2017-09-05 15:12:00 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17081385 |
| W. P. B. PERMIT: 16041215 |
| ADD: 2001 S. DIXIE HWY. |
| CONT: MAC ENTERPRISES |
| TEL: 561-236-3627 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. SEPT. 06/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE ADDITIONAL INFORMATION. THIS PROJECT |
| HAS HAD BOTH PLAN REVIEW AND INSPECTIONS COMPLETED BY |
| TEW & TAYLOR A PRIVATE PROVIDER COMPANY. A CONDITIONAL |
| USE CERTIFICATE OF COMPLIANCE WAS ISSUED BY TEW & |
| TAYLOR SINCE THERE HAS BEEN NO CERTIFICATE OF |
| OCCUPANCY, HAS NOT BEEN ISSUED THEN SHOULDN?T TEW & |
| TAYLOR CONTINUE TO PROVIDE SERVICES? 107.2.1.3 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 2) THIS REVISION 17081385 REFERENCED PERMIT 16041215 AS |
| THE PRIME PERMIT. PLEASE NOTE UNDER THE PRIME PERMIT |
| THE STRUCTURAL ENGINEERING COMPANY FOR THE PROJECT WAS |
| BCC ENGINEERING WITH CHRISTIAN AQUINO THE STRUCTURAL P. |
| E. THE SUBMITTED PLANS WAS CREATED BY EDGER DUENAS P. |
| E. WITH BUNKER ENGINEERING. IS EDGER DUENAS P. E. |
| EITHER A DELEGATE ENGINEER OR A SUCCESSOR ENGINEER? |
| |
| 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL |
| 61G-15-30.006 (3). DELEGATED ENGINEER |
| 61G 15-27.001 SUCCESSOR PROFESSIONAL ENGINEERING. |
| |
| 3) DISCREPANCY IN PLANS, THE ORIGINAL PERMIT 16041215 |
| WAS DESIGNED TO 180 MPH, BUILDING CATEGORY III AND |
| EXPOSURE C. SINCE THEN THERE HAS BEEN MEETINGS FOR |
| EXPANDING THE SCHOOL, AND A FOUNDATION PERMIT APPLIED |
| FOR. THIS NEW SECTION OR WING IS AN ADDITION TO THE |
| ORIGINAL BUILDING AND THE OCCUPANT LOAD WILL QUALIFY |
| THIS BUILDING TO BE A THRESHOLD BUILDING. THE ORIGINAL |
| DESIGN WAS IN SINK FOR THE ADDITION WITH THE |
| CLASSIFICATION AND BUILDING CLASSIFICATION. THE NEW |
| BUILDING DESIGN SHOWS A WIND SPEED AT 170 VULT AND A |
| EXPOSURE B. DISCREPANCY IN PLANS. 107.2.1.3. |
| |
| PLEASE REVIEW 2014 FBC-B 609.4.2 SURFACE ROUGHNESS |
| CATEGORIES. SURFACE ROUGHNESS C. THIS SURFACE ROUGHNESS |
| SHALL ALSO APPLY TO ANY BUILDING LOCATED WITHIN SURFACE |
| ROUGHNESS B-TYPE TERRAIN WHERE THE BUILDING IS WITHIN |
| 100 FEET (30 M) HORIZONTALLY IN ANY DIRECTION OF OPEN |
| AREAS OF SURFACE ROUGHNESS C OR D-TYPE TERRAIN THAT |
| EXTENDS MORE THAN 600 FEET IN THE UPWIND DIRECTION AND |
| A WIDTH GREATER THAN 150 FEET. |
| |
| FBC-B TABLE 1604.5. RISK CATEGORY OF BUILDINGS AND |
| OTHER STRUCTURES. RISK CATEGORY III. BUILDINGS AND |
| OTHER STRUCTURES CONTAINING ELEMENTARY SCHOOL, |
| SECONDARY SCHOOL OR DAY CARE FACILITIES WITH AN |
| OCCUPANT LOAD GREATER THAN 250. |
| |
| 4) SHEET A.1 SHOWS 3 DOORS AS EXISTING OVERHEAD DOORS, |
| 122,123 & 124. PLEASE NOTE THAT PREVIOUS REVISION THESE |
| OPENINGS WERE REVISED TO BE MODIFIED. UNDER REVISION |
| 17070951 THE HEADERS WERE EXPANDED, AND UNDER REVISION |
| 16080972 WAS APPLIED FOR OVERHEAD GARAGE DOORS WITH |
| HYDRAULIC LIFTS. THIS REVISION WAS DENIED ONCE BUT HAS |
| NEVER REAPPLIED IT IS AN OPEN REVISION THAT HAS TO BE |
| RESOLVED BEFORE A CERTIFICATE OF OCCUPANCY CAN BE |
| ISSUED. |
| |
| 5) SHEET A1 SHOWS UNITS LABELED 19 & 20 A COLD WELL AND |
| A HOT WELL, IS THIS PART OF A SERVING LINE? IS |
| COMPLIANCE WITH 2014 FBC-ACCESS. CODE 904.5 FOOD |
| SERVICE LINES REQUIRED. |
| |
| 5A) 904.5.1 SELF-SERVICE SHELVES AND DISPENSING |
| DEVICES. SELF-SERVICE SHELVES AND DISPENSING DEVICES |
| FOR TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES |
| SHALL COMPLY WITH 308. |
| |
| 5B) 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL |
| BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 6) STRUCTURAL SHEET 1OF 1 INDICATES A W 14X26 STEEL |
| BEAM AND 2 VERTICAL 4X4 LEGS. THE PLANS DO NOT INDICATE |
| THE WELDS TO THE TOP OF THE VERTICAL LEG NOR THE BOTTOM |
| WELDS. THE OTHER ISSUE IS THE A/C STAND BY OTHERS. THE |
| VERTICAL LEGS APPEAR TO STOP AT THE ROOF LINE. THE |
| PLANS INDICATE THE ROOF STAND BY OTHERS, THIS MEANS THE |
| ROOF STAND MUST HAVE THEIR SUPPORT LEGS AT 33 INCHES |
| APART. THIS ALSO MEANS THE OTHER LEGS OF THE A/C STAND |
| WILL HAVE TO HIT THE OTHER SUPPORTS PERFECTLY, NO |
| MENTION OF HOW THE ROOF STANDS ARE TO BE ANCHORED? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED . |
| |
| 7) SHEET A1 INDICATES WITH NOTE 11 A HOOD SYSTEM. THIS |
| WILL REQUIRE A SEPARATE PERMIT AND ROOF BRACING AND |
| FRAMING FOR THE NEW ROOF TOP OPENING AND ANCHORING FOR |
| THE ROOF TOP CURBS AND INTAKE AND EXHAUST SYSTEMS. FOR |
| ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |