Plan Review Details - Permit 17090105
Plan Review Stops For Permit 17090105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-18 Cont ID  
Sent By shill Date 2017-09-18 Time 11:11 Rev Time 0.00
Received By shill Date 2017-09-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jgomez Date 2017-09-06 Time 16:10 Rev Time 0.00
Received By jgomez Date 2017-09-06 Time 14:20 Sent To  
Notes
2017-09-06 14:34:10REVIEW CHECKLIST FOR RESIDENTIAL (R3) REVISION
 ADDRESSING BUILDING REVIEW PROVISO.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 B) IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR
 THE ENTIRE HOUSE (1231 S.F.). IF DOING THE CALCULATIONS
 FOR THE ENTIRE HOUSE, THEN CLARIFY WHY THERE IS NOT
 KITCHEN SHOWN ON PAGE 2 OF 4. ALSO, CLARIFY WHY THERE
 IS ONLY ONE BEDROOM AND ONE PERSON SHOWN ON PAGE 2 OF
 4. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 C) INSULATION R-VALUE FOR WOOD FRAMED WALL ON ITEM
 #9(B) DOESN'T MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) CEILING INSULATION R-VALUE ON ITEM #10 DOESN'T MATCH
 ARCHITECT'S PLANS. NOTE: INCLUDE THE NEW MASTER BEDROOM
 AREA AND NEW LEISURE ROOM AREA AND EXISTING HOUSE
 CEILING INSULATION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 E) ITEM #10 SPECIFIES UNVENTED DECK. PERSON PREPARING
 THE ENERGY CALCULATIONS TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE UNVENTED
 ROOF AS REQUIRED BY SEC. R806.5 FBC-RESIDENTIAL, 5TH
 EDITION.
 NOTE: HOUSE WAS BUILT IN 1953. TYPICALLY ROOFS WERE
 VENTED. PROVIDE PROOF THAT ROOF IS NOT VENTED.
  
 F)ROOF TYPE IS MISSING THE GABLE AREA BY THE NEW MASTER
 BEDROOM AND THE FLAT ROOF BY THE NEW LEISURE ROOM. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 G) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T
 MATCH ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION. REVISE WINDOWS SQUARE FOOTAGE AND
 ORIENTATION.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 H) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DON'T MATCH
 ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION. WHERE ARE THE WOOD DOORS. ALSO, REVISE
 THE DOOR ORIENTATION TO MATCH PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
  
 I) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR THE SWING DOOR. NOTE: NOA 15-0602.06
 SUBMITTED IS FOR THE MASTER BEDROOM WINDOW. NEED
 PRODUCT APPROVAL FOR THE LEISURE ROOM EXTERIOR DOOR.
  
 3- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-18 Cont ID  
Sent By shill Date 2017-09-18 Time 11:12 Rev Time 0.00
Received By shill Date 2017-09-18 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-06 Cont ID  
Sent By jgomez Date 2017-09-06 Time 16:16 Rev Time 0.00
Received By jgomez Date 2017-09-05 Time 10:23 Sent To  
Notes
2017-09-06 10:23:43REVISION ROUTED TO JGOMEZ