Plan Review Details - Permit 17100719
Plan Review Stops For Permit 17100719
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-08 Cont ID  
Sent By dharvey Date 2018-02-08 Time 14:54 Rev Time 0.00
Received By dharvey Date 2018-02-08 Time 14:47 Sent To  
Notes
2018-02-08 14:54:16MET WITH JESSE AT FRONT COUNTER. ALL RAILINGS ARE
 INTERIOR AND ARE ACTUALLY INTERIOR AND PERFORMING AS
 GUARDRAILS. IMPACT AND CONTINUOUS LOADS HAVE BEEN
 ACCOUNTED FOR BY THE ENGINEER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-06 Cont ID  
Sent By shill Date 2017-11-06 Time 09:09 Rev Time 0.00
Received By shill Date 2017-11-06 Time 09:09 Sent To I
Notes
2017-11-06 09:13:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLANS TO INCLUDE BUILDING HEIGHT. DESIGN
 PRESSURES APPEAR LOW FOR A HIGH RISE BUILDING.
  
 ALSO CLARIFY CALCULATIONS PREPARED BY MOHAMED W FAHMY,
 PE DATED 8/15/17 WHICH GIVES BUILDING HEIGHT AS 40'.
 BASED ON AERIALS, THIS PARCEL APPEARS TO HAVE ONE
 BUILDING WHICH HAS SEVERAL PORTIONS OF DIFFERENT
 HEIGHTS. IF NECESSARY, PROVIDE NEW CALCULATIONS.
  
 2. SEOR DID NOT SPECIFY DESIGN PRESSURES FOR THE
 COMPONENTS AND CLADDING. PLEASE CLARIFY; IS THIS
 DELEGATED ENGINEERING? IF YES, THE SEOR IS TO SPECIFY
 THE DESIGN CRITERIA (SUCH AS BUILDING HEIGHT). IF NOT
 DELEGATED ENGINEERING, SEOR IS TO SPECIFY DESIGN
 PRESSURES, FBC B 1609.
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By shill Date 2017-11-06 Time 09:14 Rev Time 0.00
Received By shill Date 2017-10-18 Time 15:23 Sent To  
Notes
2017-10-19 15:23:47SUBMITTAL ROUTED TO SHILL