Plan Review Details - Permit 17090496
Plan Review Stops For Permit 17090496
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-11-22 Time 11:15 Sent To  
Notes
2017-11-22 11:15:20RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-11-03 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-30 Time 11:34 Sent To  
Notes
2017-10-31 11:34:47RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-09-28 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-22 Time 10:07 Sent To  
Notes
2017-09-25 10:07:32ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-11-28 Cont ID  
Sent By ccole Date 2017-11-28 Time 09:07 Rev Time 0.00
Received By ccole Date 2017-11-28 Time 09:07 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-11-03 Cont ID  
Sent By ccole Date 2017-11-03 Time 15:04 Rev Time 0.00
Received By ccole Date 2017-11-03 Time 14:58 Sent To  
Notes
2017-11-03 15:18:472ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17090496
 11/3/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DISCREPTANCIES IN THE PLANS AND SUBMITTALS:
  
 A) SHEET AC-1: THE AAON MODEL NUMBER RNA SHOWN IN THE
 SCHEDULE DOESN'T MATCH THE MODEL NUMBER RN ON THE AHRI
 CERTIFICATE.
  
 B) AC-1: THE SCHEDULE SHOWS EER- 14.2, THE AHRI SHOWS
 EER- 12.70.
  
 C) AC-1: THE SCHEDULE SHOWS TOTAL MBH- 133.02, THE AHRI
 SHOWS 128.
  
 D) AC-1: THE SCHEDULE SHOWS TOTAL CFMS- 1600, THE AAON
 MANUFACTURER'S SPECIFICATIONS SHOW MODEL RN-011 TOTAL
 CFMS- 3600.
  
 E) AC-1: THE RTU DETAIL SHOWS A 24" HIGH CURB, THE FL.
 PRODUCT APPROVAL FOR THE AAON CURB SHOWS MAX HEIGHT- 1'
 2".
  
 F) AC-1: THE RTU DETAILS SHOWS ATTACHMENT OF THE UNIT
 TO THE CURB USING STEEL STRAPS ON THE FACES OF THE UNTI
 AND CURB, THE PRODUCT APPROVAL SHOWS STEEL CLIPS THAT
 WRAP AROUND THE BACKSIDE OF THE CURB.
  
 G) AC-1: THE RTU DETAIL SHOWS ATTACHMENT OF THE CURB TO
 A CONCRETE STRUCTURE, HOWEVER THE PRODUCT APPROVAL
 SHOWS ONLY AN ATTACHMENT TO STEEL STRUCTUURE AND DOES
 NOT SHOW AN ATTACHMENT DETAIL FOR CONCRETE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-28 Cont ID  
Sent By ccole Date 2017-09-28 Time 11:00 Rev Time 0.00
Received By ccole Date 2017-09-28 Time 11:00 Sent To  
Notes
2017-09-28 11:02:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090496
 9/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 11-TON SYSTEM- SECTION R403.6.1 C403.2.1 FBC-14 ENERGY
 CONSERVATION & SECTION 312.1 FBC-14 MECHANICAL.
  
 2) THE ENGINEERING FOR TIE DOWN OF THE NEW OAU IS
 INCOMPLETE. THE SUBMITTAL FROM ROBERT W. LAFFERTY PE
 DOES NOT PROVIDE ANY ANCHORING OR FASTENING INFORMATION
 AND THE DETAILS ON SHEET AC-1 ARE INCOMPLETE. INDICATE
 ON THE SUBMITTAL AND PLANS THE TYPE, SIZE AND GAUGE OF
 STEEL STRAPPING, AND NUMBER OF STRAPS REQUIRED TO TIE
 THE RTU TO THE CURB. SUBMIT THE NOA FOR THE CURB WITH
 APPROVAL STAMP BY THE ENGINEER OF RECORD.
  
 3) THE EOR ROBERT W. LAFFERTY MUST PROVIDE A TITLE
 BLOCK ON THE PLAN SHEETS AND THE TIE-DOWN SUBMITTAL-
 SECTION G15-23.002 FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  