Plan Review Details - Permit 17100292
Plan Review Stops For Permit 17100292
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By shill Date 2017-10-25 Time 16:55 Rev Time 0.00
Received By shill Date 2017-10-25 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-13 Cont ID  
Sent By shill Date 2017-10-13 Time 16:25 Rev Time 0.00
Received By shill Date 2017-10-13 Time 08:21 Sent To  
Notes
2017-10-13 11:52:45***CORRECTIONS***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2014
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. APPLICATION IS NOT CONSISTENT WITH THE PLANS;
 APPLICATION STATES THIS IS "INTERIOR DEMOLITION" BUT
 PLANS SHOW STRUCTURAL IMPROVEMENTS, PLEASE CLARIFY.
  
 2. PLEASE SEE FLORIDA DECLARATORY STATEMENT
 (WWW.FLORIDABUILDING.ORG) DS2014-61 REGARDING
 STRUCTURAL ALTERATIONS TO THRESHOLD BUILDINGS. IT
 APPEARS THAT THE PROPOSED WORK IS A STRUCTURAL
 ALTERATION TO A THRESHOLD BUILDING.
  
 THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 C) THRESHOLD BLDG., REQUIRED STATEMENT W.P.B. AMENDMENT
 110.3.7.4.4, FS553.79(7)(D): ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER
 633.
  
 3. PLEASE REVISE PLAN TO INCLUDE THRESHOLD INSPECTION
 PLAN AND TO INCLUDE THE REQUIRED THRESHOLD STATEMENT.
 WHEN RESUBMITTING, PROVIDE THREE SETS OF PLANS.
  
 THE SPECIAL INSPECTOR AGREEMENT AND RESUMES MAY BE SENT
 VIA EMAIL. RESUMES FOR THE SI, CONTRACTOR, AND JOB
 INSPECTOR(S) SHOWING EXPERIENCE WITH PROJECTS OF THIS
 TYPE ARE REQUIRED.
  
 (SI AGREEMENT AND G&P SENT TO [email protected] ON
 10/13/17)
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-27 Cont ID  
Sent By jpearson Date 2017-10-27 Time 15:45 Rev Time 0.00
Received By jpearson Date 2017-10-27 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By jpearson Date 2017-10-17 Time 13:49 Rev Time 0.00
Received By jpearson Date 2017-10-17 Time 07:32 Sent To  
Notes
2017-10-17 13:49:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MEP AND E SHEETS DO NOT SHOW PROJECT ADDRESS.
 PROVIDE CORRECTION. FBC 107.2.1
 2. PER THE INCLUDED SHEETS IN THE ELECTRICAL SHEET
 INDEX, SHEET E5.1 IS MISSING. PROVIDE CORRECTION. FBC
 107.2.1
 3. PERMIT APPLICATION AND PLAN STATES THAT THIS IS A
 DEMO PLAN, BUT THERE ARE SEVERAL ELECTRICAL SHEETS
 SHOWING NEW LIGHTING. REMOVE ANY SHEETS NOT RELEVANT TO
 DEMO. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-16 Cont ID  
Sent By scaldero Date 2017-10-16 Time 14:35 Rev Time 0.00
Received By scaldero Date 2017-10-16 Time 14:16 Sent To  
Notes
2017-10-16 14:37:34PERMIT # 17100292
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By jpearson Date 2017-10-27 Time 15:45 Rev Time 0.00
Received By jpearson Date 2017-10-20 Time 14:02 Sent To I
Notes
2017-10-27 14:55:1310/27 REMOVED FIRE STOP; RETAINED PAGE WITH FIRE STAMP
 FROM PREVIOUS REVIEW
  
2017-10-23 14:02:31B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-10 Time 14:31 Sent To  
Notes
2017-10-12 14:31:25B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-27 Cont ID  
Sent By ccole Date 2017-10-27 Time 11:14 Rev Time 0.00
Received By ccole Date 2017-10-27 Time 08:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-17 Cont ID  
Sent By ccole Date 2017-10-17 Time 16:00 Rev Time 0.00
Received By ccole Date 2017-10-17 Time 16:00 Sent To  
Notes
2017-10-17 16:12:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100292
 10/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MEP AND E SHEETS ARE MISSING FROM THE TABLE OF
 CONTENTS (PLAN INDEX) ON SHEET 1.1.
  
 2) THE ADDRESS OF THE PROJECT IS NOT SHOWN ON THE MEP
 AND E SHEETS.
  
 3) THE PROPOSED PROJECT IS FOR DEMOLITION ONLY. REMOVE
 ALL NOTES AND DETAILS PERTAINING TO NEW CONSTRUCTION.
  
 4) PROVIDE A SCOPE OF WORK FOR MECHANICAL DEMOLITION IN
 MECHANICAL ROOMS #2, 3, & 5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2017-10-16 Cont ID  
Sent By shill Date 2017-10-16 Time 07:00 Rev Time 0.00
Received By shill Date 2017-10-16 Time 07:00 Sent To  
Notes
2017-10-16 07:01:34THE ENTIRE STRUCTURE IS LOCATED IN AN X ZONE. PORTIONS
 OF THE PARKING LOT ARE LOCATED IN AE/BFE 14 ZONE.
 CHANGED THE FLOOD ZONE DESIGNATION IN THE ZONING TAB
 FROM AE TO X
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By gjohnson Date 2017-10-25 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2017-10-24 Time 16:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-16 Cont ID  
Sent By gjohnson Date 2017-10-16 Time 13:09 Rev Time 0.00
Received By gjohnson Date 2017-10-16 Time 10:59 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By shill Date 2017-10-25 Time 16:56 Rev Time 0.00
Received By shill Date 2017-10-25 Time 16:42 Sent To  
Notes
2017-10-23 18:02:10THRESHOLD INSPECTOR REQUIRED FOR THE ELEVATOR SHAFT
 EXTENSION ONLY
  
 CONTRACTOR IS VERDEX.
 SI IS JAMES FLAIG, PE, NUTTING ENGINEERS.
 JOB INSPECTOR IS JAMES HARPER, SR.
  
 SENT TO FILENET VIA EMAIL 10/23/17
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-10-13 Cont ID  
Sent By shill Date 2017-10-13 Time 12:54 Rev Time 0.00
Received By shill Date 2017-10-13 Time 12:54 Sent To  
Notes
2017-10-13 12:54:51SEE BUILDING COMMENTS
  