Plan Review Details - Permit 17080798
Plan Review Stops For Permit 17080798
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2018-06-04 Cont ID  
Sent By shill Date 2018-06-04 Time 16:13 Rev Time 0.00
Received By shill Date 2018-06-04 Time 16:13 Sent To  
Notes
2018-06-04 16:27:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, PROVIDE DIMENSIONS ON THE PLAN. WIDTH,
 HEIGHT, LENGTH NOT CLEAR.
  
 2. FBC B 1609, WIND PRESSURES ARE TOO LOW FOR A ROOF,
 REVISE.
  
 3. THE WALL PANELS HAVE A PRODUCT APPROVAL FOR USE AS A
 WALL PANEL; APPROVAL DOES NOT INCLUDE USE AS A ROOF.
 PROVIDE AN ENGINEERING ANALYSIS FOR USE IN HORIZONTAL
 ORIENTATION.
  
 4. PROVIDE A PRODUCT APPROVAL FOR THE ROOF ASSEMBLY
 PROPOSED FOR THE ROOF COVERING, FBC B 1609.
  
 5. PROVIDE A ROOF FRAMING DETAIL, FBC B 1609. ROOF
 SLOPE IS REQUIRED; SHOW ROOF SLOPE ON THE PLAN. WATER
 CANNOT DISCHARGE TO THE ADJACENT PROPERTY.
  
 6. FBC B TABLE 503, REVISE PLAN TO SHOW COMPLIANCE WITH
 BUILDING HEIGHT AND AREA. SINCE THIS IS BUILT IN PLACE
 STORAGE ROOM RATHER THAN REMOVABLE EQUIPMENT, THIS ACTS
 AS AN EXTENSION (ADDITION) TO THE EXISTING BUILDING.
  
 7. FBC B TABLE 602, FIRE RESISTANCE RATING REQUIRED FOR
 THE WALL ON THE PROPERTY LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-05-21 Cont ID  
Sent By shill Date 2018-05-21 Time 17:28 Rev Time 0.00
Received By shill Date 2018-05-21 Time 17:28 Sent To  
Notes
2018-05-21 17:36:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 109, PROVIDE A CONTRACT FOR THIS JOB. VALUE TOO
 LOW.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-09-13 Cont ID  
Sent By jwitmer Date 2017-09-13 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2017-09-13 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By jwitmer Date 2017-08-22 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2017-08-22 Time 05:59 Sent To  
Notes
2017-08-22 06:29:442014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080798
 ADD: 425 25TH ST.
 CONT: A & S REFRIGERATION & AIR
 TEL: 561-793-9698
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUG. 22/ 2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE WIND DESIGN DATA AND ASSOCIATED
 PRESSURES. 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 2) PLEASE PROVIDE EITHER A FLORIDA STATE APPROVED
 MODULAR BUILDING (COOLER/ FREEZER) UNDER FLORIDA
 ADMINISTRATIVE CODE 61-41 MANUFACTURERED BUILDING
 PROGRAM OR ENGINEERED PLANS FOR THIS WIND SPEED ZONE.
  
 3) PROVIDE A SITE PLAN FOR LOCATION ON LOT. 107.2.1.3.
 ADDITIONAL INFORMATION REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-05 Cont ID  
Sent By cpuell Date 2018-06-05 Time 17:15 Rev Time 0.00
Received By cpuell Date 2018-06-04 Time 16:27 Sent To  
Notes
2018-06-04 16:28:24TO ZONING BOX
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 11:41 Rev Time 0.00
Received By hmoser Date 2017-09-05 Time 14:13 Sent To  
Notes
2017-09-06 14:13:59RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-22 Cont ID  
Sent By jwitmer Date 2017-08-22 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2017-08-16 Time 14:01 Sent To  
Notes
2017-08-17 14:01:43MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-09-13 Cont ID  
Sent By hmoser Date 2017-09-13 Time 11:41 Rev Time 0.00
Received By hmoser Date 2017-09-07 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By hmoser Date 2017-08-21 Time 11:35 Rev Time 0.00
Received By hmoser Date 2017-08-21 Time 09:59 Sent To B
Notes
2017-08-21 11:35:32PLAN DENIED
 PROVIDE WIND LOAD CALCULATIONS FOR
 WALK IN COOLER BOX.
 PER SECTION 107.3.4 FBC 2014
 FLORIDA STATUTES 9B # 14
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-05 Cont ID  
Sent By mcruz Date 2018-06-05 Time 16:41 Rev Time 0.00
Received By mcruz Date 2018-06-05 Time 16:37 Sent To PC
Notes
2018-06-05 16:39:56ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO SEC. 94-211(B)(3), COOLER SHALL BE
 PLACED AT LEAST 15 FEET FROM REAR PROPERTY LINE.
 2) EXTERIOR FINISH MATERIAL SHALL BE LIMITED TO STONE,
 BRICK, STUCCO, EXPOSED CONCRETE, TERRA COTTA TILE,
 CERAMIC TILE, ANY STONE CLADDING MATERIAL-MARBLE,
 LIMESTONE, GRANITE, PRECAST CONCRETE, CLAPBOARD SIDING,
 AND WOOD SHINGLES. WALLS SHALL COMBINE NO MORE THAN TWO
 MATERIALS AND SHALL CHANGE MATERIAL ALONG A HORIZONTAL
 LINE, WITH THE VISUALLY HEAVIER MATERIAL BELOW THE
 LIGHTER MATERIAL.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ