Plan Review Details - Permit 17100716
Plan Review Stops For Permit 17100716
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-24 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-23 Time 10:14 Sent To  
Notes
2017-10-24 10:14:12RESUB ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-24 Cont ID  
Sent By ccole Date 2017-10-24 Time 15:00 Rev Time 0.00
Received By ccole Date 2017-10-24 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-19 Cont ID  
Sent By ccole Date 2017-10-19 Time 08:31 Rev Time 0.00
Received By ccole Date 2017-10-19 Time 07:58 Sent To  
Notes
2017-10-19 09:07:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100716
 10/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENGINEERING AND DESIGN CRITERIA BY
 WEIDER P.E IS INCORRECTLY SPECIFYING RISK CATEGORY II,
 HOWEVER THE CHURCH STRUCTURE FALLS UNDER RISK CATEGORY
 III PER TABLE 1604.5 FBC-14 BUILDING. REFER TO FIGURE
 1609B AND REVISE THE DESIGN CRITERIA AND INCREASE THE
 ULTIMATE WIND SPEED TO 180 MPH.
 A) DIGITAL SEALS AND SIGNATURES ARE ACCEPTABLE FOR
 ELECTRONIC SUBMITTALS. RAISED OR INK SEALS AND WET
 SIGNATURES ARE REQUIRED ON PAPER SUBMITTALS- PLEASE SEE
 SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
 B) THE CURRENT ENGINEERING DOES NOT INDICATE WHICH
 RTU'S ARE TO BE INSTALLED PER THE DETAILS SHOWN- PLEASE
 RESUBMIT ENGINEERING THAT SPECIFIES THE UNITS.
  
 2) PROVIDE ENGINEERING FOR THE REPLACEMENT OF THE 3
 SPLIT SYSTEM CONDENSERS. IF NEW AC ROOF STANDS ARE TO
 BE INSTALLED, PLEASE SUBMIT A PRODUCT APPROVAL OR NOA
 WITH APPROVAL STAMP BY THE ENGINEER OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  