Plan Review Details - Permit 17100279
Plan Review Stops For Permit 17100279
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By rmcdouga Date 2018-03-23 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2018-03-23 Time 18:12 Sent To  
Notes
2018-03-23 18:46:07APPROVED WITH EXCEPTIONS
 BUILDING PROVISO
  
 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR
 OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE
 REQUIRED INSPECTIONS. PLEASE BE ADVISED THE INSPECTOR
 MAY REQUIRE PREVIOUSLY COMPLETED WORK TO BE MADE
 ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) A SET OF THE APPROVED PLANS FROM THE EXPIRED PERMIT
 (#06050833) HAS BEEN PROVIDED FOR REFERENCE AND TO AID
 THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC
 107.2.1.3
  
 3) A SET OF THE APPROVED PRODUCT APPROVALS FROM THE
 EXPIRED PERMIT (#06050833) HAS BEEN PROVIDED FOR
 REFERENCE AND TO AID THE INSPECTORS WITH THEIR FIELD
 INSPECTIONS. FBC 107.2.1.3 THE RECORDS INDICATE THAT
 THE FOLLOWING STRUCTURAL INSPECTIONS WERE APPROVED: 114
 - SLAB, 105 - FOOTING, 120 - BEAM/COLUMN, 111 - ROOF
 FRAMING, 118 - ROOF SHEATHING, AND A 119 WINDOW/DOOR
 BUCK. SEE ATTACHED COPY OF INSPECTION RESULTS FROM
 EXPIRED PERMIT (#06050833).
  
 4) OWNER/AGENT TO SIGN AND DATE ENERGY FORM.
  
 5) SUBMIT TWO SETS OF INSTALLATION INSTRUCTION FOR THE
 TAMKO ASPHALT SINGLES.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 16:21 Sent To  
Notes
2018-01-08 18:42:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR
 OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE
 REQUIRED INSPECTIONS.
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) OBTAIN A SET OF THE APPROVED PLANS THAT EXPIRED
 (PERMIT #06050833) AND SUBMIT THEM WITH THE NEW PLANS
 FOR REFERENCE AND TO AID THE INSPECTORS WITH THEIR
 FIELD INSPECTIONS. FBC 107.2.1.3 (CONTACT CRAIG
 MCPHERSON AT 561-805-6684 OR [email protected] TO
 OBTAIN COPIES FROM OUR FILES.)
  
 3) SUBMIT A SET OF THE APPROVED PRODUCT APPROVALS FOR
 THE EXPIRED PERMIT AND SUBMIT THEM FOR REFERENCE AND TO
 AID THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC
 107.2.1.3
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-11-03 Cont ID  
Sent By rmcdouga Date 2017-11-03 Time 19:01 Rev Time 0.00
Received By rmcdouga Date 2017-11-03 Time 16:08 Sent To  
Notes
2017-11-03 18:32:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERMIT (#06050833) FOR THE ADDITION TO THE REAR
 OF THE STRUCTURE EXPIRED PRIOR TO RECEIVING ALL OF THE
 REQUIRED INSPECTIONS.
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 2) OBTAIN A SET OF THE APPROVED PLANS THAT EXPIRED
 (PERMIT #06050833) AND SUBMIT THEM WITH THE NEW PLANS
 FOR REFERENCE AND TO AID THE INSPECTORS WITH THEIR
 FIELD INSPECTIONS. FBC 107.2.1.3 (CONTACT CRAIG
 MCPHERSON AT 561-805-6684 OR [email protected] TO
 OBTAIN COPIES FROM OUR FILES.)
  
 3) SUBMIT A SET OF THE APPROVED PRODUCT APPROVALS FOR
 THE EXPIRED PERMIT AND SUBMIT THEM FOR REFERENCE AND TO
 AID THE INSPECTORS WITH THEIR FIELD INSPECTIONS. FBC
 107.2.1.3
  
 4) SPECIFY THE ATTACHEMENT OF THE 4 X 6 WOOD POSTS TO
 THE GLULAM BEAM IN THE DETAIL ON 4.1. FBC-R 301.1
  
 5) THE NOTES FOR THE UPTURN BEAM ON SHEETS 2.1 AND 3.1
 STATE, "SEE DETAIL THIS SHEET.". THERE IS NO DETAIL FOR
 THE UPTURN BEAM ON THESE SHEETS. PLEASE CORRECT. FBC
 107.2.1
  
 6) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO
 SPECIFY 8D RING SHANK NAILS PER FBC-R 803.2.3.1.
  
 7) REVISE THE TYPICAL WALL SECTION ON SHEET 4.1 TO
 SPECIFY A DOUBLE LAYER OF UNDERLAYMENT AS REQUIRED BY
 FBC-R 905.2.2 FOR ROOF SLOPES LESS THAN 4:12.
  
 8) SHOW COMPLIANCE WITH FBC-R 314.3.1 WHEN ALTERATIONS,
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-03-22 Cont ID  
Sent By jpearson Date 2018-03-22 Time 07:49 Rev Time 0.00
Received By jpearson Date 2018-03-22 Time 07:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-05 Cont ID  
Sent By jpearson Date 2018-01-05 Time 07:39 Rev Time 0.00
Received By jpearson Date 2018-01-05 Time 06:32 Sent To  
Notes
2018-01-05 07:39:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS:
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3 (NOT SHOWN ON PLAN.)
 7. CORRECTED.
  
 NEW COMMENT:
 8. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481, 481.229
  
 END OF COMMENTS.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-31 Cont ID  
Sent By jpearson Date 2017-10-31 Time 08:15 Rev Time 0.00
Received By jpearson Date 2017-10-31 Time 08:15 Sent To  
Notes
2017-10-31 08:15:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BLOCK NOTE STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 2. SHOW ALL SMOKE AND CO ALARMS IN HOUSE. PLAN
 CURRENTLY ONLY SHOWS NEW AREA FOR THESE ALARMS. IF NONE
 ARE EXISTING, OR NOT TO CODE, PROVIDE AS NEW
 INSTALLATION. FBC R314.3, FBC 107.2.1
 3. PANEL SCHEDULE SHOWS TWO AHU'S AT 10KW EACH, BUT THE
 LOAD CALCULATION SHOWS ONE AT 10 KW AND ONE AT 1 KW.
 PROVIDE CORRECTED LOAD CALCULATION. NEC 220; FBC
 RE3602.3
 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE4003.11
 5. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION.
 NEC 410.16; FBC RE4003.12
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 7. FOR AHU INSTALLED IN ATTIC, CODE REQUIRES: "A
 LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34." PROVIDE RECEPTACLE OUTLET
 PER CODE. FBC-RE M1305.1.3.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-03-28 Cont ID  
Sent By eschneid Date 2018-03-28 Time 15:36 Rev Time 0.00
Received By eschneid Date 2018-03-19 Time 11:16 Sent To  
Notes
2018-03-20 11:17:32R23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-05 Cont ID  
Sent By eschneid Date 2018-02-05 Time 11:19 Rev Time 0.00
Received By eschneid Date 2017-12-27 Time 08:49 Sent To  
Notes
2017-12-28 08:49:38R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By rmcdouga Date 2017-11-06 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2017-10-10 Time 13:55 Sent To  
Notes
2017-10-11 13:55:35R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By rmcdouga Date 2017-11-03 Time 17:41 Rev Time 0.00
Received By rmcdouga Date 2017-11-03 Time 16:11 Sent To  
Notes
2017-11-06 07:20:06IMPACT FEES PAID UNDER EXPIRED PERMIT #06050833.
 P.R. #06-62005 PAID $2347.26

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By rmcdouga Date 2018-03-23 Time 18:12 Rev Time 0.00
Received By rmcdouga Date 2018-03-23 Time 16:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 17:37 Sent To  
Notes
2018-01-08 18:38:50PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 3) SPECIFY THE MODEL NUMBERS AND SPECIFICATIONS FOR THE
 HEATING AND COOLING EQUIPMENT, THAT MATCHES THE
 EQUIPMENT SIZING CALCULATIONS, ON THE PLANS. AIR
 HANDLER INFORMATION IS MISSING. PROVIDE AHRI
 CERTIFICATIONS FOR THE EQUIPMENT. FBC-R M1401.3
  
 4) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-06 Cont ID  
Sent By rmcdouga Date 2017-11-06 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2017-11-06 Time 06:50 Sent To I
Notes
2017-11-06 08:18:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 3) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 4) SPECIFY THE MODEL NUMBERS AND SPECIFICATIONS FOR THE
 HEATING AND COOLING EQUIPMENT, THAT MATCHES THE
 EQUIPMENT SIZING CALCULATIONS, ON THE PLANS. PROVIDE
 AHRI CERTIFICATIONS FOR THE EQUIPMENT. FBC-R M1401.3
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-03-23 Cont ID  
Sent By rmcdouga Date 2018-03-23 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2018-03-23 Time 15:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 17:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-23 Cont ID  
Sent By thunt Date 2017-10-23 Time 15:29 Rev Time 0.00
Received By thunt Date 2017-10-23 Time 15:29 Sent To  
Notes
2017-10-23 15:42:1410/23/17 1ST PLUMBING REVIEW DENIED
  
 1) VALUE SEEMS LOW AND APPREARS TO HAVE BEEN CHANGED
 AFTER QUALIFIER FILL OUT APPLICATION. PROVIDE BONA FIDE
 SIGED CONTRACT FBC 109.3
  
 2) PROVIDE SANITARY ISOMETRIC DRAWNING OF THE PLUMBING
 SYSTEM FBC 107.2.1
  
 3) SHOW SIZING AND SOURCE OF HOT WATER FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-03-23 Cont ID  
Sent By rmcdouga Date 2018-03-23 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2018-03-23 Time 14:48 Sent To  
Notes
2018-03-23 15:19:55TAMKO ASPHALT SHINGLES, FL1956-R12 ( NEEDS TO SUBMIT
 INSTALLATION INSTRUCTIONS.)

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-01-08 Cont ID  
Sent By rmcdouga Date 2018-01-08 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2018-01-08 Time 18:43 Sent To  
Notes
2018-01-08 18:55:261) THE ROOFING PERMIT FOR THE ADDITION EXPIRED WITHOUT
 AN APPROVED FINAL INSPECTION. YOU ARE REQUIRED TO
 ACQUIRE A ROOFING PERMIT IN ORDER TO GET THE ROOFING
 FINAL INSPECTION APPROVED.
  
 2) SUBMIT TWO SETS OF THE PRODUCT APPROVALS FOR THE
 ASPHALT ROOF SHINGLES. FBC 107.3.4
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-03-28 Cont ID  
Sent By eschneid Date 2018-03-28 Time 15:35 Rev Time 0.25
Received By eschneid Date 2018-03-28 Time 15:21 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By ES Date 2018-01-22 Time 11:08 Rev Time 0.25
Received By eschneid Date 2018-01-19 Time 15:40 Sent To  
Notes
2018-01-22 11:11:27FAILED
  
 1) REPEAT COMMENT: THE ORIGINAL EXPIRED PERMIT WAS FOR
 AN ADDITION. PROVIDE TWO COPIES OF A SURVEY SHOWING THE
 SETBACKS FOR THE BUILDING.
  
 2) REPEAT COMMENT: THE SURVEY NEEDS TO SHOW THE
 PROPOSED LOCATION OF THE NEW AC UNIT AND THE PAD. THE
 A/C UNIT AND PAD NEED TO BE SHOWN TO SCALE. THE SETBACK
 DIMENSION FROM THE A/C UNIT AND THE PAD MUST BE SHOWN
 TO THE PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By eschneid Date 2017-11-01 Time 14:49 Rev Time 0.50
Received By eschneid Date 2017-11-01 Time 14:49 Sent To  
Notes
2017-11-01 14:54:13FAILED
  
 1) THIS ORIGINAL PERMIT WAS FOR AN ADDITION. PROVIDE
 TWO COPIES OF A SURVEY SHOWING THE SETBACKS FOR THE
 BUILDING.
  
 2) THE SURVEY NEEDS TO SHOW THE PROPOSED LOCATION OF
 THE NEW AC UNIT AND THE PAD. THE A/C UNIT AND PAD NEED
 TO BE SHOWN TO SCALE. THE SETBACK DIMENSION FROM THE
 A/C UNIT AND THE PAD MUST BE SHOWN TO THE PROPERTY
 LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]