Plan Review Details - Permit 17090100
Plan Review Stops For Permit 17090100
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-13 Cont ID  
Sent By rmcdouga Date 2017-09-13 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2017-09-13 Time 17:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-18 Cont ID  
Sent By jleahy Date 2017-09-18 Time 17:20 Rev Time 0.00
Received By jleahy Date 2017-09-18 Time 17:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-09-13 Cont ID  
Sent By rmcdouga Date 2017-09-13 Time 17:21 Rev Time 0.00
Received By rmcdouga Date 2017-09-13 Time 17:21 Sent To  
Notes
2017-09-13 17:22:16NO GAS SHOWN ON THE PLANS. A SEPARATE PERMIT,
 APPLICATION AND REVIEW IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-28 Cont ID  
Sent By tklarge Date 2017-09-28 Time 05:49 Rev Time 0.00
Received By tklarge Date 2017-09-26 Time 13:14 Sent To  
Notes
2017-09-27 13:14:33REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-18 Cont ID  
Sent By jleahy Date 2017-09-18 Time 17:20 Rev Time 0.00
Received By jleahy Date 2017-09-05 Time 14:44 Sent To  
Notes
2017-09-06 14:44:18ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-28 Cont ID  
Sent By tklarge Date 2017-09-28 Time 05:48 Rev Time 0.00
Received By tklarge Date 2017-09-28 Time 05:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By tklarge Date 2017-09-18 Time 09:48 Rev Time 0.00
Received By tklarge Date 2017-09-14 Time 08:45 Sent To  
Notes
2017-09-18 09:48:361) SHT. 2 OF 3 - PIPING DIAGRAM - SHOWS A 2 INCH MAIN
 DRAIN TO THE EXISTING POOL PUMP AND ALSO SHOWS A 3 INCH
 MAIN DRAIN CONNECTED TO THE PUMP, FILTER AND HEATER.
 CLARIFY.
 2) SHT.2 OF 3 - THE PIPING DIAGRAM SHOWS A 3 INCH
 RETURN TO THE SPA CONNECTED TO THE 2 HP BLOWER AND THE
 PIPING DIAGRAM ALSO SHOWS A 2 INCH RETURN TO THE SPA
 FROM THE EXISTING POOL PUMP. CLARIFY.
 3) SHT. 2 OF 3 - THE SKIMMER AND VAC DETAIL SHOWS A 3
 INCH RETURN TO THE SPA AND THE PIPING DIAGRAM SHOWS A 3
 INCH AND ALSO A 2 INCH RETURN TO THE SPA. CLARIFY.
 4) SHT. 3 OF 3 - THERE IS A AREA ON THE PLAN LABELED AS
 " ASPS-15" BUT ALL THE ITEMS IN THIS AREA ARE BLANK.
 CLARIFY.
 5) THE PLAN SHOWS AN EXISTING PUMP BUT SPECS HAVE BEEN
 SUBMITTED FOR A NEW PUMP. CLARIFY.
  
 I AM CONFUSED AS TO THIS PIPING ARRANGEMENT .PLEASE
 SUBMIT A NARRATIVE THAT EXPLAINS THIS PIPING
 ARRANGEMENT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-09-07 Cont ID  
Sent By njwira Date 2017-09-07 Time 16:56 Rev Time 0.00
Received By njwira Date 2017-09-07 Time 15:59 Sent To  
Notes
***NONE***