Plan Review Details - Permit 17081230
Plan Review Stops For Permit 17081230
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-09-06 Cont ID  
Sent By   Date 2017-09-06 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2017-09-06 Time 07:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-10-03 Cont ID  
Sent By jpearson Date 2017-10-03 Time 08:27 Rev Time 0.00
Received By jpearson Date 2017-10-03 Time 08:27 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jpearson Date 2017-09-13 Time 13:00 Rev Time 0.00
Received By jpearson Date 2017-09-13 Time 13:00 Sent To  
Notes
2017-09-13 13:00:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1
 2. RECEPTACLE CONTROL INDICATED DOES NOT COVER ALL
 AREAS REQUIRED. PROVIDE CORRECTION TO INCLUDE CONTROL
 FOR AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS. FBC CE 405.7.1, ASHRAE 90.1:8.4.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-30 Cont ID  
Sent By wjolin Date 2017-08-30 Time 13:19 Rev Time 0.00
Received By wjolin Date 2017-08-30 Time 13:08 Sent To  
Notes
2017-08-30 13:19:45REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE THE
 OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). FBC
 SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED SHALL BE
 CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND
 NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE
 ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR SHALL
 ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM
 THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS,
 CONSTRUCTION OR VIOLATIONS OF THIS CODE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-05 Cont ID  
Sent By tklarge Date 2017-10-05 Time 10:09 Rev Time 0.00
Received By tklarge Date 2017-09-29 Time 13:55 Sent To  
Notes
2017-10-02 13:55:51RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-19 Cont ID  
Sent By tklarge Date 2017-09-19 Time 14:42 Rev Time 0.00
Received By tklarge Date 2017-08-25 Time 09:10 Sent To  
Notes
2017-08-28 11:42:16C09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-09-14 Cont ID  
Sent By ccole Date 2017-09-14 Time 12:48 Rev Time 0.00
Received By ccole Date 2017-09-14 Time 12:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-10-05 Cont ID  
Sent By tklarge Date 2017-10-05 Time 10:08 Rev Time 0.00
Received By tklarge Date 2017-10-05 Time 06:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By tklarge Date 2017-09-19 Time 14:42 Rev Time 0.00
Received By tklarge Date 2017-09-19 Time 11:58 Sent To  
Notes
2017-09-19 12:32:271) THE SINK IN THE BREAK ROOM AND AT THE RECEPTION AREA
 SHALL COMPLY WITH THE 2014 FBC-ACCESS. SECS.212.3, 606.
 THE PLANS HAVE AN ELEVATION OF "ADA" SINK BUT IT IS
 SPECIFIED AS TO THE LOCATION OF THIS SINK.THE MAXIMUM
 HEIGHT FOR BOTH OF THESE SINKS SHALL BE 34 INCHES ABOVE
 FINISH FLOOR TO THE TOP OF THE COUNTER.
 2) AIR ARRESTORS ARE REQUIRED ON THE DISHWASHER, WATER
 DISPENSER AND THE ICE MAKER PER THE 2014 FBC-PLUMBING
 SEC.604.9.
 3) BACKFLOW PREVENTERS ARE REQUIRED ON THE COFFEE
 MACINE, WATER DISPENSER, AND ICEMAKER. 2014 FBC
 -PLUMBING SEC.608.3, 608.16.10.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE EEMAX
 INSTANT WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P-001 - SHOW THE REQUIRED HEIGHT AND KNEE AND
 TOE CLEARANCES FOR THE HANDICAPPED ACCESSIBLE
 LAVATORIES PER THE 2014 FBC-ACCESS. SECS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  