Plan Review Details - Permit 17100569
Plan Review Stops For Permit 17100569
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-09 Cont ID  
Sent By cthroop Date 2017-11-09 Time 09:08 Rev Time 0.00
Received By cthroop Date 2017-11-09 Time 08:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-23 Cont ID  
Sent By cthroop Date 2017-10-23 Time 11:40 Rev Time 0.00
Received By cthroop Date 2017-10-23 Time 11:38 Sent To  
Notes
2017-10-23 11:42:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND
 THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON
 RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE.
  
 1. IDENTIFY LOCATION OF WORK FOR BOTH FLOORING AND
 BATHROOM RE-MODEL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-15 Cont ID  
Sent By cpuell Date 2017-11-15 Time 16:14 Rev Time 0.00
Received By cpuell Date 2017-11-13 Time 10:05 Sent To  
Notes
2017-11-14 10:05:56SENT TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-09 Cont ID  
Sent By cthroop Date 2017-11-09 Time 09:08 Rev Time 0.00
Received By cthroop Date 2017-11-07 Time 13:34 Sent To I
Notes
2017-11-08 13:34:24RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-23 Cont ID  
Sent By cthroop Date 2017-10-23 Time 11:40 Rev Time 0.00
Received By cthroop Date 2017-10-13 Time 16:33 Sent To  
Notes
2017-10-16 16:33:58ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-11-15 Cont ID  
Sent By thunt Date 2017-11-15 Time 15:34 Rev Time 0.00
Received By thunt Date 2017-11-15 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-11-08 Cont ID  
Sent By thunt Date 2017-11-08 Time 15:16 Rev Time 0.00
Received By thunt Date 2017-11-08 Time 15:16 Sent To  
Notes
2017-11-08 15:26:2611/8/17 2ND PLUMBING REVIEW**DENIED**
  
 1) PLEASE PROVIDE CLEAR FLOOR SPACE OUTLINE @ EACH
 REQUIRED PLUMBING FIXTURE AND LIST WHAT DESIGN SPEC
 MODEL YOU ARE USING. HUD 24CFR 100-205
  
 2) SHOW OVERALL CABINET HEIGHT MAX 34" COMPLING WITH
 FAIR HOUSING SECTION 100.205 (C) (3) (IV) SECTION (V)
  
  
 CALLED AND SPOKE TO MR.BURGOS ( ARCHITECT OF RECORD)
 AND ADVISED
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-19 Cont ID  
Sent By thunt Date 2017-10-19 Time 14:51 Rev Time 0.00
Received By thunt Date 2017-10-19 Time 14:50 Sent To  
Notes
2017-10-19 15:00:2010/19/17 PLUMBING 1ST REVIEW DENIED
  
 1) PROVIDE DESCRIPTION OF WORK THAT WILL BE DONE.
 (BATHROOM REMODEL) IS NOT CLEAR WHAT IS BEING DONE.FBC
 107.2.1
  
 2) PROVIDE CLEAR FLOOR SPACES FOR EACH FIXTURE AND
 CABINET HEIGHTS SHOWING COMPLIANCE WITH FAIR HOUSING
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  