Plan Review Details - Permit 17090629
Plan Review Stops For Permit 17090629
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-29 Cont ID  
Sent By ccole Date 2017-09-29 Time 15:08 Rev Time 0.00
Received By ccole Date 2017-09-29 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-27 Cont ID  
Sent By ccole Date 2017-09-27 Time 07:55 Rev Time 0.00
Received By ccole Date 2017-09-27 Time 07:55 Sent To  
Notes
2017-09-27 08:06:471ST REVIEW FBC-2014 BUILDING
 PERMIT #17090629
 9/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE W-30 SYSTEM SELECTED HAS A MAXIMUM DESIGN
 PRESSURE OF -60 PSF WHICH IS INADEQUATE FOR ZONES 2 & 3
 ON A ROOF WITH A 10' MEAN HEIGHT IN EXPOSURE C. PLEASE
 SEE LIMITATION 5.7 ON PAGE 4 AND PROVIDE AN ATTACHMENT
 DENSITY DESIGNED BY A FL. LICENSED ENGINEER TO RESIST
 THE ELEVATED PRESSURE CRITERIA.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  