Plan Review Details - Permit 17090775
Plan Review Stops For Permit 17090775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-12-15 Cont ID  
Sent By rmcdouga Date 2017-12-15 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2017-12-14 Time 10:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-18 Cont ID  
Sent By rmcdouga Date 2017-10-18 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2017-10-18 Time 15:24 Sent To  
Notes
2017-10-18 15:36:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF CONSTRUCTION DOCUMENTS THAT SHOW
 THE EXISTING FLOOR PLAN AND THE PROPOSED FLOOR PLAN.
 PROVIDE STRUCTURAL DETAILS OF THE NEW ROOF OPENING FOR
 THE SKYLIGHT. FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE NEW
 SKYLIGHT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE SKYLIGHTS.
  
 3) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND
 COMPONENT AND CLADDING DESIGN PRESSURES PURSUANT TO
 FBC-R301.2.
  
 4) SHOW COMPLIANCE WITH FBC - R314.3.1 WHEN
 ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By jleahy Date 2017-12-13 Time 12:13 Rev Time 0.00
Received By jleahy Date 2017-12-13 Time 11:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-19 Cont ID  
Sent By jleahy Date 2017-10-19 Time 14:05 Rev Time 0.00
Received By jleahy Date 2017-10-19 Time 14:05 Sent To HIST
Notes
2017-10-19 14:06:38FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, NEED DRAWINGS INDICATING WHAT
 ELECTRICAL WORK WILL BE PERFORMED.

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By fmittner Date 2017-11-06 Time 10:39 Rev Time 0.00
Received By fmittner Date 2017-11-06 Time 10:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-15 Cont ID  
Sent By rmcdouga Date 2017-12-15 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2017-12-07 Time 14:32 Sent To  
Notes
2017-12-07 14:32:10R12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-06 Cont ID  
Sent By cpuell Date 2017-11-06 Time 13:35 Rev Time 0.00
Received By cpuell Date 2017-09-29 Time 11:27 Sent To  
Notes
2017-10-02 11:27:29R25

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-12-13 Cont ID  
Sent By lcrespo Date 2017-12-13 Time 16:10 Rev Time 0.00
Received By lcrespo Date 2017-12-13 Time 16:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-13 Cont ID  
Sent By lcrespo Date 2017-10-13 Time 13:43 Rev Time 0.00
Received By lcrespo Date 2017-10-13 Time 13:43 Sent To  
Notes
2017-10-13 13:48:331ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 PROVIDE PLUMBING RISER DIAGRAM AS STATED ON CONTRACT
 AND PER WPB AMEND TO FBC 107.3.5.3(11)
  
 PROVIDE FLOOR PLAN SHOWING WHOLE HOUSE AS STATED ON
 CONTRACT AND PER WPB AMEND TO FBC 107.2.1
  
 SUBMIT SPECS FOR SHOWER CONTROLS VALES FBC P2708.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  