Plan Review Details - Permit 17100259
Plan Review Stops For Permit 17100259
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By shill Date 2017-10-12 Time 13:54 Rev Time 0.00
Received By shill Date 2017-10-12 Time 13:54 Sent To  
Notes
2017-10-12 13:54:35***CORRECTIONS****
 REVISED 10/19/17
 LETTER RE: ACCESSIBILITY LETTER RECEIVED VIA EMAIL,
 REMOVED COMMENT
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2014
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK
  
 2. SEE CITY OF WEST PALM BEACH ORDINANCE 4729-17, SEC.
 18-283 (C),
  
 (C) BUILDINGS, STRUCTURES AND FACILITIES EXEMPT FROM
 THE FLORIDA BUILDING CODE. PURSUANT TO THE REQUIREMENTS
 OF FEDERAL REGULATION FOR PARTICIPATION IN THE NATIONAL
 FLOOD INSURANCE PROGRAM (44 C.F.R. SECTIONS 59 AND 60),
 FLOODPLAIN DEVELOPMENT PERMITS OR APPROVALS SHALL BE
 REQUIRED FOR THE FOLLOWING BUILDINGS, STRUCTURES AND
 FACILITIES THAT ARE EXEMPT FROM THE FLORIDA BUILDING
 CODE AND ANY FURTHER EXEMPTIONS PROVIDED BY LAW, WHICH
 ARE SUBJECT TO THE REQUIREMENTS OF THIS ARTICLE:
  
 (3) TEMPORARY BUILDINGS OR SHEDS USED EXCLUSIVELY FOR
 CONSTRUCTION PURPOSES.
 (4) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY
 OFFICES.
  
 THE PROPOSED LOCATION IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA WITH A BFE OF 6'NAVD88 (OR AS DETERMINED BY
 THE FLOOD INSURANCE STUDY), AND PER CITY OF WEST PALM
 BEACH ORDINANCE 4729-17, SEC. 18-34(A) AND (B), TWO
 FEET FREEBOARD REQUIRED (DESIGN FLOOR ELEVATION, DFE).
  
 PROVIDE A SURVEY WHICH SHOWS THE ELEVATION AT THE
 PROPOSED LOCATION. REVISE THE PLAN TO SHOW THE PROPOSED
 ELEVATION OF THE PROPOSED STRUCTURE.
  
 ANY ELEMENTS BELOW DFE ARE TO BE DESIGNED TO RESIST
 FLOOD LOADS. ALL EQUIPMENT AND FINISHED FLOOR TO BE AT
 OR ABOVE DFE.
  
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-20 Cont ID  
Sent By jleahy Date 2017-10-20 Time 17:10 Rev Time 0.00
Received By jleahy Date 2017-10-20 Time 17:09 Sent To Z
Notes
2017-10-20 17:10:51FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT AN ELECTYRICAL PERMIT SHOWING A RISER
 DIAGRAM AND LOCATION ON PROPERTY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-10-12 Cont ID  
Sent By wjolin Date 2017-10-12 Time 09:22 Rev Time 0.00
Received By wjolin Date 2017-10-12 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-27 Cont ID  
Sent By cpuell Date 2017-10-27 Time 10:42 Rev Time 0.00
Received By cpuell Date 2017-10-06 Time 09:24 Sent To  
Notes
2017-10-11 09:24:41B07

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By shill Date 2017-10-12 Time 13:29 Rev Time 0.00
Received By shill Date 2017-10-12 Time 13:28 Sent To  
Notes
2017-10-12 13:29:17SEE BUILDING REVIEW
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-27 Cont ID  
Sent By LL Date 2017-10-27 Time   Rev Time 0.00
Received By llouie Date 2017-10-26 Time 14:39 Sent To I
Notes
2017-10-27 09:07:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CLEARLY SHOW SETBACK DIMENSIONS FROM THE PROPERTY
 LINES. PLEASE NOTE THAT THE TRAILER MUST BE SETBACK AT
 MINIMUM OF 5 FT. FROM THE SIDE PROPERTY LINE AND 25 FT.
 FROM THE FRONT PROPERTY LINE. [ZLDR S.94-304]
  
 NOTES:
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  