Plan Review Stops For Permit 17080857 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-08-22 |
|
|
Cont ID |
|
Sent By |
fstal |
Date |
2017-08-22 |
Time |
16:47 |
Rev Time |
|
Received By |
fstal |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2017-08-22 17:04:44 | PROVISO: PROVIDE SPECIFICATION/CUT SHEETS FOR TANKS, | | PIPING AND APPURTENANCES. | | | | 6.3.5.1.2 AT LEAST 380 MM (15 IN.) CLEARANCE SHALL BE | | LEFT AROUND EACH TANK FOR THE PURPOSE OF INSPECTION AND | | REPAIR. | | | | 6.3.5.2 EACH TANK ROOM SHALL BE PROVIDED WITH AN | | OPENING THAT IS PROTECTED BY A SELF-CLOSING | | 1-HOUR-RATED FIRE DOOR IF IT OPENS INSIDE A BUILDING. | | | | | | NFPA 704 SIGNAGE REQUIRED. | | | | INSTALLATION SHALL COME INTO COMPLIANCE WITH NFPA 1, | | 30, 37, 70. | | | | CONSIDER THE FOLLOWING NFPA CODES WHEN SUBMITTING PLANS | | FOR STANDBY POWER. NFPA 37 & 110. | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | WEST PALM BEACH FIRE PREVENTION BUREAU | | 500 N. DIXIE HWY | | WEST PALM BEACH, FLORIDA 33401 | | OFFICE: 561-840-4780 | | FAX: 561-840-4774 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-08-30 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-08-17 |
Time |
12:45 |
Sent To |
|
|
Notes |
2017-08-18 12:45:59 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2017-08-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-08-30 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-08-30 |
Time |
13:03 |
Sent To |
|
|
Notes |
|
|
|