Plan Review Details - Permit 17080857
Plan Review Stops For Permit 17080857
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By fstal Date 2017-08-22 Time 16:47 Rev Time  
Received By fstal Date   Time   Sent To  
Notes
2017-08-22 17:04:44PROVISO: PROVIDE SPECIFICATION/CUT SHEETS FOR TANKS,
 PIPING AND APPURTENANCES.
  
 6.3.5.1.2 AT LEAST 380 MM (15 IN.) CLEARANCE SHALL BE
 LEFT AROUND EACH TANK FOR THE PURPOSE OF INSPECTION AND
 REPAIR.
  
 6.3.5.2 EACH TANK ROOM SHALL BE PROVIDED WITH AN
 OPENING THAT IS PROTECTED BY A SELF-CLOSING
 1-HOUR-RATED FIRE DOOR IF IT OPENS INSIDE A BUILDING.
  
  
 NFPA 704 SIGNAGE REQUIRED.
  
 INSTALLATION SHALL COME INTO COMPLIANCE WITH NFPA 1,
 30, 37, 70.
  
 CONSIDER THE FOLLOWING NFPA CODES WHEN SUBMITTING PLANS
 FOR STANDBY POWER. NFPA 37 & 110.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-30 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-17 Time 12:45 Sent To  
Notes
2017-08-18 12:45:59ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-30 Cont ID  
Sent By ccole Date 2017-08-30 Time 13:17 Rev Time 0.00
Received By ccole Date 2017-08-30 Time 13:03 Sent To  
Notes
***NONE***