Plan Review Details - Permit 17080883
Plan Review Stops For Permit 17080883
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-12 Cont ID  
Sent By shill Date 2018-01-12 Time 15:54 Rev Time 0.00
Received By shill Date 2018-01-12 Time 07:29 Sent To  
Notes
2018-01-12 15:54:02****PROVISOS****
 ****ISSUED AT APPLICANT'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE PARKING LOT WAS INSTALLED WITHOUT A PERMIT,
 APPLY AT THIS TIME. AN ACCESSIBLE ROUTE IS REQUIRED AND
 WILL BE REVIEWED UNDER THE PARKING LOT PERMIT.
  
 2. UNABLE TO LOCATE OCCUPANT LOAD FOR THE BUSINESS
 SPACES, REVISE PLAN TO INCLUDE, FBC B 1004.
  
 3. NO EXTERIOR LIGHTING SHOWN ON THE ENERGY CALC INPUT
 REPORT; MEANS OF EGRESS ILLUMINATION IS REQUIRED.
 CONFIRM THAT ALL ITEMS REQUIRED TO BE ON THE ENERGY
 CALC ARE INCLUDED.
  
 RESPONSE IS THAT THERE IS NO EXTERIOR ILLUMINATION.
 THIS IS REQUIRED, FBC B 1006.1. REVISE PLAN AND ENERGY
 CALCS ACCORDINGLY, OR SEND EMAIL TO EXPLAIN HOW THIS
 REQUIREMENT WILL BE MET.
  
 4. A ROOF PRODUCT APPROVAL WAS PROVIDED, ASSEMBLY
 SELECTED WITH A DP LIMITATION OF -52.5. RAS117
 CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL IS
 REQUIRED PRIOR TO ISSUANCE OF ROOF SUB PERMIT. THIS MAY
 BE SUBMITTED AT TIME OF ROOF PERMIT APPLICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 15:06 Rev Time 0.00
Received By shill Date 2017-09-22 Time 15:00 Sent To  
Notes
2017-09-22 15:06:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC A 201.1.1, VERTICAL ACCESSIBILITY IS NOT SHOWN
 FOR THE THREE ELEVATED PLATFORM AREAS. REVISE PLAN TO
 INCLUDE OR REVISE PLAN TO CLARIFY USE OF THE AREAS,
 APPLICALBE EXCEPTION(S).
  
 2. I WAS UNABLE TO FIND A LIFE SAFETY PLAN. EITHER
 PROVIDE ONE, OR REVISE THE FLOOR PLAN TO INCLUDE
 INFORMATION (OCCUPANT LOAD AND SQUARE FOOT AREA FOR
 EACH SPACE, TRAVEL DISTANCE, COMMON PATH, DEAD ENDS,
 FBC CHAPTER 10). THE OCC LOAD FOR THE ASSEMBLY SPACE
 WAS PROVIDED, BUT IS REQUIRED FOR THE REST OF THE
 BUILDING, FBC 107.
  
 3. IT APPEARS THAT A PARKING LOT WAS INSTALLED WITHOUT
 A PERMIT, PLEASE APPLY AT THIS TIME OR PROVIDE PERMIT
 NUMBER.
  
 4. REVISE PLAN TO INCLUDE INFORMATION ABOUT THE
 MERCANTILE AREA - WHAT WILL BE SOLD AND STORED HERE?
 FBC 107. ENERGY CALCS DO NOT APPEAR TO INCLUDE A
 MERCANTILE AREA; PLEASE CORRELATE. IF THIS INFORMATION
 IS NOT AVAILABLE AT THIS TIME, REVISE PLAN TO INDICATE
 THAT FUTURE MERCANTILE TENANT BUILDOUT WILL BE UNDER
 SEPARATE PERMIT.
  
 5. WHAT IS CURRENTLY THE OCCUPANCY (OR OCCUPANCIES) FOR
 THIS BUILDING? IF THIS IS A CHANGE OF OCCUPANCY, REVISE
 PLAN TO INCLUDE THIS INFORMATION, REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC EB CHAPTER 10. AN IMPACT FEE
 ASSESSMENT MAY BE REQUIRED.
  
 6. I WAS UNABLE TO LOCATE A DOOR SCHEDULE, PLEASE
 PROVIDE (INCLUDING HARDWARE SCHEDULE), FBC B 1008, FBC
 EC.
  
 7. NO DOORS ARE SHOWN ON THE ENERGY CALC INPUT REPORT,
 ARE ALL DOORS GLAZED? A HOLLOW METAL DOOR PRODUCT
 APPROVAL WAS SUBMITTED, FBC 107.
  
 8. NO EXTERIOR LIGHTING SHOWN ON THE ENERGY CALC INPUT
 REPORT; MEANS OF EGRESS ILLUMINATION IS REQUIRED.
 CONFIRM THAT ALL ITEMS REQUIRED TO BE ON THE ENERGY
 CALC ARE INCLUDED.
  
 9. A ROOF PRODUCT APPROVAL WAS PROVIDED, ASSEMBLY
 SELECTED WITH A DP LIMITATION OF -52.5. RAS117
 CALCULATIONS PREPARED BY A DESIGN PROFESSIONAL IS
 REQUIRED PRIOR TO ISSUANCE OF ROOF SUB PERMIT. THIS MAY
 BE SUBMITTED AT TIME OF ROOF PERMIT APPLICATION.
  
 10. ACCESSIBLE ROUTE REQUIRED, FBC A 202.3, 202.4.
 LANDINGS ARE SHOWN AT WHAT APPEARS TO BE THE MAIN
 ENTRANCES. ACCESSIBLE PARKING SHOULD BE ON AN
 ACCESSIBLE ROUTE, ACCESSIBLE ROUTE TO THE ALTERED AREA
 REQUIRED, REVISE TO COMPLY.
  
 11. FBC B 1026.6, 1022.4&5, ALSO SEE FIRE COMMENT
 REGARDING DOOR RATING. PLEASE ALSO SEE IBC 2012
 COMMENTARY PAGE 10-165; THIS INDICATES THAT NO OPENINGS
 ARE PERMITTED IN THE STAIR - THIS CAN BE SENT TO YOU
 UPON REQUEST BY EMAIL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-12-22 Cont ID  
Sent By jpearson Date 2017-12-22 Time 10:13 Rev Time 0.00
Received By jpearson Date 2017-12-22 Time 10:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-20 Cont ID  
Sent By jpearson Date 2017-09-20 Time 10:22 Rev Time 0.00
Received By jpearson Date 2017-09-20 Time 10:22 Sent To  
Notes
2017-09-20 10:21:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94
 2. RISER DIAGRAM SHOWS A "FUTURE PANEL C", HOWEVER,
 POWER PLAN SHOWS THIS INSTALLED AND CIRCUITS BEING FED
 FROM THIS PANEL. CLARIFY AND/OR CORRECT. FBC 107.2.1
 3. ALL KITCHEN RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 4. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS WHERE APPLICABLE FOR LOW VOLTAGE SYSTEMS,
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK-IN COOLERS, HOODS, ETC. FBC 105.1, 107.2.1
 5. OUTSIDE RECEPTACLE BY A/C EQUIPMENT REQUIRES GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. PLAN DOES NOT SHOW LIGHTING
 CONTROLLED BY EITHER TIME CLOCK OR OCCUPANCY SENSORS
 REQUIRED. FBC CE 405.2.2, 405.2.2.2
 7. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC CE 405.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-12-04 Cont ID  
Sent By pleduc Date 2017-12-04 Time   Rev Time 0.00
Received By pleduc Date 2017-12-04 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By pleduc Date 2017-08-23 Time   Rev Time 0.00
Received By pleduc Date 2017-08-22 Time 16:06 Sent To  
Notes
2017-08-23 10:39:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 2.1 - DOOR # 1 IS INDICATED TO EXIT OUT
 UNDER AN EXIT STAIR AND IS NOT INDICATED AS BEING
 RATED. PER NFPA 101 CHAPTER 7, A 1 HOUR RATED DOOR IS
 REQUIRED.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY CONSTRUCTION WITH THE FIRE
 RESISTANCE RATING REQUIRED FOR ENCLOSED STAIRS WITH
 FIXED OR SELF-CLOSING OPENING PROTECTIVES, EXCEPT AS
 FOLLOWS:
  
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050 MM) FROM THE STAIRS SHALL NOT BE
 REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS HAVE A MINIMUM
 ?-HOUR FIRE PROTECTION RATING.
  
 PLEASE PROVIDE.
  
  
 2) SHEET A 4.1 - THE FIRST FLOOR AND ROOF TRUSS SYSTEMS
 ARE INDICATED AS LIGHWEIGHT.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 PLEASE PROVIDE.
  
  
  
 3) SHEET FP 1 - THERE IS A REFERENCE INDICATING
 COMPLAINCE WITH NFPA 13 2007 EDITION. THE CURRENT
 EDITION OF NFPA 13 PER THE FLORIDA FIRE PREVENTION
 CODE, 5TH EDITION IS 2010.
  
 PLEASE CORRECT.
  
  
  
 4) SHEET FP 1 - THERE IS A CLOSET INDICATED ON THE
 FIRST FLOOR WITH NO DIMENSIONS AND NO SPRINKLER
 PROTECTION. THIS CLOSET IS REQUIRED TO HAVE SPRINKLER
 PROTECTION.
  
 PLEASE PROVIDE.
  
  
  
 5) SHEET FP 1 - THERE APPEARS TO BE ONE SPRINKLER
 SERVING UNDER THE STAIRS STORAGE SPACE. ANOTHER
 SPRINKLER APPEARS TO BE REQUIRED OR ADD A WALL TO LIMIT
 THE DISTANCE.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 5.1 - THERE IS REFERENCE TO THE ELEVATOR
 BEING INSTALLED PER MANUFACTURES SPEC. PER NFPA 1,
 CHAPTER 11, BUILDING SERVICES.
  
 11.3.1 FIRE FIGHTERS? EMERGENCY OPERATIONS.
 11.3.1.1 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS? EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS. [101:9.4.3.1]
  
 PLEAE ENSURE COMPLIANCE AND PROVIDEA AN APPLICABLE
 NOTE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-12 Cont ID  
Sent By shill Date 2018-01-12 Time 17:00 Rev Time 0.00
Received By shill Date 2017-11-30 Time 13:39 Sent To  
Notes
2018-01-12 17:00:43TO CC DESK
  
  
2017-12-01 13:39:27C03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 12:59 Rev Time 0.00
Received By gjohnson Date 2017-08-17 Time 13:28 Sent To  
Notes
2017-08-18 13:28:24C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-01-12 Cont ID  
Sent By shill Date 2018-01-12 Time 15:54 Rev Time 0.00
Received By shill Date 2018-01-12 Time 15:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 15:00 Rev Time 0.00
Received By shill Date 2017-09-22 Time 15:00 Sent To  
Notes
2017-09-22 15:00:31SEE BUILDING REVIEW
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-01-18 Cont ID  
Sent By ccole Date 2018-01-18 Time 13:05 Rev Time 0.00
Received By ccole Date 2018-01-18 Time 13:05 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-19 Cont ID  
Sent By ccole Date 2017-12-19 Time 16:46 Rev Time 0.00
Received By ccole Date 2017-12-19 Time 14:52 Sent To  
Notes
2017-12-19 17:01:562ND REVIEW FBC-2014 MECHANICAL , FBC-14 ENERGY
 CONSERVATION CODE
 PERMIT #17080883
 12/19/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE REQUIRED AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPERS FOR THE O/A DUCTS TO AHU 2 & 3 ARE NOT
 SHOWN. PLEASE NOTE THAT BOTH AIR HANDLERS MUST BE
 EQUIPPED WITH THE DAMPERS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION
  
 2) SHEETS A-1.0, M-1, M-2: SHOW ON THE PLANS THE A-3
 AREA AND ADJUST THE O/A CALCULATION FOR THAT SPACE IN
 ACCORDANCE WITH TABLE 403.3.
  
 3) ONE SET OF AC CALCULATIONS IS MISSING FROM THE
 RESUBMITTAL PACKAGE- PLEASE PROVIDE THE MISSING SET.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-22 Cont ID  
Sent By ccole Date 2017-09-22 Time 07:57 Rev Time 0.00
Received By ccole Date 2017-09-20 Time 16:09 Sent To  
Notes
2017-09-22 08:53:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080883
 9/22/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: INDICATE HOW OUTDOOR AIR IS BEING
 PROVIDED TO AHU-1 & 4- NO O/A DUCTS ARE SHOWN AT THESE
 LOCATIONS.
  
 2) M-1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 3) M-1: PLEASE ENLARGE THE SMOKE DETECTOR SYMBOLS IN
 THE AHU-2 & 3 CLOSET.
  
 4) M-1 & A2.2: THE AC CLOSET DOORS SHALL BE
 NON-COMBUSTIBLE IN COMPLIANCE WITH SECTION C403.2.7.2
 FBC-14 ENERGY CONSERVATION AND SECTION 602 FBC-14
 MECHANICAL. THE PLANS INDICATE WOOD DOORS.
  
 5) M-1: EXHAUST VENTILATION AT A RATE OF 0.25 CFMS PER
 SQ. FT IS REQUIRED FOR THE LOCKER ROOMS- TABLE 403.3.
  
 6) M-2: THE 150 MPH WIND SPEED SHOWN IN THE CU MOUNTING
 DETAIL IS NOT CORRECT FOR PUT REGION. PLEASE REFER TO
 SECTION 1609 FBC-BUILDING AND PROVIDE THE CORRECT WIND
 SPEED, AND CURRENT WIND DESIGN CRITERIA FOR
 INSTALLATION OF THE CONDENSERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-12 Cont ID  
Sent By gjohnson Date 2018-01-12 Time 14:14 Rev Time 0.00
Received By gjohnson Date 2018-01-12 Time 14:14 Sent To  
Notes
2018-01-12 14:15:362ND REVIEW: FBC 2014 5TH EDITION
  
 PROVISO
  
 1. THE WATER FOUNTAIN SHALL HAVE TWO SPOUTS ONE FOR A
 PERSON IN A WHEEL CHAIR AND ONE FOR A STANDING PERSON.
 PER FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 SHALL COMPLY BEFORE FINAL INSPECTION.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-11 Cont ID  
Sent By gjohnson Date 2018-01-10 Time 16:50 Rev Time 0.00
Received By gjohnson Date 2018-01-10 Time 16:50 Sent To  
Notes
2018-01-11 09:32:352ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER FOUNTAIN SHALL HAVE TWO SPOUTS ONE FOR A
 PERSON IN A WHEEL CHAIR AND ONE FOR A STANDING PERSON.
 PER FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-02 Cont ID  
Sent By gjohnson Date 2017-10-02 Time 11:30 Rev Time 0.00
Received By gjohnson Date 2017-09-29 Time 13:50 Sent To  
Notes
2017-10-02 12:58:421ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW CLEAR FLOOR SPACE FOR TOILET ,
 LAVATORY'S, SHOWER , WATER FOUNTAIN AND BREAK ROOM
 SINK. PER FBC ACC 602.2 ,604.3.1, 606.2, 608.2.1
  
 2. TRANSFER TYPE SHOWER COMPARTMENTS SHALL COMPLY WITH
 FBC ACC 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.
 TRANSFER TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES BY
 36 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE
 CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT. CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48
 INCHES LONG MINIMUM MEASURED FROM THE CONTROL WALL
 SHALL BE PROVIDED.
  
 3. IN TRANSFER TYPE SHOWER COMPARTMENTS, SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE SIDE WALL OPPOSITE THE
 SEAT 38 INCHES MINIMUM AND 48 INCHES-MAXIMUM ABOVE THE
 SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL
 15 INCHES) MAXIMUM FROM THE CENTERLINE OF THE SEAT
 TOWARD THE SHOWER OPENING. PER FBC ACC 608.5.1
  
 4. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE TOP
 OF THE SEAT SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL
 COMPLY WITH 610.3.1 OR 610.3.2.
  
 5. SHT. A2.3 DETAIL #4 CLEAR FLOOR SPACE AT TOILET THE
 DETAIL SHOWING 48" WIDE DO NOT COMPLY PLEASE REMOVE
 FROM PLAN. PER FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 6. SHT. A2.3 DETAIL #4 GRAB BARS AT WATER CLOSET (A)
 BACK WALL DOES NOT COMPLY IT SHALL COMPLY WITH FBC ACC
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
  
 7. GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR. FBC ACC 609.4
  
 8. THE CENTERLINE OF THE WATERCLOSET SHALL BE 16"-18"
 OFF SIDE WALL. PER FBC ACC 604.2
  
 9. SHT. A2.3 THE LAYOUT OF THE BREAKROOM PLAN DETAIL #5
 DOES NOT MATCH DETAIL #6 DETAIL #5 DOES NOT SHOW THE
 CABINET ON THE LEFT SIDE OF THE SINK THAT IS SHOWN ON
 DETAIL #6 PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 10. SHOW COMPLIANCE WITH FBC ACC 608.3.1 TRANSFER TYPE
 SHOWER COMPARTMENTS.
 IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE
 PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A
 POINT 18 INCHES FROM THE CONTROL WALL.
  
 11. LAVATORY FAUCETS SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 12. PLEASE SHOW TRAP PRIMERS ON ALL FLOOR DRAINS AND
 FLOOR SINK ON RISER DIAGRAM. PER WPB AMEND TO FBC
 107.2.1
  
 13. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC PL 708.3.4
  
 14. PROVIDE MANUFACTURE SPEC FOR TANKLESS WATER HEATER
 AND OIL SMART SUMP PUMP. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-09-22 Cont ID  
Sent By shill Date 2017-09-22 Time 14:59 Rev Time 0.00
Received By shill Date 2017-09-22 Time 14:59 Sent To  
Notes
2017-09-22 14:59:45A ROOF PRODUCT APPROVAL WAS PROVIDED (14-1030.02 GAF
 MODIFIED BITUMEN), ASSEMBLY SELECTED WITH A DP
 LIMITATION OF -52.5. RAS117 CALCULATIONS PREPARED BY A
 DESIGN PROFESSIONAL IS REQUIRED PRIOR TO ISSUANCE OF
 ROOF SUB PERMIT. THIS MAY BE SUBMITTED AT TIME OF ROOF
 PERMIT APPLICATION.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-09 Cont ID  
Sent By ajones Date 2018-01-09 Time 11:19 Rev Time 0.00
Received By ajones Date 2018-01-09 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By ajones Date 2017-09-15 Time 10:58 Rev Time 0.00
Received By ajones Date 2017-09-15 Time 10:58 Sent To  
Notes
2017-09-15 11:03:179/15/17- FAILED. PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
  
 1. IT APPEARS THAT THE NEW LANDING WILL IMPACT EXISTING
 LANDSCAPE AREA. PLEASE VERIFITY.
 2. DOES THE NEW STAIRS AND COLUMNS IMPACT THE EXISTING
 LANDSCAPING?
 3. THE VALUE OF THE RENOVATIONS EXCEEDS 50% OF THE
 VALUE OF THE BUILDING VALUE. WHAT ARE THE PLANS FOR
 ADDITIONAL LANDSCAPING?
  
 ANGELLA VANN
 561-822-1441
 [email protected]