Plan Review Details - Permit 17100401
Plan Review Stops For Permit 17100401
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-16 Cont ID  
Sent By jwitmer Date 2017-11-16 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2017-11-14 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 10:58 Rev Time  
Received By jwitmer Date 2017-10-21 Time 10:01 Sent To  
Notes
2017-10-21 10:54:192014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100401
 ADD: 1515 N. FLAGLER DR. SUITE: 800
 CONT: LB DEVELOPMENT
 TEL: 954-709-1926
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 21/ 2017
 ACTION: DENIED
  
 1) SHEET A-1 THE FLOOR PLAN, THE CORRIDOR WALL IN FRONT
 OF THE TENANT SPACE HAS MANY WALL IDENTIFICATION TAGS
 SEE LIST;
 A- NEW WALL 6 INCHES ABOVE CEILING, NOT RATED
 C- NEW FIRE RATED WALL SEE SECTION 3/A2
 E- NEW WALL TO DECK NOT RATED
 F- EXISTING CORRIDOR WALL
 J- MAINTAIN 1 HOUR FIRE RATING 5/8 TYPE X
  
 PLEASE CORRECT THE DISCREPANCY IN THE PLANS. THE PAST
 BUILDING STANDARD WAS A 1 HOUR RATED WALL, OR THE
 DESIGNER COULD DESIGN TO MAINTAIN THE 1 HOUR FIRE
 RATING OR NOT. 2014 FBC-B TABLE 1018.1 FIRE SPRINKLERED
 NOT REQUIRED. DISCREPANCY IN PLANS, 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 12:30 Rev Time 0.00
Received By jpearson Date 2017-12-22 Time 12:30 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-11-16 Cont ID  
Sent By jpearson Date 2017-11-16 Time 15:46 Rev Time 0.00
Received By jpearson Date 2017-11-16 Time 15:46 Sent To  
Notes
2017-11-16 15:46:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL 2ND REVIEW STATUS: DENIED, SEE COMMENTS
 BELOW.
  
 PREVIOUS COMMENTS NOT ADDRESSED, PROVIDE RESPONSE FOR
 EACH ITEM:
  
 1. PROVIDE DETAILS OF GFCI RECEPTACLE REQUIRED ON ROOF
 WITHIN 25 FEET OF CU UNIT. NEC 210.63
 2. PROVIDE DETAILS OF RECEPTACLE CONTROL REQUIRED PER
 ASHRAE 90.1. THE NOTE SUPPLIED IS NOT ADEQUATE DETAIL,
 SHOW WHICH CIRCUITS/RECEPTACLES ARE CONTROLLED AND THE
 METHOD OF CONTROL. THE AREAS INCLUDED SHOULD BE: AT
 LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP RECEPTACLES IN
 ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED
 PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK
 ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. AT
 LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR
 MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION
 DOCUMENTS. ASHRAE 90.1, 8.4.2; FBC CE 405.7.1; FBC
 107.2.1
 3. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 ETC.. FBC 105.1, 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jpearson Date 2017-10-31 Time 10:42 Rev Time 0.00
Received By jpearson Date 2017-10-31 Time 10:42 Sent To  
Notes
2017-10-31 10:42:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DETAILS OF GFCI RECEPTACLE REQUIRED ON ROOF
 WITHIN 25 FEET OF CU UNIT. NEC 210.63
 2. PROVIDE DETAILS OF RECEPTACLE CONTROL REQUIRED PER
 ASHRAE 90.1. THE NOTE SUPPLIED IS NOT ADEQUATE DETAIL,
 SHOW WHICH CIRCUITS/RECEPTACLES ARE CONTROLLED AND THE
 METHOD OF CONTROL. THE AREAS INCLUDED SHOULD BE: AT
 LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP RECEPTACLES IN
 ALL PRIVATE OFFICES, CONFERENCE ROOMS, ROOMS USED
 PRIMARILY FOR PRINTING AND/OR COPYING FUNCTIONS, BREAK
 ROOMS, CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. AT
 LEAST 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR
 MODULAR FURNITURE NOT SHOWN ON THE CONSTRUCTION
 DOCUMENTS. ASHRAE 90.1, 8.4.2; FBC CE 405.7.1; FBC
 107.2.1
 3. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 ETC.. FBC 105.1, 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-08 Cont ID  
Sent By pleduc Date 2017-11-08 Time   Rev Time 0.00
Received By pleduc Date 2017-11-07 Time 16:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-13 Cont ID  
Sent By pleduc Date 2017-10-13 Time   Rev Time 0.00
Received By pleduc Date 2017-10-13 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 12:34 Rev Time 0.00
Received By jpearson Date 2017-12-21 Time 10:49 Sent To  
Notes
2017-12-22 10:49:16RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 15:42 Rev Time 0.00
Received By gjohnson Date 2017-11-03 Time 14:19 Sent To  
Notes
2017-11-06 14:20:03B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-31 Cont ID  
Sent By jpearson Date 2017-10-31 Time 10:42 Rev Time 0.00
Received By jpearson Date 2017-10-11 Time 14:38 Sent To  
Notes
2017-10-12 14:38:43B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 10:58 Rev Time  
Received By jwitmer Date 2017-10-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-11-14 Cont ID  
Sent By ccole Date 2017-11-13 Time 07:35 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By ccole Date 2017-10-26 Time 11:08 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 17:50 Sent To E
Notes
2017-10-26 11:11:101ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING CODE
 PERMIT #17100401
 10/26/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE ACTUAL LOCATION OF THE NEW CU-1 ON THE ROOF
 AND PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE STAND AND THE CONDENSER- SECTION 301.15.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By gjohnson Date 2017-11-17 Time 15:41 Rev Time 0.00
Received By gjohnson Date 2017-11-17 Time 10:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 12:06 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 12:06 Sent To  
Notes
2017-10-21 12:17:001ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH THE REAR WALL GRAB BAR SHALL BE
 36 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE
 OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND
 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC ACC
 604.5.2
  
 2. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1
 AND SHALL COMPLY WITH FBC ACC 602 IF ONE IS PROVIDED IN
 COMMON AREA PLEASE PLACE NOTE ON PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 4. A BACKFLOW IS REQUIRED ON THE ICE MAKER LINE. PER
 FBC PL 608.3
  
 5. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
 IF ONE IS PROVIDED IN COMMON AREA PLEASE PLACE NOTE ON
 PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  