Plan Review Details - Permit 17100242
Plan Review Stops For Permit 17100242
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-31 Cont ID  
Sent By shill Date 2017-10-31 Time 06:51 Rev Time 0.00
Received By shill Date 2017-10-31 Time 06:51 Sent To I
Notes
2017-10-31 06:52:09STAMPED DELEGATED ENGINEERING
 RETAINED 1 SET OF SHOP DRAWINGS & ENGINEERING/CALCS
  
 ****PROVISO****
 ISSUED AT APPLICANT'S RISK
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE NOTE THAT THE BOTTOM RISER IS SHOWN GRAPHICALLY
 AS SMALLER THAN THE OTHER RISERS (FBC B 1009.7.4), AND
 ONE DIMENSION APPEARS TO SHOW A 7 5/8" RISER DIMENSION
 (SHOULD BE 7" MAX, FBC B 1009.7.2).
  
 A COMPREHENSIVE PLAN REVIEW IS NOT PERFORMED ON
 DELEGATED ENGINEERING AS THE ENGINEERING IS TO COMPLY
 WITH THE FLORIDA BUILDING CODE AND THE
 APPROVED/REVIEWED PLAN. DEVIATION FROM THE PLANS AND/OR
 FBC IS TO BE SUBMITTED AS A REVISION FROM THE DESIGNER
 OF RECORD.
  
 INSTALLATION TO BE IN ACCORDANCE WITH THE REVIEWED
 PLANS (PERMIT DOCUMENTS) PERMITTED UNDER MASTER PERMIT
 #15020937 AND FBC 2014. ANY DEVIATION FROM THE ISSUED
 MASTER PERMIT OR FBC 2014 IS REQUIRED TO BE SUBMITTED
 AS A REVISION, PREPARED BY DESIGNER OF RECORD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 07:07 Rev Time 0.00
Received By shill Date 2017-10-26 Time 07:07 Sent To  
Notes
2017-10-26 07:10:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE SUBMITTAL INCLUDES SHOP DRAWINGS WHICH ARE NOT
 DELEGATED ENGINEERING. PLEASE REMOVE FROM THIS
 SUBMITTAL AND PROVIDE AT INSPECTION; THEY DO REQUIRE
 PLAN REVIEW.
  
 2. ONLY ONE SET OF THE SIGNED AND SEALED DRAWINGS WERE
 SUBMITTED (DELEGATED ENGINEERING; STEEL STAIRS). PLEASE
 NOTE THAT THE BOTTOM RISER IS SHOWN GRAPHICALLY AS
 SMALLER THAN THE OTHER RISERS (FBC B 1009.7.4), AND ONE
 DIMENSION APPEARS TO SHOW A 7 5/8" RISER DIMENSION
 (SHOULD BE 7" MAX, FBC B 1009.7.2).
  
 A COMPREHENSIVE PLAN REVIEW IS NOT PERFORMED ON
 DELEGATED ENGINEERING AS THE ENGINEERING IS TO COMPLY
 WITH THE FLORIDA BUILDING CODE AND THE
 APPROVED/REVIEWED PLAN. DEVIATION FROM THE PLANS AND/OR
 FBC IS TO BE SUBMITTED AS A REVISION FROM THE DESIGNER
 OF RECORD. THEREFORE, AFTER TWO ADDITIONAL SETS OF
 STAIR DELEGATED ENGINEERING ARE SUBMITTED, THIS WILL BE
 ISSUED WITH PROVISO:
  
 PROVISO:
 INSTALLATION TO BE IN ACCORDANCE WITH THE REVIEWED
 PLANS (PERMIT DOCUMENTS) PERMITTED UNDER MASTER PERMIT
 #15020937 AND FBC 2014. ANY DEVIATION FROM THE ISSUED
 MASTER PERMIT OR FBC 2014 IS REQUIRED TO BE SUBMITTED
 AS A REVISION, PREPARED BY DESIGNER OF RECORD.
  
 3. WHEN RESUBMITTING, REMOVE OLD SHEETS (IN THIS CASE,
 THE SHOP DRAWINGS) AND PUT TOGETHER THREE IDENTICAL
 COLLATED SETS OF ENGINEERING ONLY FOR SUBMITTAL
 ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-12 Cont ID  
Sent By shill Date 2017-10-12 Time 15:44 Rev Time 0.00
Received By shill Date 2017-10-12 Time 15:44 Sent To  
Notes
2017-10-12 15:47:56SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FAC 61G15-30.006, DELEGATED ENGINEERING IS TO BE
 REVIEWED BY STRUCTURAL ENGINEER OF RECORD. EVIDENCE OF
 THIS MAY BE PROVIDED BY EITHER A SHOP DRAWING REVIEW
 STAMP OR A LETTER.
  
 2. PLEASE COORDINATE WITH KEN CONRAD, CHIEF BUILDING
 INSPECTOR, REGARDING DOCUMENTS TO BE SUBMITTED FOR
 REVIEW. IF HE DETERMINES THAT THIS SUBMITTAL MAY BE
 PROVIDED IN THE FIELD RATHER THAN SUBMITTED FOR PLAN
 REVIEW, PLEASE ADVISE AND THIS SUBMITTAL WILL BE
 REVOKED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-26 Cont ID  
Sent By shill Date 2017-10-26 Time 07:10 Rev Time 0.00
Received By shill Date 2017-10-23 Time 10:20 Sent To  
Notes
2017-10-25 10:20:51RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-12 Cont ID  
Sent By shill Date 2017-10-12 Time 15:48 Rev Time 0.00
Received By shill Date 2017-10-06 Time 14:50 Sent To  
Notes
2017-10-10 14:50:38SUBMITTAL ROUTED TO SHILL