Plan Review Details - Permit 17100262
Plan Review Stops For Permit 17100262
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-06 Time 10:21 Sent To  
Notes
2017-11-07 10:21:32RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-18 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-16 Time 13:47 Sent To  
Notes
2017-10-17 13:47:28RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-10-12 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-06 Time 10:36 Sent To  
Notes
2017-10-10 10:36:57ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-08 Cont ID  
Sent By ccole Date 2017-11-08 Time 08:09 Rev Time 0.00
Received By ccole Date 2017-11-08 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-18 Cont ID  
Sent By ccole Date 2017-10-18 Time 14:08 Rev Time 0.00
Received By ccole Date 2017-10-18 Time 14:08 Sent To  
Notes
2017-10-18 14:20:462ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17100262
 10/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGY FORM R402-2014 IS NOT FILLED
 OUT CORRECTLY. PLEASE SEE THE SCOPE AT THE TOP OF THE
 FORM WHERE IT STATES "TO COMPLY, A BUILDING MUST MEET
 OR EXCEED ALL OF THE ENERGY EFFICIENCY REQUIREMENTS ON
 TABLE 402A....." THE SUBMITTED TABLE R402A IS
 "EXISTING" WHERE ACTUAL VALUES MUST BE FILLED IN.
 PLEASE NOTE THE SCOPE INDICATES OTHER METHODS OF
 COMPLIANCE IF NECESSARY WHICH INCLUDES USING THE
 ENERGYGAUGE PERFORMANCE BASED METHOD UNDER SECTION
 R405. PLEASE PROVIDE TWO SETS OF REVISED COMPLIANCE
 FORMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By ccole Date 2017-10-12 Time 12:04 Rev Time 0.00
Received By ccole Date 2017-10-12 Time 12:04 Sent To  
Notes
2017-10-12 12:20:241ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL, ENERGY
 CONSERVATION CODES
 PERMIT #17100262
 10/12/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENERGY CONSERVATION COMPLIANCE IS REQUIRED IN
 ACCORDANCE WITH SECTION R101.4.5 CHANGE IN SPACE
 CONDITIONING.:
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE. PLEASE SEE SECTION
 TABLE R101.5.1 AND SUBMIT A COMPLIANCE REPORT.
  
 2) THE TRANSFER DUCT FROM THE MASTER BEDROOM IS
 UNDERSIZED PER SECTION M1602.4 EXCEPTION 1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  