Plan Review Details - Permit 17100404
Plan Review Stops For Permit 17100404
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 10:42 Rev Time 0.00
Received By cthroop Date 2017-11-22 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-16 Cont ID  
Sent By cthroop Date 2017-10-16 Time 11:38 Rev Time 0.00
Received By cthroop Date 2017-10-16 Time 09:59 Sent To P
Notes
2017-10-16 11:44:55BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. UNTIL INTERIOR BUILD-OUT (APPLICATION # 17100401)
 HAS BEEN APPROVED, THE CORRIDOR WALLS AND DOORS SHALL
 NOT BE REMOVED. THE 1-HR RATING OF THE CORRIDOR SHALL
 BE MAINTAINED.
 2. FLOOR PLAN APPEARS TO BE INCOMPLETE. CANNOT
 DETERMINE UNIT BOUNDARY LINES.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-08 Cont ID  
Sent By jleahy Date 2017-11-08 Time 10:43 Rev Time 0.00
Received By jleahy Date 2017-11-08 Time 10:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-13 Cont ID  
Sent By jleahy Date 2017-10-13 Time 16:55 Rev Time 0.00
Received By jleahy Date 2017-10-13 Time 16:55 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-22 Cont ID  
Sent By cthroop Date 2017-11-22 Time 10:42 Rev Time 0.00
Received By cthroop Date 2017-11-03 Time 10:57 Sent To I
Notes
2017-11-06 10:57:44RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-17 Cont ID  
Sent By gjohnson Date 2017-10-17 Time 07:37 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 14:15 Sent To  
Notes
2017-10-12 14:15:22ROUTED TO ELECTRICAL INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By gjohnson Date 2017-10-17 Time 07:34 Rev Time 0.00
Received By gjohnson Date 2017-10-17 Time 07:34 Sent To  
Notes
2017-10-17 07:36:581ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE NOTE ON THE PLAN AS TO THE SCOPE OF
 PLUMBING DEMO. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  