICIENT IS MARKED N/A, NOT APPLICABLE.
 PLEASE NOTE FOR EITHER A NEW STRUCTURE OR A SHED THAT
 WAS DESIGN AS A STORAGE RESIDENTIAL SHED IT IS
 IMPORTANT IN THE CONSIDERATION OF THE DESIGN.
 RESIDENTIAL STORAGE SHEDS COULD BE DESIGNED WITH A
 BUILDING RISK FACTOR I WITH A WIND LOAD/ ZONE
 REQUIREMENT OF 160 MPH/ VULT WHEREAS WHEN YOU CHANGE
 THE OCCUPANCY TYPE TO OCCUPIABLE SPACE OR HABITABLE
 SPACE, BUSINESS OCCUPANCY THE BUILDINGS RISK FACTOR HAS
 BEEN CHANGED TO II AND WIND ZONE CATEGORY TO 170 VULT
 MPH.
 FOR THE ENCLOSED BUILDINGS THE INTERNAL PRESSURE
 COEFFICIENT IS REQUIRED SINCE IT IS PART OF THE FORMULA
 OF THE WIND DESIGN CRITERIA FOR PRESSURES BOTH POSITIVE
 AND NEGATIVE. 2014 FBC-B 1603.1.4(4).
  
 2C) SHEET A-1, DESIGN INFORMATION. THE PLANS INDICATE
 THIS TO BE A LEVEL II ALTERATION. PLEASE NOTE WE ARE
 CONSIDERING THIS NEW CONSTRUCTION SINCE NO PERMIT WAS
 PULLED AND THE SURVEY DATED MARCH 12/2015 DOES NOT SHOW
 A BUILDING THIS SIZE ON THE SURVEY. UPDATE PLANS.
  
 2D) UNDER THE SCOPE UPDATE TO NEW CONSTRUCTION.
  
 3) WITHIN THE OFFICE THE RESTROOM # 1 IS ONLY 6 FEET IN
 LENGTH. PLEASE BE AWARE THAT THIS IS CONSIDERED NEW
 CONSTRUCTION SINCE NO PERMIT WAS PULLED FOR THIS
 STORAGE UNIT. WILL NEED TO SHOW COMPLIANCE WITH THE
 2014 ACCESSIBILITY CODE FIGURE 604.8.1.6 SINGLE USER
 TOILET ROOMS FOR NEW CONSTRUCTION, ALSO REVIEW 604.3.2.
 PLEASE NOTE THE PLANS DO NOT SHOW ANY GRAB BARS PER
 604.5 FOR THE REAR AND SIDE OF THE WATER CLOSET. PLANS
 ARE ALSO DEFICIENT IN THE WATER CLOSET HEIGHT SEE
 604.4.
  
 4) THE PLANS DO NOT SHOW COMPLIANCE WITH AN ACCESSIBLE
 ENTRANCE. SUBMITTED WITH THE PLANS IS A PHOTO OF THE
 SIDE DOOR WHERE HAS A BOTTOM PLATE GOING THROUGH THE
 BOTTOM OF THE DOOR. PLEASE PROVIDE COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES.
 (DOORWAYS)
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404. BARRIERS AT COMMON OR EMERGENCY
 ENTRANCES AND EXITS OF BUSINESS ESTABLISHMENTS
 CONDUCTING BUSINESS WITH THE GENERAL PUBLIC THAT ARE
 EXISTING, UNDER CONSTRUCTION, OR UNDER CONTRACT FOR
 CONSTRUCTION WHICH WOULD PREVENT A PERSON FROM USING
 SUCH ENTRANCES OR EXITS SHALL BE REMOVED.
  
 5) PLEASE PROVIDE COMPLIANCE WITH THE ENERGY CODE
 SECTIONS: COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF
 THE FOLLOWING:
 5.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 5.2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 5.3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 6) PLEASE NOTE WE ARE CONSIDERING THIS NEW CONSTRUCTION
 SINCE NO PERMIT WAS PULLED AND THE SURVEY DATED MARCH
 12/2015 DOES NOT SHOW A BUILDING THIS SIZE ON THE
 SURVEY. PLEASE SUBMIT EITHER A FULL SET OF PLANS
 INDICATING COMPLIANCE WITH MINIMUM PLAN REVIEW CRITERIA
 FOR NEW BUILDINGS 107.3.5.1.1 COMMERCIAL BUILDINGS/
 BUILDING SECTIONS 1-12 FOR THE BUILDING REVIEW OR IF
 THE SHED IS A PREMANUFACTURED SHED WITH STATE APPROVAL,
 SUBMIT THE STATE APPROVED PLANS, WITH APPROVAL NUMBER
 ON THE PLANS.
 INCLUSIVE OF (8)
 ( 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 TERMITE PROTECTION
 DESIGN LOADS
 WIND REQUIREMENTS
 BUILDING ENVELOPE
 STRUCTURAL CALCULATIONS (IF REQUIRED)
 FOUNDATION
 WALL SYSTEMS
 FLOOR SYSTEMS
 ROOF SYSTEMS
  
 7) ADDITIONAL INFORMATION AND CLARIFICATION IS
 REQUIRED. UNDER THE CITY BUSINESS TAX LICENSE FOR THIS
 FACILITY IT IS LISTED AS RESIDENTIAL CARE FACILITY,
 UNDER THE BUSINESS LICENSING THIS IS A GENERIC TERM
 THAT
 CAN COVER, ALCOHOL AND DRUG CENTERS, ASSISTED LIVING
 FACILITIES, CONGREGATE CARE FACILITIES, CONVALESCENT
 FACILITIES, GROUP HOMES, HALFWAY HOUSES, RESIDENTIAL
 BOARD AND CUSTODIAL CARE FACILITIES, & SOCIAL
 REHABILITATION FACILITIES. IF THE OFFICE IS ONE OF THE
 ABOVE USAGES THE PLANS WILL NEED TO DECLARE THE OFFICE
 IS PART OF ONE OF THIS TYPE OF FACILITIES, ADDITIONAL
 COMMENTS MAY APPEAR WHEN DECLARED.
  
 8) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 THE OTHER BUILDINGS AND THE PROPOSED LOCATION OF THIS
 STRUCTURE, OCCUPANCY TYPE AND MINIMUM CONSTRUCTION TYPE
 PLEASE ALSO PROVIDE THE DISTANCES BETWEEN THE
 STRUCTURES AND THE PROPERTY LINE IN COMPLIANCE WITH
 TABLE 602 OF THE FBC-B AND TABLE 705.8 FIRE SEPARATION
 AND ALLOWABLE OPENINGS.
  
 9) SHEET A-1 SHOWS A NEW FRONT FA?ADE BUT THERE IS NO
 FOUNDATION DESIGN FOR THE ADDITIONAL WEIGHT OR
 ANCHORING TO THE FOUNDATION TO BE PART OF THE MAIN WIND
 FORCE RESISTING SYSTEM. 107.3.5.1.1 COMMERCIAL
 BUILDINGS/ BUILDING SECTION 8 FOUNDATIONS.
  
 10) SHEET A-1 INDICATES THE USE OF EXTERIOR GRADE
 PLYWOOD AND P. B. METAL LATH. PLEASE REVIEW FBC-B
 2510.6 FOR SLIP SHEET PLUS A WATER RESISTANT BARRIER.
  
 11) PLEASE PROVIDE AN EXPLANATION FOR THE LETTER FROM
 THE DESIGNER OF RECORD JOHN NOSSAL COMMENT # 2 ABOUT
 THE MODIFICATION OF A WOOD DOOR WHEN WE ALSO HAVE A
 SUBMITTED PRODUCT APPROVAL FL 12769 FOR A JELD-WEN
 EXTERIOR DOOR.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-12-16 Cont ID  
Sent By jpearson Date 2019-12-16 Time 15:09 Rev Time 0.00
Received By jpearson Date 2019-12-16 Time 14:56 Sent To  
Notes
2019-12-16 15:09:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT
 PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE
 SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND
 REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL
 CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION
 PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT
 COMPLETE, PROVIDE CORRECTION.)
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP
 PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES
 THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT?
 CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL
 OR DISCONNECT AS PREVIOUSLY STATED.)
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3 (NOT PROVIDED.)
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12 (NOT PROVIDED.)
  
 NEW COMMENT:
  
 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $ 420.00,
 BASED ON CURRENT VALUE OF PROJECT
 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-06-25 Cont ID  
Sent By jpearson Date 2019-06-25 Time 08:50 Rev Time 0.00
Received By jpearson Date 2019-06-25 Time 08:50 Sent To  
Notes
2019-06-25 08:50:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM,
 SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1,
 RE3609.3; FBC 107.2.1 (NOT PROVIDED)
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT
 PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE
 SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND
 REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL
 CALCULATED LOAD. ADDITIONALLY, THE LOAD CALCULATION
 PROVIDED FOR THE PANEL IN THIS STRUCTURE IS NOT
 COMPLETE, PROVIDE CORRECTION.)
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP
 PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES
 THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT?
 CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL
 OR DISCONNECT AS PREVIOUSLY STATED.)
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.)
 6. CORRECTED.
 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM
 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC
 RE3703.4 (NOT CORRECTED.)
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3 (NOT PROVIDED.)
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12 (NOT PROVIDED.)
  
 NEW COMMENT:
  
 12. NOTE 1 OF ELECTRICAL SPECIFICATIONS STATES THE
 DESIGN IS BASED ON THE 2011 NEC, WHICH IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE, ALSO SEE
 ABOVE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-13 Cont ID  
Sent By jpearson Date 2018-11-13 Time 16:14 Rev Time 0.00
Received By jpearson Date 2018-11-13 Time 15:21 Sent To  
Notes
2018-11-13 15:46:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM,
 SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1,
 RE3609.3; FBC 107.2.1 (NOT PROVIDED)
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 (NOT
 PROVIDED. THIS IS FOR THE MAIN SERVICE THAT THE
 SUB-PANEL IS FED FROM. LOAD IS BEING ADDED TO THIS AND
 REVIEWER NEEDS TO KNOW THE CURRENT SIZE AND TOTAL
 CALCULATED LOAD.)
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32 (NOT PROVIDED IN THE NOTES IT STATES THE 60 AMP
 PANEL IS TO REMAIN, IN THE PANEL SCHEDULE IT STATES
 THAT A NEW PANEL WILL BE INSTALLED. WHICH IS CORRECT?
 CORRECT DISCREPANCY AND PROVIDE MAIN BREAKER IN PANEL
 OR DISCONNECT AS PREVIOUSLY STATED.)
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3 (NOT PROVIDED.)
 6. CORRECTED.
 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM
 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC
 RE3703.4 (NOT CORRECTED.)
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3 (NOT PROVIDED.)
 9. CORRECTED.
 10. CORRECTED.
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12 (NOT PROVIDED.)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By jpearson Date 2017-11-28 Time 10:19 Rev Time 0.00
Received By jpearson Date 2017-11-28 Time 10:19 Sent To  
Notes
2017-11-28 10:19:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION. ANY FEEDER THAT
 IS LESS THAN 100 AMPS IS NOT PERMITTED TO USE THE
 DEMAND LOADS FOUND IN THE NEC AND FBC RESIDENTIAL.
 PANEL AND FEEDERS MUST BE SIZED TO HANDLE ALL LOADS.
 PROVIDE CORRECTION. NEC 220.82
 2. WHERE IS THIS PANEL FED FROM? PROVIDE RISER DIAGRAM,
 SHOWING ALL DETAILS OF SERVICE EQUIPMENT, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO SUB-PANEL. SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1,
 RE3609.3; FBC 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
 5. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 6. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE3903.3
 7. TOILET # 2 IS SHOWN ON A 15 AMP BREAKER. A MINIMUM
 20 AMP CIRCUIT IS REQUIRED FOR BATHROOM GFCI RECEPTACLE
 OUTLETS. PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC
 RE3703.4
 8. PROVIDE SPEC SHEET FOR INSTA-HOT WATER HEATER. NEC
 110.3
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE. NEC 210.63; FBC RE3901.12
 10. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 11. PROVIDE COMPLIANCE: ALL 120-VOLT, SINGLE PHASE, 15
 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS
 OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12; FBC
 RE3902.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-11-22 Cont ID  
Sent By pleduc Date 2019-11-22 Time   Rev Time 0.00
Received By pleduc Date 2019-11-22 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-28 Cont ID  
Sent By pleduc Date 2019-05-28 Time   Rev Time 0.00
Received By pleduc Date 2019-05-28 Time 14:36 Sent To  
Notes
2019-05-28 14:39:225/28/19
  
 THE PREVIOUS PROVISO COMMENTS ARE RESUBMITTED:
  
  
  
 THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE EXIT DOOR HARWARE SHALL COMPLY WITH NFPA 101,
 CHAP[TER 7, MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEY OPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time   Rev Time 0.00
Received By pleduc Date 2018-10-24 Time 11:07 Sent To  
Notes
2018-10-24 11:10:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE EXIT DOOR HARWARE SHALL COMPLY WITH NFPA 101,
 CHAP[TER 7, MEANS OF EGRESS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEY OPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-20 Cont ID  
Sent By pleduc Date 2017-10-20 Time   Rev Time 0.00
Received By pleduc Date 2017-10-20 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-12-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-12 Time 14:42 Sent To  
Notes
2019-11-13 14:42:52C08

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-26 Cont ID  
Sent By shill Date 2019-06-26 Time 11:03 Rev Time 0.00
Received By shill Date 2019-05-23 Time 13:51 Sent To  
Notes
2019-05-24 13:52:11C08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By cpuell Date 2018-12-20 Time 13:55 Rev Time 0.00
Received By cpuell Date 2018-10-23 Time 15:29 Sent To  
Notes
2018-10-23 15:31:01C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2017-10-18 Time 14:16 Sent To  
Notes
2017-10-19 14:16:33C17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By pvalenti Date 2018-12-20 Time 11:24 Rev Time 0.00
Received By pvalenti Date 2018-12-20 Time 11:24 Sent To  
Notes
2018-12-20 11:28:22****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY AND A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION MUST BE SUBMITTED TO THE CITY OF
 WEST PALM BEACH FOR APPROVAL OF IMPACT FEES. PLEASE
 CALL 561 233 5025 FOR MORE INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By jwitmer Date 2017-10-27 Time 11:06 Rev Time  
Received By jwitmer Date 2017-10-27 Time 06:16 Sent To  
Notes
2017-10-27 11:06:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2019-12-10 Cont ID  
Sent By ccole Date 2019-12-10 Time 15:20 Rev Time 0.00
Received By ccole Date 2019-12-10 Time 15:17 Sent To  
Notes
2019-12-10 15:34:314TH REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 12/10/19
  
 PLAN REVIEW RESULTS: FAILED.
  
  
 REVISED PLANS HAVE BEEN SUBMITTED. THE GARAGE HAS BEEN
 CHANGED TO A CONFERENCE ROOM.
  
 THE REMAINING COMMENTS FROM THE THE PREVOUS THREE
 REVIEWS ARE LISTED BELOW- PLEASE COMPLY
  
 1) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS A NEW AC SYSTEM ON THE FLOOR PLAN DRAWINGS-
 SHEET A-1.
  
 A) PLEASE PROVIDE AN AC EQUIPMENT SCHEDULE.
  
 B) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 ROOMS AND SPACES EITHER USING NATURAL OR MECHANICAL
 MEANS- SEE SECTIONS 402, 403 AND TABLE 403.3.
  
 C) PROVIDE AC COOLING AND HEATING CALCULATIONS-
 C403.3.2 FBC-14 ENERGY COMPLIANCE.
  
 D) PROVIDE ENERGY CALCULATIONS- SECTION C101 AND
 C401.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-06-13 Cont ID  
Sent By ccole Date 2019-06-13 Time 09:26 Rev Time 0.00
Received By ccole Date 2019-06-13 Time 09:26 Sent To  
Notes
2019-06-13 09:30:413RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 6/13/19
  
 PLAN REVIEW RESULTS: FAILED.
 PLEASE NOTE THIS IS THE 3RD REVIEW OF THE PLANS.
 COMMENTS FROM THE 2ND REVIEW WITH RESULTS ARE PRINTED
 BELOW. COMMENTS WITH RESULTS NOT INDICATED AS "OK" MUST
 STILL BE ADDRESSED.
  
 THE COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED AND STILL EXIST- PLEASE COMPLY.
  
 1) OK
  
 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE
 OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING:
  
 A) AC EQUIPMENT SCHEDULE.
  
 B) OK
  
 C) AIR DEVICE SCHEDULE.
  
 D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND
 RESISTANCE COMPLIANCE.
  
 3) CALCULATIONS REQUIRED:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED
 AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE
 SECTIONS 402, 403 AND TABLE 403.3
  
 B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14
 ENERGY COMPLIANCE.
  
 C) ENERGY CALCULATIONS- SECTION C101 AND C401.2.
  
 D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE -
 SEE TABLE 403.3 AND SECTION 404
  
 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 GARAGE- SEE SECTION 404.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-21 Cont ID  
Sent By ccole Date 2018-11-21 Time 12:18 Rev Time 0.00
Received By ccole Date 2018-11-21 Time 12:18 Sent To  
Notes
2018-11-21 12:19:192ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 11/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED AND STILL EXIST- PLEASE COMPLY.
  
 1) THE BUILDING PLAN REVIEWER HAS DETERMINED THAT NO
 PERMIT EXISTS FOR THE BUILDING AND AS A RESULT IT WILL
 BE REVIEWED AS A NEW BUILDING.
  
 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE
 OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING:
  
 A) AC EQUIPMENT SCHEDULE.
  
 B) DUCT LAYOUT PLAN.
  
 C) AIR DEVICE SCHEDULE.
  
 D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND
 RESISTANCE COMPLIANCE.
  
 3) CALCULATIONS REQUIRED:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED
 AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE
 SECTIONS 402, 403 AND TABLE 403.3
  
 B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14
 ENERGY COMPLIANCE.
  
 C) ENERGY CALCULATIONS- SECTION C101 AND C401.2.
  
 D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE -
 SEE TABLE 403.3 AND SECTION 404
  
 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 GARAGE- SEE SECTION 404.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By ccole Date 2017-11-15 Time 17:49 Rev Time 0.00
Received By ccole Date 2017-11-15 Time 17:42 Sent To  
Notes
2017-11-15 17:52:411ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 WPB AMENDMENTS TO THE FBC.
 PERMIT #17100767
 11/15/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BUILDING PLAN REVIEWER HAS DETERMINED THAT NO
 PERMIT EXISTS FOR THE BUILDING AND AS A RESULT IT WILL
 BE REVIEWED AS A NEW BUILDING.
  
 2) THERE ARE NO MECHANICAL PLANS SUBMITTED HOWEVER
 THERE IS AN AIR HANDLER SHOWN IN A CLOSET BY THE
 OFFICE. PLEASE PROVIDE COMPLETE AC PLANS INCLUDING:
  
 A) AC EQUIPMENT SCHEDULE.
  
 B) DUCT LAYOUT PLAN.
  
 C) AIR DEVICE SCHEDULE.
  
 D) LOCATION OF CONDENSER AND FLOOD ELEVATION AND WIND
 RESISTANCE COMPLIANCE.
  
 3) CALCULATIONS REQUIRED:
  
 A) MINIMUM VENTILATION CALCULATIONS FOR THE OCCUPIED
 AREA EITHER USING NATURAL OR MECHANICAL MEANS- SEE
 SECTIONS 402, 403 AND TABLE 403.3
  
 B) AC COOLING AND HEATING CALCULATIONS- C403.3.2 FBC-14
 ENERGY COMPLIANCE.
  
 C) ENERGY CALCULATIONS- SECTION C101 AND C401.2.
  
 D) EXHAUST VENTILATION CALCULATIONS FOR THE GARAGE -
 SEE TABLE 403.3 AND SECTION 404
  
 4) PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 GARAGE- SEE SECTION 404.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2019-12-16 Cont ID  
Sent By pvalenti Date 2019-12-16 Time 06:39 Rev Time 0.00
Received By pvalenti Date 2019-12-16 Time 06:39 Sent To  
Notes
2019-12-16 06:59:18***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 NATIONAL FLOOD INSURANCE PROGRAM REVIEW DENIED:
  
 IT APPEARS THAT REQUIRED FLOOD INFORMATION HAS NOT BEEN
 CONSIDERED.
 FOR THIS STRUCTURE A BREAK DOWN OF THE VALUATION IS
 REQUIRED AS IT APPEARS TO BE A SUBSTANTIAL IMPROVEMENT.
  
 MORE INFORMATION IS REQUIRED:
  
 1. FBC B 107.2.1, PROVIDE THE SURVEYOR'S ELEVATION
 CERTIFICATE.
 2. FBC B 107.2.1, PROVIDE A COMPLETED FORM BOARD SURVEY
 FOR THIS STRUCTURE.
 3. FBC B 107.2.1/FBC B 109.3, PROVIDE A BREAK DOWN OF
 THE VALUATION, AS THIS APPEARS TO BE A SUBSTANTIAL
 IMPROVEMENT PER FEMA'S DEFINITION.
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-12-10 Cont ID  
Sent By jesmith Date 2019-12-10 Time 11:38 Rev Time 0.00
Received By jesmith Date 2019-12-05 Time 16:05 Sent To  
Notes
2019-12-10 11:38:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2014
 5TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 4TH REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. IT APPEARS THAT THERE HAS NOT BEEN A PLUMBING PERMIT
 APPLIED FOR OR EXECUTED FOR THIS STRUCTURE.
  
 2. PROVIDE AS REQUIRED BY THE PLUMBING OFFICIAL, ANY
 DOCUMENTATION INCLUDING OPENING OF WALLS, SLAB AND/OR
 VIDEO OF EXISTING PLUMBING INFRASTRUCTURE TO SHOW
 COMPLIANCE WITH THE 2014 FLORIDA PLUMBING CODE
  
 3. PLUMBING RISER NOTED AS EXISTING IS NOT CODE
 COMPLIANT.
 A. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY SHOW
 ALL FIXTURE DRAINS AND THEIR RESPECTIVE TRAPS (SEE THE
 SHOWER) AND ACTUAL LAYOUT OF WET VENT AND BUILDING
 DRAIN.
 B. IN ACCORDANCE WITH FBC PL 904.1, A MINIMUM OF ONE
 (1) VENT SHALL EXTEND TO THE OUTSIDE.
  
 3. PER WPB FBC 107.2.1, PROVIDE DETAILS AS NOTED IN THE
 FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION THE
 FOLLOWING;
 603.3 MIRRORS, 604.2 LOCATION, 604.3 CLEARANCE, 604.5.1
 SIDE WALL GRAB BARS, 604.5.2 REAR WALL GRAB BARS, 604.6
 FLUSH CONTROLS, 604.7 DISPENSERS, 606.2 LAVATORY CLEAR
 FLOOR SPACE, 606.3 LAVATOTY HEIGHT, 608.2.2 STD ROLL-IN
 SHOWERS, 608.3.2 GRAB BARS FOR STD ROLL-IN SHOWERS,
 608.5.2 SHOWER CONTROLS, 608.7 THRESHOLDS.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION SHEETS AND MANUFACTURER?S INSTALLATION
 REQUIREMENTS FOR THE NOTED INSTA-HOT WATER HEATER.
 INDICATE MODEL NUMBER, ELECTRICAL CHARACTERISTICS,
 MOUNTING DETAILS AND TYPE (TANK TYPE OR TANKLESS). IF
 TANKLESS, PROVIDE THE GPM. TANKLESS SHALL BE INSTALLED
 IN ACCORDANCE WITH MANUFACTURER?S RECOMMENDATION AND
 APPLICABLE REQUIREMENTS OF FBC PL CHAPTER 5. IF TANK
 TYPE, PROVIDE STORAGE CAPACITY AND TYPE AND SIZE OF
 THERMAL EXPANSION CONTROL AS REQIRED BY FBC PL 607.3.
 TANK TYPE SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATION AND SHALL BE PROVIDED
 WITH VALVES AND SAFETY DEVICES AS REQUIRED BY FBC PL
 503.1, 504.1, 504.2, 504.3, 504.4, 504.4.1, 504.5,
 504.6 (1-13), 504.7, 504.7.1, 504.7.2 AND FBC PL 607.3.
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM THE LAVATORY
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070.
 PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION FOR A TEMPERATURE LIMITING DEVICE FOR THE
 LAVATORY.
  
 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, SHOW ON THE
 FLOOR PLAN, THE ROUTING OF THE UNDERGROUND SANITARY TO
 THE EXTERIOR OF THE BUILDING.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A WATER
 RISER DIAGRAM SHOWING THE COLD WATER SERVICE, COLD
 WATER DISTRIBUTION AND HOT WATER DISTRIBUTION. WATER
 HEATER SHALL BE SHOWN. PROVIDE SIZES TO SATISFY FIXTURE
 DEMAND TO COMPLY WITH FBC PL 604.3, 604.4 AND 604.5.
 MINIMUM SIZE OF DISTRIBUTION PIPING SHALL BE ? INCH
 NOMINAL IN ACCORDANCE WITH INDUSTRY STANDARDS. MINIMUM
 SIZE OF WATER SERVICE SHALL BE 3/4"INCH PIPING AND
 SHALL BE PROVIDED WITH A FULL SIZED VALVE AT THE
 ENTRANCE TO THE STRUCTURE PER FBC PL 606.1(2). SPECIFY
 AND PROVIDE A BACKFLOW PREVENTOR FOR THE WATER SERVICE
 IN ACCORDANCE WITH FBC PL 608.1.
  
 8. PER WPB FBC 107.2.1, SUBMIT A SITE PLAN SHOWING THE
 FOLLOWING:
 A. THE BUILDING SEWER ROUTING AND CONNECTION TO
 EXISTING SANITARY BUILDING DRAIN/SEWER COMPLYING WITH
 FBC PL 703.4, OR TO AN APPROVED CITY LATERAL.
 B. THE WATER SERVICE ROUTING AND CONNECTION TO EXISTING
 SITE WATER.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 17100767 4012 GARDEN AVE
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-06-14 Cont ID  
Sent By gjohnson Date 2019-06-14 Time 17:11 Rev Time 0.00
Received By gjohnson Date 2019-06-14 Time 17:05 Sent To  
Notes
2019-06-14 17:17:523RD REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS THEIR HAS BEEN NO
 RESPONSE TO PREVIOUS COMMENTS YOU WILL NEED TO MEET
 WITH PLAN REVIEWER BEFORE RESUBMITTING PLEASE SEE
 CONTACT INFO BELOW.
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC
  
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 604.6 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
 COMPARTMENTS COMPLYING WITH 604.8.2.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 2. THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL
 HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS. PER FBC PL 904.1
  
 3. PLEASE PROVIDE WATER RISER DIAGRAM SHOWING LOCATION
 OF WATER HEATER. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 08:50 Rev Time 0.00
Received By jesmith Date 2018-12-18 Time 15:06 Sent To  
Notes
2018-12-20 08:50:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012
 5TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
 1. PLEASE SEE THE NOTES FROM THE LAST REVIEW DATED
 10/28/17.
 2. REVIEW ALL NOTES AND SUBMIT THE NEW PERMIT
 APPLICATION PACKAGE INCLUDING THE REQUIRED MISSING
 INFORMATION AS NOTED ON THE LAST REVIEW DATED
 10/28/2017.
 3. NEW COMMENT: TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 TO COMPLY WITH FBC PL 416.5
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-28 Cont ID  
Sent By gjohnson Date 2017-11-28 Time 13:47 Rev Time 0.00
Received By gjohnson Date 2017-11-28 Time 13:25 Sent To  
Notes
2017-11-28 14:01:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC
  
 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 604.6 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET EXCEPT IN AMBULATORY ACCESSIBLE
 COMPARTMENTS COMPLYING WITH 604.8.2.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 2. THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL
 HAVE NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS. PER FBC PL 904.1
  
 3. PLEASE PROVIDE WATER RISER DIAGRAM SHOWING LOCATION
 OF WATER HEATER. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2019-11-20 Cont ID  
Sent By awooten Date 2019-11-20 Time   Rev Time 0.00
Received By awooten Date 2019-11-20 Time   Sent To  
Notes
2019-11-20 14:54:15***********************ZONING REVIEW
 FAILED***************************
  
 PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL
 STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED
 IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW
 RESUBMITTAL.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-06-21 Cont ID  
Sent By awooten Date 2019-06-21 Time   Rev Time 0.00
Received By awooten Date 2019-06-21 Time   Sent To  
Notes
2019-06-21 15:38:23***********************ZONING REVIEW FAILED
 (REPEAT)***************************
  
 PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL
 STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED
 IS FOR 827 BRIGGS STREET. IS THE FOOTPRINT OF THE
 ACCESSORY BUIDLING INCREASING/CHANGING? FURTHER
 COMMENTS MAY FOLLOW RESUBMITTAL.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-10-30 Time   Rev Time 0.00
Received By awooten Date 2018-10-29 Time 13:33 Sent To  
Notes
2018-10-30 10:18:23***********************ZONING REVIEW
 FAILED***************************
  
 PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL
 STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED
 IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW
 RESUBMITTAL.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By AW Date 2017-11-27 Time   Rev Time 0.00
Received By awooten Date 2017-10-27 Time 15:02 Sent To  
Notes
2017-11-27 14:07:55***********************ZONING REVIEW
 FAILED***************************
  
 PROVIDE A COPY OF THE SURVEY FOR PROPERTY SHOWING ALL
 STRUCTURES ON PROPERTY. THE SURVEY THAT WAS SUBMITTED
 IS FOR 827 BRIGGS STREET. FURTHER COMMENTS MAY FOLLOW
 RESUBMITTAL.
  
 THANKS,
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449