Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-09-29 Cont ID  
Sent By pleduc Date 2017-09-29 Time   Rev Time 0.00
Received By pleduc Date 2017-09-27 Time 16:59 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By pleduc Date 2017-08-30 Time   Rev Time 0.00
Received By pleduc Date 2017-08-30 Time 13:01 Sent To M
Notes
2017-08-30 14:01:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF MULTIPLE FLEXHEAD PIPING
 ATTACHING TO THE EXISTING SYSTEM. THE EXISTING SYSTEM
 WAS NOT DESIGNED WITH FLEXHEAD PIPING.
  
 DUE TO THE POTENTIAL FOR ADDED FRICTION LOSS OF THIS
 PIPING PLEASE PROVIDE THE APPLICABLE NEW HYDRALIC
 CALCULATIONS FOR THIS EXISTING SYSTEM WITH THE ADDED
 FLEXHEAD PIPING TO SHOW THE REQUIRED FLOW.
  
  
  
 2) MANUFACTURES SPECIFICATION SHEETS FOR THE FLEXHEAD
 PIPING WAS NOT PROVIDED.
  
 PLEASE PROVIDE THE APPLICABLE SPEC SHEETS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2017-10-11 Time   Rev Time 0.00
Received By lmarchan Date 2017-09-25 Time 13:31 Sent To  
Notes
2017-09-26 13:32:09RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-07 Cont ID  
Sent By hmoser Date 2017-09-07 Time 11:48 Rev Time 0.00
Received By hmoser Date 2017-08-29 Time 09:47 Sent To  
Notes
2017-08-30 09:48:06ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By ccole Date 2017-10-11 Time 12:08 Rev Time 0.00
Received By ccole Date 2017-10-11 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-07 Cont ID  
Sent By hmoser Date 2017-09-07 Time 11:48 Rev Time 0.00
Received By hmoser Date 2017-09-07 Time 11:47 Sent To  
Notes
2017-09-07 11:48:07PLAN DENIED
 REFER TO FIRE COMMENTS.HM.