Plan Review Details - Permit 17090196
Plan Review Stops For Permit 17090196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By aclange Date 2017-11-17 Time 14:16 Rev Time 0.00
Received By aclange Date 2017-11-17 Time 14:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 16:06 Rev Time 0.00
Received By shill Date 2017-09-22 Time 16:06 Sent To  
Notes
2017-09-22 16:33:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS481.
  
 2. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED, FBC
 107.
  
 3. TITLE BLOCK STATES THIS IS A "CUSTOM RESIDENCE";
 THIS DOES NOT APPEAR TO BE CONSISTENT WITH THE WORK
 PROPOSED, REVISE.
  
 4. MOST OF THE DETAILS ON SHEET A5 LACK NUMBERS,
 REVISE. REVISE THE PLAN TO SHOW WHERE THE SECTIONS OR
 DETAILS ARE APPLICABLE, FBC 107.
  
 5. IS THE FACILITY AVAILABLE FOR RENT OR IS IT
 EXCLUSIVELY FOR USE BY MEMBERS OF THE TEMPLE? IT IS NOT
 CLEAR WHETHER OR NOT FBC ACCESSIBILITY IS APPLICABLE.
 REVISE PLAN TO CLARIFY; THIS MAY BE A STATEMENT ON THE
 PLAN.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-11-17 Cont ID  
Sent By jpearson Date 2017-11-17 Time 10:12 Rev Time 0.00
Received By jpearson Date 2017-11-17 Time 10:12 Sent To  
Notes
2017-11-17 10:12:04FOLLOWING COMMENTS (2) ADDED TO PLAN AS PROVISO:
  
 1. RISER DIAGRAM AND PANEL SCHEDULES PROVIDED SHOW THE
 HIGH LEG ON PHASE C. HIGH LEG IS REQUIRED TO BE ON
 PHASE B PER THE NEC. PROVIDE CORRECTION FOR RISER AND
 PANEL SCHEDULES. NEC 408.3(E)
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By jpearson Date 2017-09-22 Time 15:21 Rev Time 0.00
Received By jpearson Date 2017-09-22 Time 15:21 Sent To  
Notes
2017-09-22 15:21:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30; FBC 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. PLAN DOES NOT SHOW ANY TYPE OF
 AUTOMATIC LIGHTING CONTROL REQUIRED BY THE ENERGY CODE.
 FBC CE 405.2.2, 405.2.2.2
 6. NOTE 12 OF GENERAL ELECTRICAL NOTES STATES THAT
 ROMEX MAY BE USED IN THIS INSTALLATION. PROVIDE DETAILS
 OF BUILDING TYPE TO COMPLY WITH PERMITTED INSTALLATIONS
 FOR ROMEX, OR REVISE NOTE. NEC 334.10, 12
 7. PROVIDE FIXTURE SCHEDULE AND LEGEND. FBC 107.2.1;
 NEC 110.3
 8. PROVIDE 2 COPIES OF PLAN FOR REVIEW, PROVIDE CORRECT
 ADDRESS ON PLANS FOR PROJECT, PROVIDE PROPER SIGNATURE
 AND SEAL PER FS 471. FS 471.003(2)(H); 471.025; FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-11-07 Cont ID  
Sent By pleduc Date 2017-11-07 Time   Rev Time 0.00
Received By pleduc Date 2017-11-07 Time 12:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By pleduc Date 2017-09-14 Time   Rev Time 0.00
Received By pleduc Date 2017-09-14 Time 11:52 Sent To  
Notes
2017-09-14 14:13:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO ADDRESS ON THE TILTE BLOCK AND THERE IS
 WORDING INDICATING TEMPLE BETH EL, MARTIN COUNTY,
 FLORIDA.
  
 PLEASE PROVIDE THE CORRECT ADDRESS WITHIN THE TITLE
 BLOCK
  
  
  
 2) THERE IS ONLY ONE SET OF PLANS SUBMITTED.
  
 PLEASE PROVIDE AT LEAST ONE ADDITIONAL SET.
  
  
  
 3) THERE IS NO INDICATION OF COMPLIANCE WITH ANY FIRE
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE THE APPLICABLE
 NOTES.
  
  
  
 4) THERE ARE NO INDICATIONS OF ANY FIRE SPRINKLER OR
 FIRE ALARM SYSTEMS.
  
 PLEASE PROVIDE INDICATING NOTES.
  
 ALL FIRE SPRINKLER AND FIRE ALARM WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
  
 5) NEW DOORS ARE INDICATED; HOWEVER, THERE IS NOT DOOR
 SCHEDULE.
  
 PLEASE PROVIDE A DOOR SCHEDULE INCLUDING HARDWARE.
  
  
  
 6) NEW WALLS ARE INDICATED; HOWEVER, THERE IS NO
 INDICATOR OF WHAT WALL TYPE IS BEING USED.
  
 PLEASE CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-11-17 Cont ID  
Sent By aclange Date 2017-11-17 Time 14:16 Rev Time 0.00
Received By aclange Date 2017-11-03 Time 13:04 Sent To  
Notes
2017-11-06 13:04:34B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 16:33 Rev Time 0.00
Received By shill Date 2017-09-07 Time 14:43 Sent To  
Notes
2017-09-07 14:43:19B27

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-11-13 Cont ID  
Sent By ccole Date 2017-11-13 Time 16:09 Rev Time 0.00
Received By ccole Date 2017-11-13 Time 15:34 Sent To  
Notes
2017-11-13 16:13:04THE ARCHITECT OF RECORD IS STATING IN HIS RESPONSE
 NARRATIVE TO THE 1ST REVIEW COMMENTS THAT NO MECHANICAL
 ALTERATIONS WILL BE DONE ON THE PROJECT.
 BASED ON THAT RESPONSE, A SEPARATE PERMIT AND PLANS
 SHALL BE SUBMITTED FOR ANY MECHANICAL WORK THAT OCCURS
 ON THE PROJECT.
 CCOLE- 11/13/17
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By ccole Date 2017-09-22 Time 10:00 Rev Time 0.00
Received By ccole Date 2017-09-22 Time 09:58 Sent To  
Notes
2017-09-22 10:08:281ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING
 CODES
 PERMIT #17090196
 9/122/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS SHOWING ALL REQUIRED
 ALTERATIONS TO THE SYSTEMS TO ACCOMODATE THE FLOOR PLAN
 CHANGES.
  
 2) THE ARCHITECT SHALL PROVIDE ORIGINAL SEALS AND
 SIGNATURES TO THE PLANS- SECTION 61G15- 16.003 FLORIDA
 AMINISTRATIVE CODE.
  
 3) A MINIMUM OF TWO SETS OF PLANS ARE REQUIRED PER
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  