Plan Review Details - Permit 17090552
Plan Review Stops For Permit 17090552
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-12-01 Cont ID  
Sent By shill Date 2017-12-01 Time 15:16 Rev Time 0.00
Received By shill Date 2017-12-01 Time 06:41 Sent To  
Notes
2017-12-01 15:27:32PROVISOS
  
 1. 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH
 FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE
 LOCATED 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 2. 2014 FBC-ACCESSIBILITY CODE 216.6 ENTRANCES. WHERE
 NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES COMPLYING
 WITH 404 SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL OF ACCESSIBILITY COMPLYING WITH 703.7.2.1.
 DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT INDICATE
 THE LOCATION OF THE NEAREST ENTRANCE COMPLYING WITH 404
 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT COMPLY WITH
 404.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-21 Cont ID  
Sent By jwitmer Date 2017-11-21 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2017-11-21 Time 11:46 Sent To  
Notes
2017-11-21 13:24:522014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090552
 ADD: 4411 BEACON CIRCLE
 CONT: MAC ENTERPRISES
 TEL: 561-236-2627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 21/2017
 ACTION: DENIED
  
 1-3) COMPLIED.
  
  
 4A) COMPLIED.
  
 4B) 2ND REQUEST, SHEET A3 THE ROOM ID NUMBER PLEASE
 NOTE THE TACTILE BRAILLE SIGNAGE PORTION OF THE SIGN IS
 TO BE NOT OVER 4 FEET ABOVE THE FINISH FLOOR, NOT THE
 TOP OF THE WHOLE SIGN. A PERSON IN A WHEELCHAIR THE
 SIGN WILL BE WITHIN THEIR REACH RANGES.
 1S ROUND OF COMMENTS. SHEET A.3. ROOM ID NUMBERS IS
 SHOWN ON THE PLAN CENTERLINE AT 5 FEET FROM FINISH
 FLOOR. 2014 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE
 FINISH FLOOR OR GROUND. TACTILE CHARACTERS ON SIGNS
 SHALL BE LOCATED 48 INCHES MINIMUM ABOVE THE FINISH
 FLOOR OR GROUND SURFACE, MEASURED FROM THE BASELINE OF
 THE LOWEST TACTILE CHARACTER AND 60 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND SURFACE, MEASURED FROM
 THE BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 5) COMPLIED. MICROWAVE REACH RANGES, ON COUNTERTOP.
  
 6) SEMI-COMPLIED. PLEASE PROVIDE SIGNAGE BOTH INSIDE
 AND THE EXTERIOR OF THE BUILDING FOR THE ENTRANCE /
 EXIT THAT IS NOT ACCESSIBLE AND THE CLOSEST ACCESSIBLE
 EGRESS.
  
 2014 FBC-ACCESSIBILITY CODE 216.6 ENTRANCES. WHERE NOT
 ALL ENTRANCES COMPLY WITH 404, ENTRANCES COMPLYING WITH
 404 SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY COMPLYING WITH 703.7.2.1. DIRECTIONAL
 SIGNS COMPLYING WITH 703.5 THAT INDICATE THE LOCATION
 OF THE NEAREST ENTRANCE COMPLYING WITH 404 SHALL BE
 PROVIDED AT ENTRANCES THAT DO NOT COMPLY WITH 404.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY LS.1 PLAN DOES
 NOT SHOW WHAT THE CONDITIONS ARE FOR ACCESSIBLE
 ENTRANCES. 2014 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES.
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404.
  
  
 7) 2ND REQUEST. THE RESPONSE COMMENTS INDICATE THE
 EXISTING RESTROOMS ARE TO BE REMOVED FROM THE PROJECT.
 BUT ON THE DEMOLITION SHEET THEY ARE LISTED WITH NO
 WORK, EXISTING RESTROOMS. DISCREPANCY IN PLANS. PLEASE
 UPDATE THE DEMOLITION PLAN.
 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN NOR SHEET
 A.1 SHOW EXISTING RESTROOMS WITH NO WORK IN EITHER
 RESTROOM. THE PERMIT APPLICATION INDICATES A VALUE FOR
 THIS PROJECT OF $409,670.00 IN VALUE, 20% OF THIS VALUE
 IS $81,934.00 DOLLARS, THIS IS UP TO THE AMOUNT OF
 ACCESSIBLE UPGRADES REQUIRED TO MEET
 DISPROPORTIONALITY. PLEASE PROVIDE AN ITEMIZED LIST ON
 THE BUSINESS LETTER HEAD SHOWING WHERE THIS REQUIREMENT
 HAS BEEN MET AND THE EXISTING RESTROOMS DO NOT NEED TO
 SHOW COMPLIANCE WITH THE ACCESSIBILITY CODE.
  
 2014 FBC-ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY. WHEN THE
 COST OF ALTERATIONS NECESSARY TO MAKE THE PATH OF
 TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-19 Cont ID  
Sent By jwitmer Date 2017-10-19 Time 12:44 Rev Time 0.00
Received By jwitmer Date 2017-10-19 Time 09:30 Sent To  
Notes
2017-10-19 12:44:112014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090552
 ADD: 4411 BEACON CIRCLE
 CONT: MAC ENTERPRISES
 TEL: 561-236-2627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. OCT. 19/2017
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) COMPLIED.
  
 2) 2ND REQUEST. BEFORE THE 1ST ROUND OF COMMENTS WERE
 WRITTEN I TOOK THE ISSUE OF MULTIPLE ENTRY/ EXIT POINTS
 TO THE BUILDING OFFICIAL FOR HIS RULING. WE AGREE THAT
 THE BUILDING WAS CUT UP BY MULTIPLE TENANTS, BUT THE
 CODE IN SECTION 1008.1.9.3 OF THE FBC-B CODE IS
 ADDRESSING ALL DOORS THAT LEAD TO THE EXTERIOR.
 YOU CANNOT JUST LOCK UP A DOOR WHEN THE BUILDING IS
 OCCUPIED. IN MAKING THE DOOR INOPERABLE YOU WILL NEED
 TO SHOW THE DOOR IS NO LONGER A DOOR, AN EXAMPLE IF THE
 WINDOW WALLS START THE BOTTOM OF THE WINDOW AT 3 FEET,
 THEN DO THE SAME WITH THE DOOR SO IT NO LONGER
 RESEMBLES A DOOR, OR WALL IT OVER SO THE DOOR IS NO
 LONGER VISIBLE. PLEASE PROVIDE HOW YOU INTEND TO COMPLY
 WITH THE CODE?
  
 1ST REVIEW COMMENT. SHEET A.0 THE DEMO PLAN NOTE NUMBER
 (10) INDICATES (7) OF THE EXISTING EXIT DOORS ARE TO
 REMAIN IN THE CLOSED & LOCKED POSITION. SHEET A.1 THE
 FLOOR PLAN NOTE NUMBER (13) INDICATES THESE SAME (7) OF
 THE EXISTING EXIT DOORS ARE TO REMAIN IN THE CLOSED &
 LOCKED POSITION.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED WITH
 CODE SECTION 1008.1.9.3 LOCKS AND LATCHES 2-2.3.
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 3) COMPLIED.
  
 4A) SEMI ?COMPLIED. SHEET A.3, THE TELEPHONE OUTLET AND
 INTERCOM/ PHONE OUTLET ARE ABOVE THE REACH RANGES FOUND
 IN THE 2014 ACCESSIBILITY CODE;
 308.2 FORWARD REACH. 308.2.1 UNOBSTRUCTED.
 308.3 SIDE REACH. 308.3.1 UNOBSTRUCTED.
 AND
 309.3 OPERABLE PARTS OF THE ACCESSIBILITY CODE. IT
 WOULD APPEAR THAT IN NOT DESIGNING FOR ACCESSIBILITY IT
 COULD LEAD THE WAY FOR LAW SUITS UNDER THE FEDERAL ADA.
 THESE ARE COMMON AREA USES THAT NOT ONLY WORKERS BUT
 ALSO VISITORS TO THE SITE MAY NEED TO USE.
  
 1ST ROUND OF COMMENTS. SHEET A.3, THE THERMOSTAT,
 TELEPHONE OUTLET, INTERCOM/ PHONE, AND COAT HOOKS ARE
 ALL ABOVE THE REACH RANGES FOUND IN THE 2014
 ACCESSIBILITY CODE;
 308.2 FORWARD REACH. 308.2.1 UNOBSTRUCTED.
 308.3 SIDE REACH. 308.3.1 UNOBSTRUCTED.
 604.8.3 COAT HOOKS.
  
 4B) COMPLIED.
  
 5) 2ND REQUEST. SHEET A.4 STILL SHOWS BOTH MICROWAVES
 ABOVE THE REACH RANGES AND OPERABLE PARTS FOUND UNDER
 THE 2014 FBC-ACCESSIBILITY CODE SECTION 309.3 HEIGHT
 AND 309.4 OPERATION. WE AGREE THAT NOTHING STOPS YOU
 FROM DESIGNING TO THE ACCESSIBILITY CODE. ONE MICROWAVE
 ON THE COUNTER TOP WILL COMPLY WITH THE CODE, BUT HAS
 TO BE DETAILED THAT WAY.
  
 1ST ROUND COMMENT. SHEET A.4 DETAIL 2 BREAK ROOM
 INDICATES 2 MICROWAVES SITTING ON SHELVING AT A HEIGHT
 OF 4 FOOT 8 INCHES TO THE BOTTOM OF THE MICROWAVE. THIS
 IS ABOVE THE HEIGHT OF EITHER REACH RANGES.
 308.2 FORWARD REACH. 308.2.1 UNOBSTRUCTED.
 308.3 SIDE REACH. 308.3.1 UNOBSTRUCTED.
  
 6) 2ND REQUEST. PLACING A NOTE ON THE PLANS THAT THESE
 ARE THE ACCESSIBLE ENTRANCES DOES NOT SHOW CODE
 COMPLIANCE. HOW DO YOU GET ONTO THE SIDEWALK FOR EITHER
 OF THE EGRESS DOORS. ARE BOTH EGRESS DOORS ON BOTH
 SIDES OF THE THRESHOLD AT THE SAME ELEVATION, IF NOT
 WHAT IS THE DIFFERENCE IN HEIGHT. THE ACCESSIBILITY
 CODE ONLY ALLOWS FOR ? INCH CHANGE IN ELEVATION SEE
 303.2 AND 303.3.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY LS.1 PLAN DOES
 NOT SHOW WHAT THE CONDITIONS ARE FOR ACCESSIBLE
 ENTRANCES. 2014 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES.
 IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH
 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES
 SHALL COMPLY WITH 404.
  
 7) 2ND REQUEST. THE ACCESSIBILITY CODE SECTION 213.2
 EXCEPTION # 4 REQUIRES COMPLIANCE WITH:
 2014 FBC-ACC. CODE 213.2.4. WHERE MULTIPLE SINGLE USER
 TOILET ROOMS ARE CLUSTERED AT A SINGLE LOCATION, NO
 MORE THAN 50 PERCENT OF THE SINGLE USER TOILET ROOMS
 FOR EACH USE AT EACH CLUSTER SHALL BE REQUIRED TO
 COMPLY WITH 603.
 THE COMMENT ABOUT THE DISPROPORTIONATE COST IF THE
 REQUIRED AMOUNT NEEDED TO MEET THEN THIS REQUIREMENT
 DOES NOT NEED TO BE MET BECAUSE DISPROPORTIONALITY WAS
 MET (20% OR UP TO $81,934.00 DOLLARS), THEN THE
 DESIGNER AND CONTRACTOR DOES NOT NEED TO SPEND OVER THE
 REQUIRED 20% OF THE REQUIRED FUNDS, BUT WE DO NEED THE
 ITEMIZED LETTER SHOWING DISPROPORTIONALITY. THIS
 ITEMIZED LIST ON EITHER THE DESIGNER OF RECORD OR
 CONTRACTORS LETTERHEAD IS FILED WITH THE PERMIT
 DOCUMENTS AND RECORDED INTO THE RECORD RETENTION
 PROGRAM.
  
 1ST ROUND OF COMMENTS. THE LIFE SAFETY PLAN NOR SHEET
 A.1 SHOW EXISTING RESTROOMS WITH NO WORK IN EITHER
 RESTROOM. THE PERMIT APPLICATION INDICATES A VALUE FOR
 THIS PROJECT OF $409,670.00 IN VALUE, 20% OF THIS VALUE
 IS $81,934.00 DOLLARS, THIS IS UP TO THE AMOUNT OF
 ACCESSIBLE UPGRADES REQUIRED TO MEET
 DISPROPORTIONALITY. PLEASE PROVIDE AN ITEMIZED LIST ON
 THE BUSINESS LETTER HEAD SHOWING WHERE THIS REQUIREMENT
 HAS BEEN MET AND THE EXISTING RESTROOMS DO NOT NEED TO
 SHOW COMPLIANCE WITH THE ACCESSIBILITY CODE.
  
 2014 FBC-ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY. WHEN THE
 COST OF ALTERATIONS NECESSARY TO MAKE THE PATH OF
 TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-04 Cont ID  
Sent By jwitmer Date 2017-10-04 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2017-11-21 Time 11:37 Sent To  
Notes
2017-10-04 08:24:292014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17090552
 ADD: 4411 BEACON CIRCLE
 CONT: MAC ENTERPRISES
 TEL: 561-236-2627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 04/2017
 ACTION: DENIED
  
 1) THE COVERSHEET T.1 LIST THIS AS A BUSINESS OCCUPANCY
 WITH 106 OCCUPANTS AND 10,609 SQ. FT. (GROSS).
 PLEASE SEE BPAF BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA IN COOPERATION WITH THE FLORIDA BUILDING
 COMMISSION, THE FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS
 THE INFORMAL INTERPRETATION # 5479, THAT YOU ALWAYS
 ROUND UP, OCCUPANTS ONLY COME AS A WHOLE. IN THIS CASE
 THE OCCUPANT LOAD WOULD BE 107. 2014 FBC-B TABLE
 1004.1.2.
  
 2) SHEET A.0 THE DEMO PLAN NOTE NUMBER (10) INDICATES
 (7) OF THE EXISTING EXIT DOORS ARE TO REMAIN IN THE
 CLOSED & LOCKED POSITION. SHEET A.1 THE FLOOR PLAN NOTE
 NUMBER (13) INDICATES THESE SAME (7) OF THE EXISTING
 EXIT DOORS ARE TO REMAIN IN THE CLOSED & LOCKED
 POSITION.
 PLEASE PROVIDE HOW COMPLIANCE WILL BE ACHIEVED WITH
 CODE SECTION 1008.1.9.3 LOCKS AND LATCHES 2-2.3.
 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT
 LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN
 PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR
 DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED
 LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED:
 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS
 LOCKED;
 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE
 EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS
 DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE
 SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND; AND
 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS
 REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE.
  
 3) SHEET A.3 THE DETAILS FOR THE RESTROOM GRAB BARS THE
 FINISH ELEVATIONS ARE TAKEN FROM FINISH FLOOR TO THE
 CENTERLINE OF THE GRAB BAR. PLEASE REVIEW THE 2014
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 4A) SHEET A.3, THE THERMOSTAT, TELEPHONE OUTLET,
 INTERCOM/ PHONE, AND COAT HOOKS ARE ALL ABOVE THE REACH
 RANGES FOUND IN THE 2014 ACCESSIBILITY CODE;
 308.2 FORWARD REACH. 308.2.1 UNOBSTRUCTED.
 308.3 SIDE REACH. 308.3.1 UNOBSTRUCTED.
 604.8.3 COAT HOOKS.
  
 4B) SHEET A.3. ROOM ID NUMBERS IS SHOWN ON THE PLAN
 CENTERLINE AT 5 FEET FROM FINISH FLOOR. 2014
 ACCESSIBILITY CODE. 703.4.1 HEIGHT ABOVE FINISH FLOOR
 OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED
 48 INCHES MINIMUM ABOVE THE FINISH FLOOR OR GROUND
 SURFACE, MEASURED FROM THE BASELINE OF THE LOWEST
 TACTILE CHARACTER AND 60 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND SURFACE, MEASURED FROM THE
 BASELINE OF THE HIGHEST TACTILE CHARACTER.
  
 5) SHEET A.4 DETAIL 2 BREAK ROOM INDICATES 2 MICROWAVES
 SITTING ON SHELVING AT A HEIGHT OF 4 FOOT 8 INCHES TO
 THE BOTTOM OF THE MICROWAVE. THIS IS ABOVE THE HEIGHT
 OF EITHER REACH RANGES.
 308.2 FORWARD REACH. 308.2.1 UNOBSTRUCTED.
 308.3 SIDE REACH. 308.3.1 UNOBSTRUCTED.
  
 6) THE LIFE SAFETY LS.1 PLAN DOES NOT SHOW WHAT THE
 CONDITIONS ARE FOR ACCESSIBLE ENTRANCES. 2014 ACCESS.
 CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION TO ENTRANCES
 REQUIRED BY 206.4.2 THROUGH 206.4.9, AT LEAST 60
 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH 404.
  
 7) THE LIFE SAFETY PLAN NOR SHEET A.1 SHOW EXISTING
 RESTROOMS WITH NO WORK IN EITHER RESTROOM. THE PERMIT
 APPLICATION INDICATES A VALUE FOR THIS PROJECT OF
 $409,670.00 IN VALUE, 20% OF THIS VALUE IS $81,934.00
 DOLLARS, THIS IS UP TO THE AMOUNT OF ACCESSIBLE
 UPGRADES REQUIRED TO MEET DISPROPORTIONALITY. PLEASE
 PROVIDE AN ITEMIZED LIST ON THE BUSINESS LETTER HEAD
 SHOWING WHERE THIS REQUIREMENT HAS BEEN MET AND THE
 EXISTING RESTROOMS DO NOT NEED TO SHOW COMPLIANCE WITH
 THE ACCESSIBILITY CODE.
  
 2014 FBC-ACCESSIBILITY CODE. 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY. WHEN THE
 COST OF ALTERATIONS NECESSARY TO MAKE THE PATH OF
 TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By jleahy Date 2017-10-26 Time 14:44 Rev Time 0.00
Received By jleahy Date 2017-10-26 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 10:18 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 10:18 Sent To  
Notes
2017-09-28 10:27:22FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
  
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5,
  
 THE SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM
 AVAILABLE SHORT CIRCUIT CURRENT AVAILABLE PER NEC
 110.24.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-11-17 Cont ID  
Sent By wjolin Date 2017-11-17 Time 10:54 Rev Time 0.00
Received By wjolin Date 2017-11-17 Time 10:54 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-10-25 Cont ID  
Sent By wjolin Date 2017-10-25 Time 09:40 Rev Time 0.00
Received By wjolin Date 2017-10-25 Time 09:34 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-28 Cont ID  
Sent By wjolin Date 2017-09-28 Time 12:05 Rev Time 0.00
Received By wjolin Date 2017-09-28 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-12-01 Cont ID  
Sent By shill Date 2017-12-01 Time 15:16 Rev Time 0.00
Received By shill Date 2017-11-27 Time 06:41 Sent To  
Notes
2017-12-01 06:41:20TO SH DESK
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-21 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-06 Time 15:27 Sent To  
Notes
2017-11-07 15:27:31RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-26 Cont ID  
Sent By jleahy Date 2017-10-26 Time 14:44 Rev Time 0.00
Received By jleahy Date 2017-10-11 Time 14:22 Sent To  
Notes
2017-10-12 14:22:41C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-05 Cont ID  
Sent By gjohnson Date 2017-10-05 Time 14:36 Rev Time 0.00
Received By gjohnson Date 2017-09-25 Time 14:49 Sent To  
Notes
2017-09-29 14:09:35C12
 9/29/17 REMOVED DEMO APPLICATION FOR ISSUANCE
  
  
2017-09-26 14:49:49C12
  
 **TRAVELLING WITH 17090551**

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-10-04 Cont ID  
Sent By jwitmer Date 2017-10-04 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2017-10-04 Time 06:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-20 Cont ID  
Sent By ccole Date 2017-10-20 Time 17:04 Rev Time 0.00
Received By ccole Date 2017-10-20 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By ccole Date 2017-10-02 Time 17:16 Rev Time 0.00
Received By ccole Date 2017-10-02 Time 17:16 Sent To  
Notes
2017-10-02 17:32:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090552
 10/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING RTU'S
 INCLUDING THE COOLING AND HEATING CAPACITIES AND SUPPLY
 CFMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-17 Cont ID  
Sent By gjohnson Date 2017-10-17 Time 15:55 Rev Time 0.00
Received By gjohnson Date 2017-10-17 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By gjohnson Date 2017-10-05 Time 14:21 Rev Time 0.00
Received By gjohnson Date 2017-10-05 Time 09:43 Sent To  
Notes
2017-10-05 14:30:381ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW DIMENSIONS OF BATHROOMS ALSO SHOW CLEAR
 FLOOR SPACE FOR WC AND LV. PER FBC ACC 604.3.1/606.2
  
 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 3. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 THE TOP OF THE GRIPPING SURFACE. PER 609.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  