2017-10-23 07:40:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. TWO LAYERS OF ROOFING UNDERLAYMENT REQUIRED PER FBCR
 905.2.7.
 2. ROOFING PERMIT REQUIRED.
 3. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS.
  
 R905.2.7 UNDERLAYMENT APPLICATION.
 UNDERLAYMENT SHALL BE INSTALLED USING ONE OF THE
 FOLLOWING METHODS:
  
 1. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 UNDERLAYMENT SHALL COMPLY WITH ASTM D 226, TYPE I OR
 TYPE II OR ASTM D 4869, TYPE II OR TYPE IV OR ASTM D
 6757 AND SHALL BE TWO LAYERS APPLIED IN THE FOLLOWING
 MANNER. APPLY A 19-INCH (483 MM) STRIP OF UNDERLAYMENT
 FELT PARALLEL TO AND STARTING AT THE EAVES, FASTENED
 SUFFICIENTLY TO HOLD IN PLACE. STARTING AT THE EAVE,
 APPLY 36-INCH-WIDE (914 MM) SHEETS OF UNDERLAYMENT,
 OVERLAPPING SUCCESSIVE SHEETS 19 INCHES (483 MM), AND
 FASTENED WITH A 1-INCH (25 MM) ROUND PLASTIC CAP, METAL
 CAP NAILS OR NAILS AND TIN-TABS ATTACHED TO A NAILABLE
 DECK WITH ONE ROW IN THE FIELD OF THE SHEET WITH A
 MAXIMUM FASTENER SPACING OF 12 INCHES (305 MM) O.C.,
 AND ONE ROW AT THE OVERLAPS FASTENED 6 INCHES (152 MM)
 O.C. SYNTHETIC UNDERLAYMENT SHALL BE FASTENED IN
 ACCORDANCE WITH THIS SECTION AND THE MANUFACTURER?S
 RECOMMENDATIONS.
  
 2. FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE) OR GREATER. UNDERLAYMENT
 SHALL COMPLY WITH ASTM D 226, TYPE II OR ASTM D 4869,
 TYPE IV OR ASTM D 6757 AND SHALL BE ONE LAYER APPLIED
 IN THE FOLLOWING MANNER. UNDERLAYMENT SHALL BE APPLIED
 SHINGLE FASHION, PARALLEL TO AND STARTING FROM THE EAVE
 AND LAPPED 2 INCHES (51 MM), FASTENED WITH 1-INCH (25
 MM) ROUND PLASTIC CAP, METAL CAP NAILS OR NAILS AND
 TIN-TABS ATTACHED TO A NAILABLE DECK WITH TWO STAGGERED
 ROWS IN THE FIELD OF THE SHEET WITH A MAXIMUM FASTENER
 SPACING OF 12 INCHES (305 MM) O.C., AND ONE ROW AT THE
 OVERLAPS FASTENED 6 INCHES (152 MM) O.C. SYNTHETIC
 UNDERLAYMENT SHALL BE FASTENED IN ACCORDANCE WITH THIS
 SECTION AND THE MANUFACTURER?S RECOMMENDATIONS END LAPS
 SHALL BE OFFSET BY 6 FEET (1829 MM).
  
 3. AS AN ALTERNATIVE, THE ENTIRE ROOF DECK SHALL BE
 COVERED WITH AN APPROVED SELF-ADHERING POLYMER MODIFIED
 BITUMEN SHEET MEETING ASTM D 1970 OR AN APPROVED
 SELF-ADHERING SYNTHETIC UNDERLAYMENT INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By cthroop Date 2017-10-27 Time 13:48 Rev Time 0.00
Received By cthroop Date 2017-10-26 Time 10:11 Sent To I
Notes
2017-10-27 10:11:16RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-23 Cont ID  
Sent By cthroop Date 2017-10-23 Time 07:36 Rev Time 0.00
Received By cthroop Date 2017-10-06 Time 15:23 Sent To  
Notes
2017-10-10 15:24:11ROUTED TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2017-10-18 Cont ID  
Sent By ajones Date 2017-10-18 Time 15:15 Rev Time 0.00
Received By ajones Date 2017-10-11 Time 16:48 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved