Plan Review Details - Permit 17090410
Plan Review Stops For Permit 17090410
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-12-04 Cont ID  
Sent By rmcdouga Date 2017-12-04 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2017-12-04 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-11-30 Cont ID  
Sent By rmcdouga Date 2017-11-30 Time 19:12 Rev Time 0.00
Received By rmcdouga Date 2017-11-30 Time 18:34 Sent To I
Notes
2017-11-30 19:15:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER NEEDS TO SPECIFY THE REQUIRED EMBEDMENT
 DEPTH OF THE ANCHORS ON THE TIE DOWN SCHEDULE DRAWING
 OR PROVIDE THE MANUFACTURER'S SPECIFICATIONS THAT
 SPECIFY THE REQUIRED EMBED DEPTHS. FBC-R301.1
  
 2) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS
 OR PRODUCT APPROVALS FOR THE EARTH AND CONCRETE
 ANCHORS. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-10-24 Cont ID  
Sent By rmcdouga Date 2017-10-24 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2017-10-24 Time 11:00 Sent To  
Notes
2017-10-24 11:27:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ANCHORING DETAIL, SHEET 1 OF 1 IS NOT PART OF
 THE STATE APPROVED MANUFACTURED BUILDING PLANS. THE
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE IS
 REQUIRED ON THE FOUNDATION ANCHORING PLAN. FS 471 AND
 FAC 61G-15-23.003
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-28 Cont ID  
Sent By rmcdouga Date 2017-09-28 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2017-09-28 Time 06:46 Sent To  
Notes
2017-09-28 08:00:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS THAT WERE SUBMITTED ARE REQUIRED TO HAVE
 THE DBPR PLAN TRACKING NUMBER ON THEM. THE PSI APPROVAL
 DATE ON THESE PLANS DO NOT MATCH THE ONES ON FILE WITH
 THE STATE. SUBMIT THE CURRENT PLANS WITH THE CORRECT
 DATE AND TRACKING NUMBER. FAC 61G20-3.006
  
 2) THE ANCHORING DETAIL, SHEET 1 OF 1 IS NOT PART OF
 THE STATE APPROVED MANUFACTURED BUILDING PLANS. THE
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE IS
 REQUIRED ON THE FOUNDATION ANCHORING PLAN. FS 471 AND
 FAC 61G-15-23.003
  
 3) THE NAME OF THE OWNER ON THE APPLICATION DOES NOT
 MATCH THE CITY RECORDS OR THE PALM BEACH COUNTY
 PROPERTY APPRAISER. PLEASE SUBMIT THE APPROPRIATE
 DOCUMENTS FOR PROOF OF OWNERSHIP. FBC 107.2.1
  
 4) ADDRESS ZONING REVIEW COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2017-12-04 Cont ID  
Sent By rmcdouga Date 2017-12-04 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2017-12-04 Time 16:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-30 Cont ID  
Sent By rmcdouga Date 2017-11-30 Time 19:12 Rev Time 0.00
Received By rmcdouga Date 2017-11-28 Time 10:12 Sent To  
Notes
2017-11-30 10:12:31RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-24 Cont ID  
Sent By rmcdouga Date 2017-10-24 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2017-10-12 Time 12:48 Sent To  
Notes
2017-10-13 12:48:22RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-28 Cont ID  
Sent By rmcdouga Date 2017-09-28 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2017-09-20 Time 11:19 Sent To  
Notes
2017-09-22 11:19:51ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2017-10-20 Cont ID  
Sent By ajones Date 2017-10-20 Time 15:33 Rev Time 0.00
Received By ajones Date 2017-10-20 Time 15:33 Sent To  
Notes
2017-10-20 15:34:11RM

Review Stop Z ZONING
Rev No 1 Status F Date 2017-09-25 Cont ID  
Sent By njwira Date 2017-09-25 Time 15:08 Rev Time 0.00
Received By njwira Date 2017-09-22 Time 15:59 Sent To B
Notes
2017-09-25 15:09:439/25/17- FAILED
  
 94-304(B)3- THERE MUST BE A SEPORATION BETWEEN THE MAIN
 STRUCTURE AND THE SHED OF 6FT.
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved