Plan Review Details - Permit 17090028
Plan Review Stops For Permit 17090028
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-03-21 Cont ID  
Sent By tklarge Date 2018-03-21 Time 13:00 Rev Time 0.00
Received By tklarge Date 2018-03-21 Time 13:00 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By thunt Date 2017-09-06 Time 14:24 Rev Time 0.00
Received By thunt Date 2017-09-06 Time 14:24 Sent To  
Notes
2017-09-06 14:36:39GAS 1ST REVIEW-DENIED, THERE ARE NO SUPPORTING
 DOCUMENTS SUPPLIED WITH YOUR PERMIT APPLICATION.
  
 THE VALUE OF THIS JOB SEEMS TOO LOW. PLEASE PROVIDE A
 BONA FIDE SIGNED CONTRACT TO COMPLY WITH 109.3 FBC
  
 CITY RECORDS SHOW EXISTING POOL HEATER AS A HEAT PUMP
 INSTALLED UNDER PERMIT #167071123. THE ONLY PERMIT FOR
 GAS AT THIS PROPERTY IS FROM 2002 FOR THE RANGE AND
 BBQ. PLEASE SUBMIT THE FOLLOWING FBC 107.2
  
 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. G2413
  
 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 4) CITY RECORDS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-21 Cont ID  
Sent By tklarge Date 2018-03-21 Time 13:01 Rev Time 0.00
Received By tklarge Date 2018-03-12 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-06 Cont ID  
Sent By thunt Date 2017-09-06 Time 14:37 Rev Time 0.00
Received By thunt Date 2017-09-01 Time 09:40 Sent To  
Notes
2017-09-05 09:41:09PLUMB <5K