Plan Review Details - Permit 17090287
Plan Review Stops For Permit 17090287
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2017-09-25 Cont ID  
Sent By hhall Date 2017-09-25 Time 08:56 Rev Time 0.00
Received By hhall Date 2017-09-25 Time 08:56 Sent To I
Notes
2017-09-25 08:59:10PASSED - NO UTILITY CONFLICTS
 ADDRESS PLUMBING ISSUES - DETAIL GS-7.1 INCLUDED
 LOCATION FOR GREASE TRAP NOT SPECIFIED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-04 Cont ID  
Sent By thunt Date 2017-10-04 Time 14:39 Rev Time 0.00
Received By thunt Date 2017-10-02 Time 12:44 Sent To  
Notes
2017-10-03 12:44:38RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-25 Cont ID  
Sent By cpuell Date 2017-09-25 Time 10:11 Rev Time 0.00
Received By cpuell Date 2017-09-15 Time 11:23 Sent To  
Notes
2017-09-18 11:23:53PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-04 Cont ID  
Sent By thunt Date 2017-10-04 Time 14:38 Rev Time 0.00
Received By thunt Date 2017-10-04 Time 14:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By thunt Date 2017-09-19 Time 15:14 Rev Time 0.00
Received By thunt Date 2017-09-19 Time 15:14 Sent To  
Notes
2017-09-19 15:23:021ST PLUMBING REVIEW 09/19/17 DENIED
  
 1) GREASE INTERCEPTOR NOT PER APPROVED PLANS. SUBMITTED
 DRAWING SHOWS 750 GALLON INTERCEPTER. THE APPROVED
 INTERCEPTOR AND WHAT THE DESIGN PROFESSIONAL SPEC OUT
 FOR THIS JOB IS A 1250 GALLON TANK. ALSO MUST COMPLY
 WITH CITY PUBLIC WORKS STANDARD DETAIL GS-7.1
  
 2) THE VALUATION IS LOW AND MUST INCLUDE ALL COST FOR
 MATERIAL AND LABOR. PROVIDE A BONA FIDEN SIGNED
 CONTRACT FOR THIS JOB FBC 109.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  