Plan Review Details - Permit 17090693
Plan Review Stops For Permit 17090693
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-03 Cont ID  
Sent By cthroop Date 2018-01-03 Time 13:11 Rev Time 0.00
Received By cthroop Date 2018-01-03 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-05 Cont ID  
Sent By cthroop Date 2017-12-05 Time 11:41 Rev Time 0.00
Received By cthroop Date 2017-12-05 Time 10:25 Sent To  
Notes
2017-12-05 11:43:27BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED HOUSE IS LOCATED IN A FLOOD ZONE. PROVIDE
 ELEVATION CERTIFICATE.
 2. ENERGY SUBMITTAL TO BE SIGNED BY OWNER/AGENT.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-26 Cont ID  
Sent By cthroop Date 2017-10-26 Time 13:55 Rev Time 0.00
Received By cthroop Date 2017-10-25 Time 07:19 Sent To M
Notes
2017-10-26 15:12:08BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PER FOUNDATION NOTE ON PAGE S-0, PROVIDE A SIGNED
 AND SEALED GEOTECHNICAL REPORT. THE REPORT SHALL BE
 ISSUED BY AN ACCREDITED LABORATORY.
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTAL.
 3. DETAIL 3, PAGE A-5 SPECIFIES 1X2 WOOD FURRING ON
 INTERIOR WALLS. TYPICAL DOOR AND WINDOW SILL DETAILS ON
 PAGE A-6 SPECIFIES 15/8 METAL FURRING. PLEASE CLARIFY.
 4. PLEASE PROVIDE AN INTERPRETATION FOR THE
 INSTALLATION OF SHERWIN WILLIAMS SHER-CRETE FLEXIBLE
 CONCRETE WATER PROOFING AT ALL DOOR AND WINDOW MASONRY
 OPENINGS. IS THIS A QA/QC MEASURE OR A CODE
 REQUIREMENT? PLEASE CLARIFY.
 5. TYPICAL DOOR BUCK DETAIL ON PAGE A-6 SPECIFIES 2X
 P.T. WOOD BUCKS TO BE ATTACHED PER PRODUCT APPROVALS.
 PRODUCT APPROVALS SPECIFIES WOOD BUCK DESIGN AND
 INSTALLATION IS THE RESPONSIBILITY OF THE EOR AND AOR.
 PROVIDE ATTACHMENT DETAIL FOR 2X WOOD BUCKS AT EXT.
 DOORS.
 6. NOTICE - MANDATORY RESIDENTIAL AIR INFILTRATION
 (BLOWER DOOR) TEST REQUIRED.
 7. TYPICAL WINDOW ANCHORAGE DETAIL, PAGE A-6 REQUIRES A
 MIN. OF R-7.0 FOIL INSULATION. ENERGY SUBMITTAL
 REQUIRES A MIN. OF R-4.2. PLEASE CLARIFY.
 8. PROVIDE CERTIFICATE OF TERMITE TREATMENT PER FBC,
 SETION 1816.
 9. REFERENCE CONCRETE BEAM AND MASONRY LINTEL SCHEDULE,
 PAGE S-1. IDENTIFY WHAT A MB-3 IS FOR AN 8" WALL?
 10. REFERENCE CONCRETE COLUMN SCHEDULE, PAGE S-1. THE
 DESCRIPTION FOR TWO DIFFERENT FILLED CELL REINFORCEMENT
 REQUIREMENTS APPEARS TO BE THE SAME. PLEASE CLARIFY.
 11. THE VERTICAL REINFORCEMENT SPACING FOR A MW-1 TYPE
 WALL, SEE MASONRY WALL SCHEDULE, PAGE S-1, DOES NOT
 CORRESPOND TO THE VERTICAL SPACING ON THE FOUNDATION
 PLAN. PLEASE CLARIFY.
 12. REFERENCE SOIL STATEMENT, PAGE S-1. PLEASE CLARIFY
 WHAT THE STATEMENT "WITH THE SO S PREPERATION, ETC."
 MEANS IN ITEM B.
 13. PROVIDE SHOP DRAWINGS FOR PROPOSED STAIRS. THESE
 MAY BE LISTED AS A DEFFERRED SUBMITTAL. SHOP DRAWINGS
 MUST BE REVIEWED AND APPROVED PRIOR TO INSTALLATION.
 14. ROOF SHEATHING FASTENER DETAIL 2, PAGE A-5 IS IN
 CONFLICT WITH ROOF SHEATHING FASTENER SCHEDULE, PAGE
 S-2. PLEASE CLARIFY.
 15. REFERENCE DETAIL D, PAGE S-6. THERE ARE TWO
 DIFFERENT SHEATING PRODUCTS LISTED FOR THE SAME
 INSTALLATION. BOTH PRODUCTS ARE IN CONFLICT WITH THE
 SHEATHING DETAIL ON PAGE A-5. PLEASE CLARIFY.
 16. REFERENCE DETAIL H, PAGE S-7. HORIZONTAL
 REINFORCEMENT (DUROWALL) REQUIRED FOR MASONRY WALLS PER
 FBCR 606.12.2.2.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-27 Cont ID  
Sent By jpearson Date 2017-11-27 Time 07:41 Rev Time 0.00
Received By jpearson Date 2017-11-27 Time 07:41 Sent To  
Notes
2017-11-27 07:41:02NO CHANGE TO PLANS PREVIOUSLY APPROVED BY FG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-10-03 Cont ID  
Sent By fgiaquin Date 2017-10-03 Time 11:54 Rev Time 0.00
Received By fgiaquin Date 2017-10-03 Time 11:45 Sent To  
Notes
2017-10-03 11:53:25THIS PLAN HAS BEEN PASSED PROVISIONALLY.
  
 PLAN HAS BEEN MARKED ACCORDINGLY.
  
 1. ALL OUTDOOR GFCI RECEPTACLES WILL BE OF THE WP TYPE
 NEC 406.9(B1)
  
 2. OUTDOOR LUMINAIRES WILL BE SUITABLE FOR USE IN WET
 LOCATION. IF LUMINAIRE IS A HIGH HAT "CAN" TYPE IT WILL
 HAVE A VP TRIM. NEC 410.10
  
 3. GARAGE DOOR OPENER RECEPTACLES REQUIRE GFCI
 PROTECTION. NEC 210.8 (A2)
  
 4. CIRCUIT A-18 FOR SMALL APPLIANCE WILL NOT SERVE D/W
 OR DISPOSAL. NEC 210.52(B2)
  
 5. FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 (1)THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
  
 6. BOND GAS AND C/W PIPE IF APPLICABLE. NEC 250.104
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 DEVELOPMENT SERVICES DEPT.
 CELL 561-657-1653
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-01-03 Cont ID  
Sent By cthroop Date 2018-01-03 Time 13:11 Rev Time 0.00
Received By cthroop Date 2017-12-14 Time 14:06 Sent To I
Notes
2017-12-15 14:06:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-12-05 Cont ID  
Sent By cthroop Date 2017-12-05 Time 13:08 Rev Time 0.00
Received By cthroop Date 2017-11-02 Time 13:17 Sent To I
Notes
2017-11-03 13:17:49R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-11-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-27 Time 14:06 Sent To  
Notes
2017-09-28 14:06:57R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By cthroop Date 2017-10-25 Time 09:55 Rev Time 0.00
Received By cthroop Date 2017-10-25 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-12-28 Cont ID  
Sent By ccole Date 2017-12-28 Time 14:37 Rev Time 0.00
Received By ccole Date 2017-12-28 Time 14:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-22 Cont ID  
Sent By ccole Date 2017-11-22 Time 13:39 Rev Time 0.00
Received By ccole Date 2017-11-22 Time 13:39 Sent To  
Notes
2017-11-22 13:42:422ND REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17090693
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS WERE NOT ADDRESSED AND STILL
 EXIST. I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
  
 1ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17090693
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF MECHANICAL PLANS BY TWO
 DIFFERENT DESIGNERS HAVE BEEN SUBMITTED. THERE ARE THE
 M-1 & M-2 PLANS IN THE MAIN PLANS SETS PREPARED BY THE
 ARCHITECT OF RECORD, AND AN M.1 PLAN SEPARATE FROM THE
 MAIN SETS PREPARED BY K.O. ENERGY DESIGN. PLEASE CHOOSE
 ONE OF THE DESIGNS AND REMOVE THE OTHER. PLEASE NOTE
 THAT THE ENERGY AND AC CALCULATIONS WERE PREPARED BY K.
 O. ENERGY DESIGN, AND THE COMPLIANCE DATA LISTED FOR
 THE AC SYSTEM DOES NOT MATCH THE SCHEDULE ON THE MAIN
 SETS.
  
 2) THE AIR BARRIER AND INSPECTION CHECKLIST IS NOT
 ATTACHED WITH THE ENERGY COMPLIANCE FORM R405-2014.
 PLEASE PROVIDE THE CHECKLIST.
  
 3) FORM R405 IS MISSING THE OWNER/AGENT'S SIGNATURE AND
 DATE.
  
 4) THE AC LOAD CALCS ARE INDICATING THE FRONT DOOR
 FACES SOUTH HOWEVER THE MAPS SHOW THE FRONT DOOR MUST
 FACE NORTH.
  
 5) THE 10KW HEATER SPECIFIED IN THE K.O. ENERGY
 EQUIPMENT SCHEDULE IS UNDERSIZED FOR THE 48,948
 CALCULATED HEATING LOAD- MINIMUM 14KW REQUIRED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-01 Cont ID  
Sent By ccole Date 2017-11-01 Time 09:43 Rev Time 0.00
Received By ccole Date 2017-11-01 Time 09:43 Sent To  
Notes
2017-11-01 10:00:241ST REVIEW FBC-2014 RESDIENTIAL MECHANICAL
 PERMIT #17090693
 11/1/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TWO DIFFERENT SETS OF MECHANICAL PLANS BY TWO
 DIFFERENT DESIGNERS HAVE BEEN SUBMITTED. THERE ARE THE
 M-1 & M-2 PLANS IN THE MAIN PLANS SETS PREPARED BY THE
 ARCHITECT OF RECORD, AND AN M.1 PLAN SEPARATE FROM THE
 MAIN SETS PREPARED BY K.O. ENERGY DESIGN. PLEASE CHOOSE
 ONE OF THE DESIGNS AND REMOVE THE OTHER. PLEASE NOTE
 THAT THE ENERGY AND AC CALCULATIONS WERE PREPARED BY K.
 O. ENERGY DESIGN, AND THE COMPLIANCE DATA LISTED FOR
 THE AC SYSTEM DOES NOT MATCH THE SCHEDULE ON THE MAIN
 SETS.
  
 2) THE AIR BARRIER AND INSPECTION CHECKLIST IS NOT
 ATTACHED WITH THE ENERGY COMPLIANCE FORM R405-2014.
 PLEASE PROVIDE THE CHECKLIST.
  
 3) FORM R405 IS MISSING THE OWNER/AGENT'S SIGNATURE AND
 DATE.
  
 4) THE AC LOAD CALCS ARE INDICATING THE FRONT DOOR
 FACES SOUTH HOWEVER THE MAPS SHOW THE FRONT DOOR MUST
 FACE NORTH.
  
 5) THE 10KW HEATER SPECIFIED IN THE K.O. ENERGY
 EQUIPMENT SCHEDULE IS UNDERSIZED FOR THE 48,948
 CALCULATED HEATING LOAD- MINIMUM 14KW REQUIRED
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-01-03 Cont ID  
Sent By cthroop Date 2018-01-03 Time 12:54 Rev Time 0.00
Received By cthroop Date 2018-01-03 Time 11:53 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-12-05 Cont ID  
Sent By cthroop Date 2017-12-05 Time 11:43 Rev Time 0.00
Received By cthroop Date 2017-12-05 Time 11:41 Sent To  
Notes
2017-12-05 11:49:12BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPOSED HOUSE IS LOCATED IN FLOOD ZONE A5 WITH A
 BASE FLOOD ELEVATION (BFE) OF 7 FEET 0 INCHES.
 2. PROVIDE ELEVATION CERTIFICATE AS FOLLOWS:
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 A7 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 12 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 8. 0 FEET. PLEASE NOTE THIS
 INFORMATION ON YOUR PLANS.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD.
  
 AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 RECOMMENDED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-10-12 Cont ID  
Sent By lcrespo Date 2017-10-12 Time 14:47 Rev Time 0.00
Received By lcrespo Date 2017-10-12 Time 14:45 Sent To  
Notes
2017-10-12 14:47:0410/12/17 APPROVED PLUMBING, LAC

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-10-25 Cont ID  
Sent By cthroop Date 2017-10-25 Time 13:34 Rev Time 0.00
Received By cthroop Date 2017-10-25 Time 07:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-11-16 Cont ID  
Sent By ajones Date 2017-11-16 Time 15:48 Rev Time 0.00
Received By ajones Date 2017-11-06 Time 16:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By njwira Date 2017-10-05 Time 16:58 Rev Time 0.00
Received By njwira Date 2017-10-05 Time 16:30 Sent To  
Notes
2017-10-05 17:01:0410/5/17- FAILED
  
 WHERE IS THE A/C UNIT GOING?
 DRIVEWAY IS 22FT. 9IN. EXCEEDS 20FT. MAXIMUM
 MUST PROVIDE A 3FT. SIDE SETBACK FROM THE DRIVEWAY
 MUST PROVIDE 75% OR 1,000SQFT. OF PERVIOUS SURFACE IN
 THE FRONT SETBACK
 WHAT IS THE ROOF OVERHANG? CANNOT EXCEED 3FT.
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved