2017-09-06 14:34:10 | REVIEW CHECKLIST FOR RESIDENTIAL (R3) REVISION |
| ADDRESSING BUILDING REVIEW PROVISO. |
| CODE: FBC 5TH EDITION (2014). |
| |
| |
| 1- ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR |
| THE ENTIRE HOUSE (1231 S.F.). IF DOING THE CALCULATIONS |
| FOR THE ENTIRE HOUSE, THEN CLARIFY WHY THERE IS NOT |
| KITCHEN SHOWN ON PAGE 2 OF 4. ALSO, CLARIFY WHY THERE |
| IS ONLY ONE BEDROOM AND ONE PERSON SHOWN ON PAGE 2 OF |
| 4. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| |
| C) INSULATION R-VALUE FOR WOOD FRAMED WALL ON ITEM |
| #9(B) DOESN'T MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| D) CEILING INSULATION R-VALUE ON ITEM #10 DOESN'T MATCH |
| ARCHITECT'S PLANS. NOTE: INCLUDE THE NEW MASTER BEDROOM |
| AREA AND NEW LEISURE ROOM AREA AND EXISTING HOUSE |
| CEILING INSULATION. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| E) ITEM #10 SPECIFIES UNVENTED DECK. PERSON PREPARING |
| THE ENERGY CALCULATIONS TO PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE UNVENTED |
| ROOF AS REQUIRED BY SEC. R806.5 FBC-RESIDENTIAL, 5TH |
| EDITION. |
| NOTE: HOUSE WAS BUILT IN 1953. TYPICALLY ROOFS WERE |
| VENTED. PROVIDE PROOF THAT ROOF IS NOT VENTED. |
| |
| F)ROOF TYPE IS MISSING THE GABLE AREA BY THE NEW MASTER |
| BEDROOM AND THE FLAT ROOF BY THE NEW LEISURE ROOM. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| G) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 4 DOESN'T |
| MATCH ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. REVISE WINDOWS SQUARE FOOTAGE AND |
| ORIENTATION. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| H) DOORS INFORMATION SHOWN ON PAGE 3 OF 4 DON'T MATCH |
| ARCHITECTURAL PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. WHERE ARE THE WOOD DOORS. ALSO, REVISE |
| THE DOOR ORIENTATION TO MATCH PLANS. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| I) CONTRACTOR TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. |
| |
| 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR THE SWING DOOR. NOTE: NOA 15-0602.06 |
| SUBMITTED IS FOR THE MASTER BEDROOM WINDOW. NEED |
| PRODUCT APPROVAL FOR THE LEISURE ROOM EXTERIOR DOOR. |
| |
| 3- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVAL. SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| |