Plan Review Details - Permit 17100726
Plan Review Stops For Permit 17100726
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-23 Cont ID  
Sent By cthroop Date 2018-01-23 Time 14:11 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By cthroop Date 2017-11-15 Time 17:11 Rev Time 0.00
Received By cthroop Date 2017-11-14 Time 10:35 Sent To  
Notes
2017-11-15 17:15:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IMPACT FEES REQUIRED.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE ICC-ES REPORT FOR PROPOSED ICYNENE
 INSULATION. DESIGNER TO IDENTIFY TYPE OF INSULATION
 WILL BE INSTALLED. PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS AT TIME OF INSPECTION.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By jleahy Date 2017-11-13 Time 17:56 Rev Time 0.00
Received By jleahy Date 2017-11-13 Time 17:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-23 Cont ID  
Sent By cthroop Date 2018-01-23 Time 14:11 Rev Time 0.00
Received By cthroop Date 2018-01-18 Time 14:04 Sent To I
Notes
2018-01-19 14:04:50RESUB ROUTED TO AWOOTEN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-29 Cont ID  
Sent By cpuell Date 2017-11-29 Time 08:55 Rev Time 0.00
Received By cpuell Date 2017-10-18 Time 15:14 Sent To  
Notes
2017-10-19 15:14:20R06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-01-23 Cont ID  
Sent By cthroop Date 2018-01-23 Time 14:11 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 13:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By cthroop Date 2017-11-15 Time 17:08 Rev Time 0.00
Received By cthroop Date 2017-11-15 Time 16:28 Sent To  
Notes
2017-11-15 17:09:33BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-11-27 Cont ID  
Sent By ccole Date 2017-11-27 Time 11:57 Rev Time 0.00
Received By ccole Date 2017-11-27 Time 11:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-11-13 Cont ID  
Sent By gjohnson Date 2017-11-13 Time 12:53 Rev Time 0.00
Received By gjohnson Date 2017-11-13 Time 10:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-01-23 Cont ID  
Sent By cthroop Date 2018-01-23 Time 14:11 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 13:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-11-15 Cont ID  
Sent By cthroop Date 2017-11-15 Time 17:09 Rev Time 0.00
Received By cthroop Date 2017-11-15 Time 17:07 Sent To  
Notes
2017-11-15 17:11:16BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-22 Cont ID  
Sent By AW Date 2018-01-22 Time 16:29 Rev Time 0.00
Received By awooten Date 2018-01-22 Time 15:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By AW Date 2017-11-28 Time   Rev Time  
Received By   Date 2017-11-28 Time   Sent To  
Notes
2017-11-28 15:09:49********************************ZONING REVIEW
 FAILED*************************************
  
 PROVIDE THE SETBACK FOR THE NEW AC UNIT.
 MECHANICAL EQUIPMENT. MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
 PROVIDE DIMENSION THE STRUCTURAL OVERHANGS.
 STRUCTURAL INTRUSIONS. STRUCTURAL OVERHANGS, INCLUDING
 BUT NOT LIMITED TO BALCONIES, CORNICES, GUTTERS, EAVES,
 AND ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER
 THAN THREE FEET INTO ANY SETBACK.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]