Plan Review Details - Permit 17090016
Plan Review Stops For Permit 17090016
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-10-31 Cont ID  
Sent By J.Walker Date 2017-10-31 Time   Rev Time 0.20
Received By   Date 2017-10-30 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By J.Walker Date 2017-09-26 Time   Rev Time 0.20
Received By   Date 2017-09-25 Time   Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-09-06 Cont ID  
Sent By J.Walker Date 2017-09-06 Time   Rev Time 0.25
Received By   Date 2017-09-05 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2017-12-14 Time   Rev Time 0.00
Received By lmarchan Date 2017-12-08 Time 14:32 Sent To  
Notes
2017-12-12 14:32:41ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2017-11-09 Time 10:33 Sent To  
Notes
2017-11-13 10:33:13RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2017-11-02 Time   Rev Time 0.00
Received By lmarchan Date 2017-10-27 Time 11:42 Sent To  
Notes
2017-10-30 11:42:34RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-24 Cont ID  
Sent By hmoser Date 2017-10-24 Time 16:59 Rev Time 0.00
Received By hmoser Date 2017-09-20 Time 14:22 Sent To  
Notes
2017-09-22 14:22:26RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-14 Cont ID  
Sent By hmoser Date 2017-09-14 Time 13:25 Rev Time 0.00
Received By hmoser Date 2017-09-01 Time 09:39 Sent To  
Notes
2017-09-05 09:40:07ROUTED TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2017-12-14 Cont ID  
Sent By ccole Date 2017-12-14 Time 09:30 Rev Time 0.00
Received By ccole Date 2017-12-14 Time 09:25 Sent To I
Notes
2017-12-14 09:36:13MECHANCIAL PROVISIO;
  
 THE SUBMITTED LETTERS FROM THE HOOD DEPOT ENGINEER AND
 THE EOR ALEJANDRO FRANYIE MUST BEAR ORIGNAL SIGNATURES
 AND SEALS- SECTION 61G15- 23.002 FAC.
 A HOLD WILL BE PLACED ON THE CC PENDING RECEIPT OF THE
 LETTERS.
  
 CCOLE- 12/14/17

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-11-16 Cont ID  
Sent By ccole Date 2017-11-16 Time 16:39 Rev Time 0.00
Received By ccole Date 2017-11-16 Time 16:39 Sent To P
Notes
2017-11-16 16:43:094TH REVIEW FBC-2014 MECHANICAL
 PERMIT #170I90016
 11/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS WERE RESUBMITTED WITHOUT ANY CORRECTIONS
 OR RESPONSES TO THE PREVIOUS MECHANICAL REVIEW
 COMMENTS. I HAVE REPINTED THE COMMENTS BELOW- PLEASE
 COMPLY.
  
 1) REFER TO SECTION 506.3.11.2 FIELD APPLIED GREASE
 DUCT ENCLOSURE FBC-14 MECHANICAL: "THE SURFACE OF THE
 DUCT SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM
 THE POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET
 TERMINAL." "PARTIAL APPLICATION OF A FIELD-APPLIED
 GREASE DUCT ENCLOSURE SYSTEM SHALL NOT BE INSTALLED FOR
 THE SOLE PURPOSE OF REDUCING CLEARANCES TO COMBUSTIBLES
 AT ISOLATED SECTIONS OF GREASE DUCT." IT APPEARS BY
 THIS SECTION THAT THE DUCT WRAPPING AS SHOWN ON THE
 PLAN IS NOT BEING INSTALLED IN ACCORDANCE WITH THE ASTM
 E 2336 LISTING. ADDITIONAL INFORMATION FROM THE PRODUCT
 MANUFACTURER WILL BE REQUIRED, AS WELL AS EVIDENCE THAT
 THE INSTALLATION AS SHOWN DOES NOT VOID THE UL LISTING.
 PLEASE NOTE THAT SECTION 506.3.6 PERMITS A 3" CLEARANCE
 TO NON-COMBUSTIBLE CONSTRUCTION AND GYPSUM WALL BOARD
 ATTACHED TO NON-COMBUSTIBLE STRUCTURES.
  
 2) REFER TO SECTION 8.1.3.6 NFPA 96 REGARDING THE
 INLINE FAN: WHERE THE DUCT SYSTEM CONNECTED TO THE FAN
 IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE
 EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE
 RESISTANCE RATING AS THE ENCLOSURE. ACCORDING TO THIS
 SECTION, THE FAN MUST BE IN A FIRE-RATED ROOM.
  
 3) IN RESPONSE TO PREVIOUS REVIEW COMMENT #3, THE HOOD
 DESIGNER IS STATING THAT THE ADDED HEATING AND COOLING
 LOADS OF THE MUA (MAKEUP AIR) DO NOT EXCEED THE
 CAPACITY OF THE AC SYSTEM. PLEASE PROVIDE ACTUAL
 EVIDENCE IN THE FORM OF CALCULATIONS, DETAILS ETC. TO
 SUPPORT AND PROVE THIS CLAIM.
  
 4) PROVIDE A DETAILL SHOWING HOW GREASE FROM THE INLINE
 FAN WILL BE DISPOSED OF PROPERLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-11-02 Cont ID  
Sent By ccole Date 2017-11-02 Time 15:44 Rev Time 0.00
Received By ccole Date 2017-11-02 Time 15:44 Sent To  
Notes
2017-11-02 16:20:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17090016
 11/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 506.3.11.2 FIELD APPLIED GREASE
 DUCT ENCLOSURE FBC-14 MECHANICAL: "THE SURFACE OF THE
 DUCT SHALL BE CONTINUOUSLY COVERED ON ALL SIDES FROM
 THE POINT AT WHICH THE DUCT ORIGINATES TO THE OUTLET
 TERMINAL." "PARTIAL APPLICATION OF A FIELD-APPLIED
 GREASE DUCT ENCLOSURE SYSTEM SHALL NOT BE INSTALLED FOR
 THE SOLE PURPOSE OF REDUCING CLEARANCES TO COMBUSTIBLES
 AT ISOLATED SECTIONS OF GREASE DUCT." IT APPEARS BY
 THIS SECTION THAT THE DUCT WRAPPING AS SHOWN ON THE
 PLAN IS NOT BEING INSTALLED IN ACCORDANCE WITH THE ASTM
 E 2336 LISTING. ADDITIONAL INFORMATION FROM THE PRODUCT
 MANUFACTURER WILL BE REQUIRED, AS WELL AS EVIDENCE THAT
 THE INSTALLATION AS SHOWN DOES NOT VOID THE UL LISTING.
 PLEASE NOTE THAT SECTION 506.3.6 PERMITS A 3" CLEARANCE
 TO NON-COMBUSTIBLE CONSTRUCTION AND GYPSUM WALL BOARD
 ATTACHED TO NON-COMBUSTIBLE STRUCTURES.
  
 2) REFER TO SECTION 8.1.3.6 NFPA 96 REGARDING THE
 INLINE FAN: WHERE THE DUCT SYSTEM CONNECTED TO THE FAN
 IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE
 EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE
 RESISTANCE RATING AS THE ENCLOSURE. ACCORDING TO THIS
 SECTION, THE FAN MUST BE IN A FIRE-RATED ROOM.
  
 3) IN RESPONSE TO PREVIOUS REVIEW COMMENT #3, THE HOOD
 DESIGNER IS STATING THAT THE ADDED HEATING AND COOLING
 LOADS OF THE MUA (MAKEUP AIR) DO NOT EXCEED THE
 CAPACITY OF THE AC SYSTEM. PLEASE PROVIDE ACTUAL
 EVIDENCE IN THE FORM OF CALCULATIONS, DETAILS ETC. TO
 SUPPORT AND PROVE THIS CLAIM.
  
 4) PROVIDE A DETAILL SHOWING HOW GREASE FROM THE INLINE
 FAN WILL BE DISPOSED OF PROPERLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-10-24 Cont ID  
Sent By hmoser Date 2017-10-24 Time 16:58 Rev Time 0.00
Received By hmoser Date 2017-10-24 Time 16:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By hmoser Date 2017-09-14 Time 13:24 Rev Time 0.00
Received By hmoser Date 2017-09-14 Time 12:51 Sent To  
Notes
2017-09-14 13:24:39PLAN DENIED
 1) PLEASE INDICATE ON PLAN HOW YOU PLAN ON MEETING THE
 INTENT
 OF SECTION 506.3.11 GREASE DUCT ENCLOSURES WITH INLINE
 FAN.
 WITH OUT WRAPPING THE FAN.
 2) SOMEONE NEEDS TO REVISE A PLUMBING PAGE FOR GREASE
 DRAIN
 TO GREASE TRAP OFF INLINE FAN. SECTION 107 FBC.
 3) PLEASE INDICATE ON THE PLAN HOW YOU PLAN ON MEETING
 THE
 INTENT OF SECTION 508.1.1 MAKE UP AIR TEMPERATURE
 2014 FBC (M)
 4) ADDRESS ON PLAN IS NOT CORRECT
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2017-11-21 Cont ID  
Sent By gjohnson Date 2017-11-21 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2017-11-21 Time 13:53 Sent To  
Notes
2017-11-21 13:54:04PLUMB SHALL BE REVISED UNDER MASTER 16020194/ GPJ

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-11-07 Cont ID  
Sent By gjohnson Date 2017-11-07 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2017-11-07 Time 13:09 Sent To P
Notes
2017-11-07 13:33:191ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DETAIL SHOWING HOW GREASE WILL BE
 DISPOSED OF FROM THE INLINE FAN, IF THE PLUMBING SYSTEM
 IS BEING REVISED IT SHALL BE UNDER THE MASTER16020194.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711