Plan Review Details - Permit 17100291
Plan Review Stops For Permit 17100291
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-04 Cont ID  
Sent By jwitmer Date 2017-12-04 Time 12:34 Rev Time 0.00
Received By jwitmer Date 2017-12-04 Time 11:58 Sent To  
Notes
2017-12-04 12:21:002014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100291
 ADD: 515 N. FLAGLER DR. SUITE: 800
 CONT: FINE LINE CONSTRUCTION CONTRACTORS, INC.
 TEL: 561-427-5664
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. DEC. 04/ 2017
 ACTION: BUILDING PROVISO
  
 1) SHEET A4.0.1 DETAIL # 2 & 3 THE RECEPTION DESK,
 COUNTERTOP, FINISH ELEVATION IS GIVEN TO BE 3 FOOT 8
 INCHES DOES NOT COMPLY WITH ACCESSIBILITY SECTION
 904.3.3 FOR CHECK WRITING SURFACES COMPLYING WITH 2014
 FBC-ACCESSIBILITY CODE 902.3.
 2014 ACCESSIBILITY CODE 226.1 IN ADDITION, WHERE WORK
 SURFACES ARE PROVIDED FOR USE BY OTHER THAN EMPLOYEES,
 SHALL COMPLY WITH 902.
  
 EXCEPTION: 1. SERVICE COUNTERS SHALL NOT BE REQUIRED TO
 COMPLY WITH 902.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2017-10-20 Time 16:56 Sent To  
Notes
2017-10-21 06:30:302014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17100291
 ADD: 515 N. FLAGLER DR. SUITE : 800
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 21/ 2017
 ACTION: DENIED
  
 1) SHEET A4.0.1 DETAIL # 10 THE KITCHEN SHOWS A
 MICROWAVE SITTING ON A SHELF 4 FOOT 8 INCHES ABOVE THE
 FINISH FLOOR. THIS IS WELL OUT OF THE REACH RANGES AND
 OPERABLE PARTS SEE THE 2014 FBC-ACCESSIBILITY CODE
 SECTIONS:
 1A) 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 1B) 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 2) SHEET A4.0.1 DETAIL # 2 & 3 THE RECEPTION DESK,
 COUNTERTOP, FINISH ELEVATION IS GIVEN TO BE 3 FOOT 8 ?
 INCHES DOES NOT COMPLY WITH ACCESSIBILITY SECTION
 904.3.3 FOR CHECK WRITING SURFACES COMPLYING WITH 902.3
 OR 904.4 FOR ACCESSIBLE SERVICE COUNTER.
  
 3) SHEET A1.1.1 AT DOOR # 801 SHOWS THE PROPOSED NEW
 CORRIDOR WALL TO BE A 1 HOUR FIRE RATED WALL AND THE
 NEW TENANT DOOR TO BE 45 MINUTE RATED. IT WOULD APPEAR
 THAT THE BUILDING STANDARD IS TO MAINTAIN THE 1 HOUR
 FIRE RATING WHICH IT WAS BUILT UNDER OR THE DESIGNER
 PREFERENCE SINCE IT IS CALLED OUT TO BE A 1 HOUR RATED
 WALL. SHEET A.2.0.1. DOOR SCHEDULE DOOR # 800 IS SHOWN
 TO BE A HERCULITE ALL GLASS DOOR WITH A WATER CURTAIN
 ON BOTH SIDES. PLEASE NOTE WATER CURTAINS ARE NOT
 ALLOWED ON DOORS, THE ONLY TIME YOU SEE THE USE OF A
 WATER CURTAIN IS IN SECTION 404.6 OF THE FBC-B THIS
 SECTION DEALS STRICTLY WITH ATRIUM SEPARATION AND THE
 GLAZING NEEDING TO BE A GASKETED FRAME, IN A GLASS
 WALL.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-11-02 Cont ID  
Sent By jleahy Date 2017-11-02 Time 16:58 Rev Time 0.00
Received By jleahy Date 2017-11-02 Time 16:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-28 Cont ID  
Sent By wjolin Date 2017-11-28 Time 14:21 Rev Time 0.00
Received By wjolin Date 2017-11-28 Time 14:18 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-12 Cont ID  
Sent By wjolin Date 2017-10-12 Time 10:46 Rev Time 0.00
Received By wjolin Date 2017-10-12 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-12-04 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-17 Time 10:40 Sent To  
Notes
2017-12-01 08:32:0412/1 TO JW DESK
  
2017-11-21 10:40:30RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-02 Cont ID  
Sent By jleahy Date 2017-11-02 Time 16:58 Rev Time 0.00
Received By jleahy Date 2017-10-10 Time 15:52 Sent To  
Notes
2017-10-11 15:52:16B13

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-21 Cont ID  
Sent By jwitmer Date 2017-10-21 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2017-10-20 Time 16:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By ccole Date 2017-10-25 Time 12:41 Rev Time 0.00
Received By ccole Date 2017-10-25 Time 12:41 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 11:13 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved