Plan Review Stops For Permit 17090437 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2018-01-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-01-05 |
Time |
16:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-01-05 |
Time |
16:39 |
Sent To |
|
|
Notes |
2018-01-05 16:47:08 | PROVISO | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH | | ELEVATIONS OR AN ELEVATION CERTIFICATE IS REQUIRED | | | | PRIOR TO FINAL INSPECTION, A FINISHED CONSTRUCTION | | ELEVATION CERTIFICATE IS REQUIRED | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2017-11-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-11-27 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-11-27 |
Time |
17:30 |
Sent To |
|
|
Notes |
2017-11-27 17:40:01 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | FROM PREVIOUS LIST: | | | | 1. PROVIDE A SITE PLAN SHOWING PROPOSED LOCATION, | | INCLUDING DISTANCE TO PROPERTY LINES AND ASSUMED | | PROPERTY LINES FBC B 705.3. | | | | 2ND REVIEW, NO DISTANCES TO THE ASSUMED PROPERTY LINE | | BETWEEN THE TWO BUILDINGS, OR OTHER FORM OF COMPLIANCE, | | WAS PROVIDED. | | | | 2. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS | | REQUIRED. CONTACT 561-233-5025 FOR MORE INFORMATION. | | THIS MAY BE DONE AFTER ALL REVIEWS ARE COMPLETE. | | | | 3. THIS PERMIT WILL BE ISSUED WITH PROVISO, A "BUILDING | | UNDER CONSTRUCTION" ELEVATION CERTIFICATE WILL BE | | REQUIRED PRIOR TO CONCRETE POUR. A "FINISHED | | CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED | | PRIOR TO FINAL INSPECTION. | | | | 4. ALL EQUIPMENT SERVICING THE BUILDING WILL ALSO BE | | REQUIRED TO MEET THE MINIMUM ELEVATION OF 17' NGVD29; | | REVISE PLAN WITH A NOTE. | | | | NEW COMMENTS: | | | | 5. PROVIDE LEGIBLE PLANS FOR THE MODULAR, FBC 107. | | COMPLIANCE WITH DISTANCE TO THE ASSUMED PROPERTY LINE | | (SEE ITEM 1) REQUIRES INFORMATION SUCH AS THE BUILDING | | TYPE, FBC 107. | | | | 6. IF NOT INCLUDED IN THE DCA APPROVAL, PROVIDE AN | | ENGINEERED DETAIL FOR THE FOUNDATION AND TIE DOWNS FOR | | THE PROPOSED MODULAR, FBC B 1609. | | | | 7. PROVIDE A NEW PERMIT APPLICATION WITH CORRECT SCOPE | | OF WORK PROPOSED WITH UPDATED VALUE. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-09-27 |
Time |
17:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-09-27 |
Time |
17:33 |
Sent To |
|
|
Notes |
2017-09-27 17:41:59 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. PROVIDE A SITE PLAN SHOWING PROPOSED LOCATION, | | INCLUDING DISTANCE TO PROPERTY LINES AND ASSUMED | | PROPERTY LINES FBC B 705.3. | | | | 2. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS | | REQUIRED. CONTACT 561-233-5025 FOR MORE INFORMATION. | | | | 3. THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA, MAP PANEL 1202250015B, BFE OF 16'. THE CITY OF | | WEST PALM BEACH MUNICIPAL CODE REQUIRES A FREEBOARD OF | | 1'. FBC 1612.3. REVISE PLAN TO INDICATE PROPOSED FFE, A | | MINIMUM OF 17' NGVD29. REVISE SITE PLAN TO SHOW | | ACCESSIBLE ROUTE, INCLUDING ELEVATIONS AND SLOPES, FBC | | A 206. | | | | THIS PERMIT WILL BE ISSUED WITH PROVISO, A "BUILDING | | UNDER CONSTRUCTION" ELEVATION CERTIFICATE WILL BE | | REQUIRED PRIOR TO CONCRETE POUR. A "FINISHED | | CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED | | PRIOR TO FINAL INSPECTION. | | | | ALL EQUIPMENT SERVICING THE BUILDING WILL ALSO BE | | REQUIRED TO MEET THE MINIMUM ELEVATION OF 17' NGVD29; | | REVISE PLAN WITH A NOTE. | | | | 4. FBC 107, ROUTE INTO THE FUTURE MODULAR NOT CLEAR; IS | | A STAIR/RAMP PROPOSED? REVISE SITE PLAN TO INCLUDE, | | NOTING IT AS "FUTURE". | | | | 5. SCOPE NOT CLEAR. APPLICATION IS FOR SLAB ONLY, BUT | | SOME DCA PAPERWORK WAS SUBMITTED. REMOVE (BY VOIDING | | THE SHEETS) OR PROVIDE PLANS AND VALUE FOR PROPOSED | | MODULAR AND RELATED WORK. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2017-11-27 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-11-27 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-11-27 |
Time |
09:46 |
Sent To |
|
|
Notes |
2017-11-27 09:52:18 | ELECTRICAL TO GUARD SHACK ON PERMIT 17110135. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-10-04 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-10-04 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-10-04 |
Time |
06:19 |
Sent To |
|
|
Notes |
2017-10-04 11:44:02 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT ANY | | ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE THAT | | ON PLAN. FS 471.003(2)(H); 471.025; FBC 107.2.1, | | 107.3.5 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-01-17 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-01-17 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-11-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-11-29 |
Time |
12:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-11-15 |
Time |
10:49 |
Sent To |
I |
|
Notes |
2017-11-28 11:58:02 | 11/28 REMOVED FROM BOARD; PICKED UP BY JR | | | | | 2017-11-15 10:29:49 | B14 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-11-15 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2017-11-15 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2017-09-20 |
Time |
16:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-01-17 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-01-17 |
Time |
10:58 |
Sent To |
|
|
Notes |
2018-01-17 10:58:38 | MU=2018-000743-0000 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-09-27 |
Time |
17:42 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-09-27 |
Time |
17:42 |
Sent To |
|
|
Notes |
2017-09-27 17:42:31 | SEE BUILDING REVIEW | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-11-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-11-22 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-11-22 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-10-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-10-02 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-10-02 |
Time |
10:34 |
Sent To |
|
|
Notes |
2017-10-02 10:38:09 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17090437 | | 10/2/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REVIEW BUILDING COMMENT #3 REGARDING EXTERIOR | | EQUIPMENT IN A FLOOD HAZARD AREA AND PROVIDE A SITE | | PLAN THAT SHOWS THE LOCATION OF THE AC CONDENSE. REFER | | TO SECTION 301.16: | | | | [B] 301.16 FLOOD HAZARD. | | FOR STRUCTURES LOCATED IN FLOOD HAZARD AREAS, | | MECHANICAL SYSTEMS, EQUIPMENT AND APPLIANCES SHALL BE | | LOCATED AT OR ABOVE THE ELEVATION REQUIRED BY SECTION | | 1612 OF THE FLORIDA BUILDING CODE, BUILDING FOR | | UTILITIES AND ATTENDANT EQUIPMENT. | | | | EXCEPTION: MECHANICAL SYSTEMS, EQUIPMENT AND APPLIANCES | | ARE PERMITTED TO BE LOCATED BELOW THE ELEVATION | | REQUIRED BY SECTION 1612 OF THE OF THE FLORIDA BUILDING | | CODE, BUILDING FOR UTILITIES AND ATTENDANT EQUIPMENT | | PROVIDED THAT THEY ARE DESIGNED AND INSTALLED TO | | PREVENT WATER FROM ENTERING OR ACCUMULATING WITHIN THE | | COMPONENTS AND TO RESIST HYDROSTATIC AND HYDRODYNAMIC | | LOADS AND STRESSES, INCLUDING THE EFFECTS OF BUOYANCY, | | DURING THE OCCURRENCE OF FLOODING UP TO SUCH ELEVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
3 |
Status |
P |
Date |
2018-01-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2018-01-17 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2018-01-17 |
Time |
10:59 |
Sent To |
|
|
Notes |
2018-01-17 10:59:54 | PROVISO | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | PRIOR TO CONCRETE POUR, A FORM BOARD SURVEY WITH | | ELEVATIONS OR AN ELEVATION CERTIFICATE IS REQUIRED | | | | PRIOR TO FINAL INSPECTION, A FINISHED CONSTRUCTION | | ELEVATION CERTIFICATE IS REQUIRED | | | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
2 |
Status |
F |
Date |
2017-11-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-11-27 |
Time |
17:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-11-27 |
Time |
17:41 |
Sent To |
|
|
Notes |
2017-11-27 17:41:43 | SEE BUILDING REVIEW | | |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
F |
Date |
2017-09-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-09-27 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-09-27 |
Time |
18:15 |
Sent To |
|
|
Notes |
2017-09-27 18:15:36 | SEE BUILDING REVIEW | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2017-11-15 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2017-11-15 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2017-11-15 |
Time |
10:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-10-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-10-04 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-10-04 |
Time |
12:45 |
Sent To |
|
|
Notes |
2017-10-04 12:52:29 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE PROVIDE PLUMBING PLAN OR SITE PLAN SHOWING | | LOCATION OF BATHROOM FACILITY'S. PER FBC PL | | 403.1/403.3/403.3.3 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2017-11-29 |
|
|
Cont ID |
|
Sent By |
JR |
Date |
2017-11-29 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2017-11-27 |
Time |
10:58 |
Sent To |
|
|
Notes |
|
|