Plan Review Details - Permit 17081371
Plan Review Stops For Permit 17081371 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2017-09-29 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-09-29 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-09-27 |
Time |
16:59 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-08-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-08-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-08-30 |
Time |
13:01 |
Sent To |
M |
|
Notes |
2017-08-30 14:01:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF MULTIPLE FLEXHEAD PIPING | | ATTACHING TO THE EXISTING SYSTEM. THE EXISTING SYSTEM | | WAS NOT DESIGNED WITH FLEXHEAD PIPING. | | | | DUE TO THE POTENTIAL FOR ADDED FRICTION LOSS OF THIS | | PIPING PLEASE PROVIDE THE APPLICABLE NEW HYDRALIC | | CALCULATIONS FOR THIS EXISTING SYSTEM WITH THE ADDED | | FLEXHEAD PIPING TO SHOW THE REQUIRED FLOW. | | | | | | | | 2) MANUFACTURES SPECIFICATION SHEETS FOR THE FLEXHEAD | | PIPING WAS NOT PROVIDED. | | | | PLEASE PROVIDE THE APPLICABLE SPEC SHEETS. | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-10-11 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-09-25 |
Time |
13:31 |
Sent To |
|
|
Notes |
2017-09-26 13:32:09 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-09-07 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-09-07 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-08-29 |
Time |
09:47 |
Sent To |
|
|
Notes |
2017-08-30 09:48:06 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-10-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-10-11 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-10-11 |
Time |
11:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-09-07 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-09-07 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-09-07 |
Time |
11:47 |
Sent To |
|
|
Notes |
2017-09-07 11:48:07 | PLAN DENIED | | REFER TO FIRE COMMENTS.HM. |
|
|
|