Plan Review Details - Permit 17080793
Plan Review Stops For Permit 17080793
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-10-20 Cont ID  
Sent By jwitmer Date 2017-10-20 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2017-10-20 Time 11:58 Sent To  
Notes
2017-10-20 15:06:352014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080793
 ADD: 329 CLEMATIS ST. SUITE: B
 CONT: DURHAM BROTHERS
 TEL: 561-662-0736
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT. 20/ 2017
 ACTION: BUILDING PROVIO
  
 1) PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 2) PROVISO/ DEFERRED SUBMITTAL: IDENTIFY GLAZING/
 MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 3) PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By jwitmer Date 2017-09-27 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2017-09-27 Time 06:15 Sent To  
Notes
2017-09-27 08:03:132014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080793
 ADD: 329 CLEMATIS ST. SUITE: B
 CONT: DURHAM BROTHERS
 TEL: 561-662-0736
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. SEPT. 27/ 2017
 ACTION: DENIED
  
 1) COMPLIED. SITE THE OLD MYERS LUGGAGE STORE. A CHANGE
 OF OCCUPANCY TO A A2
  
 1A)SEMI-COMPLIED. SHEET A-1 THE EAST 6 INCH FRAME WALL
 WILL NEED TO PROVIDE EITHER A U. L. LISTING, OR GYPSUM
 ASSOCIATION LISTING, WITH TYPE OF FRAMING MEMBER,
 SPACING OF FRAMING MEMBER, TYPE OF DRYWALL, THICKNESS
 AND LAYERS TO COMPLETE THE WALL ASSEMBLY FOR A 2 HOUR
 FIRE RATING. . FBC-B 707.3.9 SEPARATED OCCUPANCIES &
 707.5 CONTINUITY.1ST ROUND OF COMMENTS. THE COVERSHEET
 DOES NOT PROVIDE THE REQUIRED OCCUPANCY SEPARATION
 REQUIREMENT FOUND IN TABLE 508.4 OF THE 2014 FBC-B.
 SHEET A-1 DOES INDICATE EXISTING 2 HR. OCCUPANCY
 SEPARATION BUT DOES NOT DECLARE THE TYPE OF WALL
 ASSEMBLY TO MAKE UP THE EXISTING 2 HR. FIRE BARRIER.
 FBC-B 707.3.9 SEPARATED OCCUPANCIES & 707.5 CONTINUITY.
  
 1B) COMPLETED.
  
 1C) 2ND REQUEST. SHEET A-1 RESTATES THE CODE SECTION
 MANY TIMES, DOES NOT SHOW CODE COMPLIANCE. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 1ST ROUND COMMENT. PLEASE PROVIDE COMPLIANCE WITH THE
 2014 FBC-EXISTING BUILDING CODE SECTION 1012.1.2 FIRE
 PROTECTION AND INTERIOR FINISH. THE PROVISIONS OF
 SECTIONS 1012.2 AND 1012.3 FOR FIRE PROTECTION AND
 INTERIOR FINISH, RESPECTIVELY, SHALL APPLY TO ALL
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 1D) 2ND REQUEST. PLEASE NOTE THE SEATING AGAINST THE
 EAST WALL HAS BEEN ELIMINATED, NOT SHOWING ANY DENSITY
 WILL TAKE THE MOST RESTRICTIVE AT 5 SQ. FT./ OCCUPANT.
 PLEASE REVIEW UNDER CHAPTER 10 OF THE EXISTING BUILDING
 CODE THE REQUIREMENT FOR FIRE SPRINKLERS. 2014 EXT.
 BLDG. CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 EXST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2014 FBC-B SECTION F] 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR
 MORE.
  
 2) SHEET A-1:
 2A-B) COMPLIED.
  
 2C) 2ND REQUEST. SHEET A1 SHOWS 4 ACCESSIBLE SEATS. THE
 LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE :
 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 80 SEATS X 0.05= 4.0 OR 4 SEATS,3 SHOWN ON
 PLANS.
  
 2D) 2ND REQUEST, NO DROPPED PORTION OF BAR FOR
 HANDICAPPED SEATING AT BAR. FBC-ACCESSIBILITY CODE
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES. THE PLANS DO NOT SHOW
 COMPLIANCE WITH: 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2E) COMPLIED.
  
 3) COMPLIED.
  
 4) 2ND REQUEST. NOTE THE ARCHITECT OF RECORD IS SIGNING
 AND SEALING COMPUTER SOFTWARE PROGRAM. PLEASE BE AWARE
 WITHIN THE SOFTWARE GROGRAM YOU HAVE TAKEN CREDIT FOR 3
 FOOT PARAPETS ON ALL SIDES OF THE ROOF. ON THE NORTH
 AND EAST SIDES OF THE BUILDING THERE IS NO 3 FOOT
 PARAPET, PLEASE CORRECT THE INPUT DATA TO PROVIDE
 PRESSURES FOR ROOF ZONE 3. GOOGLE EARTH AND A
 COUNTYWIDE GIS PROGRAM ALLOWS FOR AERIAL VIEWS OF
 BUILDINGS. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE.
  
 THE MECA SOFTWARE PROGRAM SUBMITTED IS VERY LIGHT, HARD
 TO READ AND WILL NOT MEET THE QUALITY OF PLANS
 REQUIRED, FOR SCANNING INTO RECORD RETENTION. 107.2.1.4
 QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
 THE 3RD ISSUE WITH THE ARCHITECT SIGNING AND SEALING
 THE WIND DESIGN REPORT IS ONLY THE FRONT PAGE OF THE
 REPORT IS SEALED, NOT ALL PAGES. FL ADMIN CODE
 61G16.003(1) ARCHITECTS.PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
  
 1ST ROUND OF COMMENTS. SHEET A-3. PLEASE PROVIDE
 COMPLIANCE WITH FBC-B WIND DESIGN. THE PLANS REFERENCE
 THE RESIDENTIAL CODE, R703.13, R616.4, TABLE R301.2(2)
 & R301.2(2).
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5-6) COMPLIED.
  
 7) PROVISO/ DEFERRED SUBMITTAL: 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) PROVISO/ DEFERRED SUBMITTAL: IDENTIFY GLAZING/
 MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2014 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 9) PROVISO/ DEFERRED SUBMITTAL: FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 10) COMPLIED. THRESHOLDS ACCESS. CODE 404.2.5
  
 11) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-19 Cont ID  
Sent By   Date 2017-08-19 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2017-08-19 Time 10:31 Sent To  
Notes
2017-08-21 10:20:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080793
 ADD: 329 CLEMATIS ST. SUITE: B
 CONT: DURHAM BROTHERS
 TEL: 561-662-0736
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 21/ 2017
 ACTION: DENIED
  
 1) SITE THE OLD MYERS LUGGAGE STORE. THE COVER SHEET
 INDICATES THIS TENANT SPACE WAS A MERCANTILE AND IS
 PROPOSED TO BE AN A-2 OCCUPANCY. A CHANGE OF OCCUPANCY
 IS MORE STRINGENT THAN A LEVEL II ALTERATION AND MUST
 MEET ALL OF THE REQUIREMENTS FOUND IN THE 2014 FBC-
 EXISTING BUILDING CODE. PLEASE REFER TO CHAPTER 10,
 CHANGE OF OCCUPANCY. 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1A) THE COVERSHEET DOES NOT PROVIDE THE REQUIRED
 OCCUPANCY SEPARATION REQUIREMENT FOUND IN TABLE 508.4
 OF THE 2014 FBC-B. SHEET A-1 DOES INDICATE EXISTING 2
 HR. OCCUPANCY SEPARATION BUT DOES NOT DECLARE THE TYPE
 OF WALL ASSEMBLY TO MAKE UP THE EXISTING 2 HR. FIRE
 BARRIER. FBC-B 707.3.9 SEPARATED OCCUPANCIES & 707.5
 CONTINUITY.
  
 1B) SINCE THE OCCUPANCY SEPARATION WALLS WILL HAVE
 ADDITIONAL ELECTRICAL AND OR PLUMBING PLEASE PROVIDE
 FIRE RATED WALL PENETRATION DETAILS PER FBC-B 707.7.
 PENETRATIONS. PENETRATIONS OF FIRE BARRIERS SHALL
 COMPLY WITH SECTION 714 OF THE FBC-B.
  
 1C) PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-EXISTING BUILDING CODE SECTION 1012.1.2 FIRE
 PROTECTION AND INTERIOR FINISH. THE PROVISIONS OF
 SECTIONS 1012.2 AND 1012.3 FOR FIRE PROTECTION AND
 INTERIOR FINISH, RESPECTIVELY, SHALL APPLY TO ALL
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 1D) PLEASE REVIEW UNDER CHAPTER 10 OF THE EXISTING
 BUILDING CODE THE REQUIREMENT FOR FIRE SPRINKLERS. 2014
 EXT. BLDG. CODE 1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
 EXST. BLDG. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
 2014 FBC-B SECTION F] 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR
 MORE.
  
 2) SHEET A-1:
 2A) PLEASE REVIEW THE DOOR SWING FOR THE DOOR BETWEEN
 THE BACK SEATING ROOM AND THE RESTROOM VESTIBULE. THIS
 DOOR SWINGS AGAINST THE MEANS OF EGRESS WITH AN
 OCCUPANT LOAD GREATER THAN 50 OCCUPANTS. PLEASE REVIEW
 SECTION 1008.1.2 OF THE 2014 FBC-B. 1008.1.2 DOOR
 SWING. DOORS SHALL SWING IN THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING A ROOM OR AREA CONTAINING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS.
  
 2B) THE REAR OF THE TENANT SPACE IS LABELED A OFFICE
 AREA BUT LOOKS MORE LIKE A STORAGE AREA WITH AN EXIT
 ACCESS GOING THROUGH. NOTE THERE IS A SIGNAGE ON PLANS
 NO STORAGE, IF TO BE CONSIDERED AN OFFICE AREA SHOW
 FURNITURE AND IT NOT BLOCKING THE MEANS OF EGRESS.
 2014 FBC-B 014.2 EGRESS THROUGH INTERVENING SPACES.
 (4). EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
  
 2C) SHEET A1 SHOWS 4 ACCESSIBLE SEATS. THE LIFE SAFETY
 SHEET DOES NOT SHOW COMPLIANCE WITH THE :
 2014 FBC-ACCESSIBILITY CODE; 226.1 WHERE DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. 98 SEATS X 0.05= 4.9 OR 5 SEATS, 4SHOWN ON
 PLANS.
  
 2D) FBC-ACCESSIBILITY CODE 226.2 DISPERSION. DINING
 SURFACES AND WORK SURFACES REQUIRED TO COMPLY WITH 902
 SHALL BE DISPERSED THROUGHOUT THE SPACE OR FACILITY
 CONTAINING DINING SURFACES AND WORK SURFACES. THE PLANS
 DO NOT SHOW COMPLIANCE WITH: 902.1 .DINING SURFACES AND
 WORK SURFACES SHALL COMPLY WITH 902.2 AND 902.3.
 ADVISORY 902.1 GENERAL. DINING SURFACES INCLUDE, BUT
 ARE NOT LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND
 BOOTHS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2E) SHEET A-2 SHOWS THE ACCESS AISLE WITH A HASH LINE
 AT 36 INCHES WIDE. PLEASE REVIEW UNDER AN ASSEMBLY
 OCCUPANCY WITH AN OCCUPANT LOAD OF 102 FBC-B 1028.9
 .1.4. FORTY-TWO INCHES FOR LEVEL OR RAMPED AISLE HAVING
 SEATING ON BOTH SIDES.
  
 3) SHEET A2 SHOWS THE DEMOLITION AND REMOVAL OF THE
 FRONT DISPLAY WINDOWS AND STOREFRONT. SHEET A3 SHOWS
 THE NEW LOCATION OF THE STOREFRONT. PLEASE PROVIDE THE
 LOCATION OF THE FRONT PROPERTY LINE. THE FRONT DOOR IS
 NOT TO SWING BEYOND THE PROPERTY LINE. 2014 FBC-B
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 4)SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH FBC-B WIND
 DESIGN. THE PLANS REFERENCE THE RESIDENTIAL CODE,
 R703.13, R616.4, TABLE R301.2(2) & R301.2(2).
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5) SHEET A-3. SHOWS A DETAIL LISTED AS A/3. PLEASE
 REVIEW THIS DETAIL , THE STUD IS DETAILED AS METAL STUD
 20 GAUGE W/ TOP AND BOTTOM STEEL PLATES, STUDS AT 16
 INCHES O. C. THE LEFT SIDE OF THE DETAIL LIST 1X2 INCH
 FURRING AT 24 INCHES ON CENTER, THE RIGHT SIDE OF THE
 DETAIL INDICATES THE INSTALLATION OF 5/8 INCH PLYWOOD
 SHEATHING NAILED WITH 8D RING SHANK NAILS @ 6 INCHES ON
 CENTER, NAILS USE ON METAL STUDS?
 ON THE SAME RIGHT SIDE THE FINISH IS LABELED AS 2 COAT
 STUCCO AND ALSO 5/8 INCH TYPE X GBD. DISCREPANCIES IN
 MATERIALS, SPACING, TO MANY ERRORS TO COMMENT ON.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) SHEET A-3 WALL PRESSURES ARE STATED TO BE ALLOWABLE
 (VASD):
 6A) THE POSITIVE PRESSURES APPEAR TO BE VULT AND NOTE,
 THE SQUARE FOOT AREA IS NOT GIVEN, AND THE SAME
 POSITIVE 58.3 IN BOTH WALL ZONES 4 & 5!!! 2014 FBC-B
 1603.1.4 WIND DESIGN DATA.
  
 6B) THE NEGATIVE PRESSURES APPEAR TO BE VULT AND THE
 SQUARE FEET OF AREA FOR THE PRESSURES IS NOT GIVEN.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 10) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-10-26 Cont ID  
Sent By jleahy Date 2017-10-26 Time 12:08 Rev Time 0.00
Received By jleahy Date 2017-10-26 Time 12:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-28 Cont ID  
Sent By jleahy Date 2017-09-28 Time 17:46 Rev Time 0.00
Received By jleahy Date 2017-09-28 Time 17:36 Sent To  
Notes
2017-09-28 17:52:21FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2
 SEE FBC CODE SECTION 405.2.2.FOR THE ADDITIONAL
 REQUIREMENT FOR OCUUPANCY SENSORS IN ADDITION TO MANUAL
 CONTROL IN ALL AREAS.
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-23 Cont ID  
Sent By jpearson Date 2017-08-23 Time 14:35 Rev Time 0.00
Received By jpearson Date 2017-08-23 Time 14:35 Sent To  
Notes
2017-08-23 14:08:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-1 HAS SEVERAL NOTES (THE NOTES THAT ARE NOT
 NUMBERED) THAT APPLY TO RESIDENTIAL INSTALLATIONS.
 EXAMPLE: 75% OF LAMPS SHALL BE HIGH EFFICIENCY,
 RECEPTACLES TO BE TAMPER RESISTANT, AFCI PROTECTION,
 ETC. REMOVE ALL NOTES NOT APPLICABLE TO PROJECT. FBC
 107.2.1
 2. PROVIDE SHOW WINDOW OUTLET PER CODE. NEC 210.62
 3. PROVIDE AUTOMATIC CONTROL FOR SIGN AND SHOW WINDOW
 LIGHTING. FBC CE 405.2.4
 4. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1
 5. PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
 6. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED
 IN THE FBC ENERGY CODE. NO AUTOMATIC CONTROL IS
 CURRENTLY SHOWN. FBC CE 405.2.2, 405.2.2.2
 7. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR SYSTEMS TO INCLUDE BUT NOT BE LIMITED TO
 FIRE ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS,
 WALK IN COOLER, ETC. FBC 105.1
 8. CIRCUIT 16,18 IS DESIGNATED IN PANEL SCHEDULE FOR
 WALK IN COOLER, BUT CIRCUIT 18 IS SHOWN FEEDING SEVERAL
 RECEPTACLES. CORRECT DISCREPANCY. FBC 107.2.1, NEC
 215.5, 408.4
 9. PROVIDE REQUIRED GFCI SERVICE OUTLET FOR A/C
 EQUIPMENT. NEC 210.63
 10. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 11. PANEL SCHEDULE SHOWS AHU-1, AHU-2, CU-1, AND CU-2.
 ELECTRICAL PLAN SHOWS RTU-1 ONLY. PROVIDE CORRECTION,
 UPDATE PANEL LOAD IF NECESSARY. FBC 107.2.1; NEC 220,
 408.4
 12. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 13. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9
 14. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
 15. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 USING METHOD FOR COMMERCIAL SERVICE. CURRENT LOAD
 STATED FOR RECEPTACLES IS NOT ACCURATE. NEC 220; FBC
 107.2.1
 16. NOTE UNDER PANEL SCHEDULE STATES THAT ALL 15 AN 20
 AMP BREAKERS SHOULD BE AFCI TYPE. CLARIFY AND/OR
 CORRECT. FBC 107.2.1; NEC 210.12
 17. NOTE ON SHEET E-2 STATES THAT "SMOKE DETECTORS TO
 BE HARD WIRED WITH BATTERY BACK UP". NO SMOKE DETECTORS
 SHOWN ON PLAN. A SEPARATE PERMIT IS REQUIRED FOR FIRE
 ALARM INSTALLATIONS. PLEASE CLARIFY AND/OR CORRECT. FBC
 105.1, 107.2.1
 18. SCOPE OF WORK ON C-1 STATES THAT THERE WILL BE 4
 NEW SERVICES WITH 4 NEW PANELS. THIS WORK IS NOT
 REFLECTED ON PLAN. PLEASE CLARIFY AND/OR CORRECT. FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2018-01-16 Cont ID  
Sent By wjolin Date 2018-01-16 Time 09:52 Rev Time 0.00
Received By wjolin Date 2018-01-16 Time 09:52 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2017-11-17 Cont ID  
Sent By wjolin Date 2017-11-17 Time 10:49 Rev Time 0.00
Received By wjolin Date 2017-11-17 Time 10:49 Sent To I
Notes
2017-11-17 10:49:41329B CLEMATIS STREET
 PERMIT #17080793
 REVIEW COMMENTS - FIRE DEPARTMENT
 **NOTE: CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY**
  
  
 RESPONSE COMMENT - 4TH REQUEST: THE REDUCTION IN
 OCCUPANT LOAD FROM +100 TO 80 OCCUPANTS IS NOT
 JUSTIFIED. THE OPEN FLOOR AREAS HAVE NOT BEEN INCLUDED
 IN THE OCCUPANT LOAD CALCULATION. PER FFPC
 SECTION12.1.7 OCCUPANT LOAD.
 12.1.7.1 GENERAL. THE OCCUPANT LOAD, IN NUMBER OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED, SHALL BE DETERMINED ON THE BASIS OF THE
 OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
  
 ORIGINAL REVIEW COMMENTS:
 CALCULATED OCCUPANT LOAD DOES NOT FACTOR ANY STANDING
 ROOM OR CLOSELY SPACED BAR SEATING.
  
 BAR/ASSEMBLY SPACE OCCPUANT LOAD EXCEEDS 100 PERSONS
 AND NO FIRE SPRINKLER PROTECTION PROVIDED PER FBC
 903.2.1.2.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NO DOOR/HARDWARD SCHEDULE PROVIDED. FOR ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2017-10-25 Cont ID  
Sent By wjolin Date 2017-10-25 Time 09:31 Rev Time 0.00
Received By wjolin Date 2017-10-25 Time 09:20 Sent To E
Notes
2017-10-25 09:32:26329B CLEMATIS STREET
 PERMIT #17080793
 REVIEW COMMENTS - FIRE DEPARTMENT
 **NOTE: CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY**
  
  
 RESPONSE COMMENT - 3RD REQUEST: THE REDUCTION IN
 OCCUPANT LOAD FROM +100 TO 80 OCCUPANTS IS NOT
 JUSTIFIED. THE OPEN FLOOR AREAS HAVE NOT BEEN INCLUDED
 IN THE OCCUPANT LOAD CALCULATION. PER FFPC
 SECTION12.1.7 OCCUPANT LOAD.
 12.1.7.1 GENERAL. THE OCCUPANT LOAD, IN NUMBER OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED, SHALL BE DETERMINED ON THE BASIS OF THE
 OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
  
 ORIGINAL REVIEW COMMENTS:
 CALCULATED OCCUPANT LOAD DOES NOT FACTOR ANY STANDING
 ROOM OR CLOSELY SPACED BAR SEATING.
  
 BAR/ASSEMBLY SPACE OCCPUANT LOAD EXCEEDS 100 PERSONS
 AND NO FIRE SPRINKLER PROTECTION PROVIDED PER FBC
 903.2.1.2.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NO DOOR/HARDWARD SCHEDULE PROVIDED. FOR ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-09-20 Cont ID  
Sent By wjolin Date 2017-09-20 Time 10:20 Rev Time 0.00
Received By wjolin Date 2017-09-20 Time 10:07 Sent To  
Notes
2017-09-20 10:20:42329B CLEMATIS STREET
 PERMIT #17080793
 REVIEW COMMENTS - FIRE DEPARTMENT
 **NOTE: CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY**
  
  
 RESPONSE COMMENT: THE REDUCTION IN OCCUPANT LOAD FROM
 +100 TO 80 OCCUPANTS IS NOT JUSTIFIED. THE OPEN FLOOR
 AREAS HAVE NOT BEEN INCLUDED IN THE OCCUPANT LOAD
 CALCULATION. PER FFPC SECTION12.1.7 OCCUPANT LOAD.
 12.1.7.1 GENERAL. THE OCCUPANT LOAD, IN NUMBER OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED, SHALL BE DETERMINED ON THE BASIS OF THE
 OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE
 DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF THE
 SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
  
 ORIGINAL REVIEW COMMENTS:
 CALCULATED OCCUPANT LOAD DOES NOT FACTOR ANY STANDING
 ROOM OR CLOSELY SPACED BAR SEATING.
  
 BAR/ASSEMBLY SPACE OCCPUANT LOAD EXCEEDS 100 PERSONS
 AND NO FIRE SPRINKLER PROTECTION PROVIDED PER FBC
 903.2.1.2.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NO DOOR/HARDWARD SCHEDULE PROVIDED. FOR ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-18 Cont ID  
Sent By wjolin Date 2017-08-18 Time 11:23 Rev Time 0.00
Received By wjolin Date 2017-08-18 Time 10:17 Sent To  
Notes
2017-08-18 11:23:24329B CLEMATIS STREET
 PERMIT #17080793
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **NOTE: CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY**
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 CALCULATED OCCUPANT LOAD DOES NOT FACTOR ANY STANDING
 ROOM OR CLOSELY SPACED BAR SEATING.
  
 BAR/ASSEMBLY SPACE OCCPUANT LOAD EXCEEDS 100 PERSONS
 AND NO FIRE SPRINKLER PROTECTION PROVIDED PER FBC
 903.2.1.2.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 NO DOOR/HARDWARD SCHEDULE PROVIDED. FOR ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS (50 PERSONS PER THE FLORIDA BUILDING CODE),
 PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO RELEASE
 THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE PERMITTED
 THAT WOULD NOT BE RELEASED BY THE PANIC HARDWARE. AS A
 SUBSTITUTE FOR PANIC HARDWARE, THE MAIN ENTRANCE IS
 PERMITTED TO HAVE AN INTERIOR KEYED DOOR LOCK (AND NO
 LATCH) WITH A READILY VISIBLE SIGN STATING THIS DOOR TO
 REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN
 LETTERS SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK
 TO BE EQUIPPED WITH AN "OPEN/LOCKED" INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN
 STYLE LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A
 KEYED LOCK.
  
 THE BACK SEATING AREA DOOR LEADING TO THE REAR
 (SECONDARY) EXIT HAS A SWING THAT IS AGAINST THE FLOW
 OF EGRESS FOR MORE THAN 50 PERSONS.
  
 INSUFFICIENT EMERGENCY LIGHTING PROVIDED IN MAIN
 ASSEMBLY AREA. EMERGENCY ILLUMINATION SHALL BE PROVIDED
 FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF
 NORMAL LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2018-01-25 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-24 Time 14:05 Sent To  
Notes
2018-01-25 14:06:06RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-01-17 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-09 Time 14:48 Sent To  
Notes
2018-01-10 14:48:41RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-11-20 Cont ID  
Sent By lmarchan Date 2017-11-20 Time 10:30 Rev Time 0.00
Received By lmarchan Date 2017-11-01 Time 15:00 Sent To  
Notes
2017-11-02 15:00:45RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-26 Cont ID  
Sent By jleahy Date 2017-10-26 Time 12:08 Rev Time 0.00
Received By jleahy Date 2017-10-13 Time 14:41 Sent To  
Notes
2017-10-16 14:44:39B02

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 14:22 Rev Time 0.00
Received By gjohnson Date 2017-09-18 Time 13:00 Sent To  
Notes
2017-09-19 13:00:32B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2017-08-30 Time   Rev Time 0.00
Received By lmarchan Date 2017-08-16 Time 16:29 Sent To  
Notes
2017-08-17 16:29:27B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2018-01-25 Time   Rev Time 0.00
Received By jwitmer Date 2018-01-25 Time 17:20 Sent To  
Notes
2018-01-25 17:25:18PALM BEACH COUNTY IMPACT FEES
 RECEIPT NUMBER 2018-0125-161
 TRACKING NUMBER MU-2018-002528-0000
 FEES: $274.37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-10-20 Cont ID  
Sent By jwitmer Date 2017-10-20 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2017-10-20 Time 15:06 Sent To  
Notes
2017-10-20 15:07:30BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2017-09-27 Cont ID  
Sent By jwitmer Date 2017-09-27 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2017-09-27 Time 06:15 Sent To  
Notes
2017-09-27 08:02:29BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By jwitmer Date 2017-08-21 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2017-08-21 Time 10:18 Sent To  
Notes
2017-08-21 10:18:56BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-01-17 Cont ID  
Sent By ccole Date 2018-01-17 Time 15:54 Rev Time 0.00
Received By ccole Date 2018-01-17 Time 15:54 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-11-09 Cont ID  
Sent By ccole Date 2017-11-09 Time 16:32 Rev Time 0.00
Received By ccole Date 2017-11-09 Time 16:32 Sent To  
Notes
2017-11-09 16:43:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080793
 11/9/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) RESIDENTIAL MANUAL J CALCULATIONS CANNOT BE
 SUBMITTED FOR COMMERCIAL AC SYSTEMS. PLEASE REFER TO
 SECTION C403.2.1 CALCULATION OF HEATING AND COOLING
 LOADS:
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT.
  
 2) PLEASE NOTE THAT THE MANUAL J CALCULATION
 INCORRECTLY INDICATES THE "FRONT DOOR FACING NORTH"
 HOWEVER THE FRONT DOOR IS FACING SOUTH.
  
 3) THE COMCHECK COMPLIANCE CERTIFICATE INDICATES 16
 SEER SYSTEMS, HOWEVER 14 SEER SYSTEMS ARE SHOWN IN THE
 AC SCHEDULE- PLEASE CORRECT.
  
 4) THE REQUESTED MIAMI-DADE NOA FOR THE ROOF STAND WAS
 NOT SUBMITTED. PLEASE NOTE THAT THE PREVIOUSLY
 SUBMITTED NOA DID NOT HAVE THE RIGHT INSTALLATION
 DRAWINGS ATTACHED WITH THE COVER SHEETS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-10-23 Cont ID  
Sent By ccole Date 2017-10-23 Time 17:10 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 16:11 Sent To  
Notes
2017-10-23 17:30:463RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17080793
 10/23/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESUBMITTED PLAN APPEARS TO SHOW NEW ROUND
 OUTSIDE AIR DUCTS GOING THROUGH THE ROOF HOWEVER THEY
 ARE LABELED AS R/A (RETURN AIR) DUCTS AND THE SIZES OF
 THESE DUCTS ARE NOT INDICATED- PLEASE CORRECT.
  
 2) THE RESUBMITTED PLAN IS NOW INDICATING 765 CFMS OF
 O/A FOR THE 5-TON SYSTEM WHICH IS 38% OF THE TOTAL 2000
 CFM SUPPLY CFMS. BY INDUSTRY STANDARDS THIS WOULD BE
 CONSIDERED A LARGE AMOUNT OF O/A TO BE CONSTANTLY
 COOLED BY A 5-TON SYSTEM. PLEASE NOTE THAT A TEST AND
 BALANCE REPORT MUST BE SUBMITTED TO VERIFY THE O/A
 AMOUNT AND THE AIR DISTRIBUTION AS DESIGNED- SEE NOTE
 #13 ON SHEET M-1.
  
 3) SHEETS M-1 & M-2: THE ARCHITECT IS INDICATING THAT
 THE ROOF TOP CONDENSER "SHALL BE INSTALLED TO RESIST
 WIND PRESSURES AT VELOCITIES INDICATED ON FBCM 301.15".
 PLEASE NOTE THAT THE MECHANICAL CODE SECTION 301.15
 REFERENCES THE FLORIDA BUILDING CODE FOR WIND DESIGN,
 AND DOES NOT PROVIDE ANY DESIGN PRESSURES- PLEASE
 CORRECT AND PROVIDE ACCURATE WIND LOAD DESIGN CRITERIA
 . AS PREVIOUSLY REQUESTED, SUBMIT THE MIAMI-DADE NOA,
 OR THE FLORIDA PRODUCT APPROVAL FOR THE AC STAND WITH
 APPROVAL STAMP BY THE ARCHITECT OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-09-28 Cont ID  
Sent By ccole Date 2017-09-28 Time 14:00 Rev Time 0.00
Received By ccole Date 2017-09-28 Time 12:21 Sent To  
Notes
2017-09-28 14:12:251ST REVIEW FBC-2014 MECHANICAL, EXISTING, ENERGY
 CONSERVATION CODES
 PERMIT #17080793
 9/28/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESCHECK COMPLIANCE SUBMITTAL IS INDICATING THE
 PROJECT TYPE TO BE A "MULTI-FAMILY", HOWEVER THE
 PROPOSED PROJECT IS CHANGE OF OCCUPANCY FROM MERCANTILE
 TO ASSEMBLY AND MUST BE IN COMPLIANCE WITH THE
 COMMERCIAL CODES. PLEASE SEE SECTION C101.5.1 FBC-14
 ENERGY CONSERVATION AND PROVIDE EITHER A FLORIDA
 ENERGYGAUGE COMPLIANCE SUBMITTAL OR A COMCHECK
 COMPLIANCE CERTIFICATE.
  
 2) M-2: THE 5-TON AC SYSTEM WHICH IS PRESUMED TO
 PRODUCE APPROXIMATE 2000 CFMS WOULD BE UNDERSIZED TO
 CONDITION 1040 CFMS OF OUTSIDE AIR ACCORDING TO
 ASHRAE/ACCA STANDARDS. THE TYPICAL PERCENTAGE OF
 OUTSIDE AIR TO SUPPLY AIR WOULD RANGE AROUND 17-20%. IN
 ADDITION THE 14X12 DUCT THAT IS BOTH SUPPLYING THE O/A
 AND RETURNING 1370 CFMS OF AIR FROM THE SPACE IS
 UNDERSIZED FOR THE TOTAL 2410 CFMS OF AIR- PLEASE
 CORRECT.
  
 3) M-2, AC EQUIPMENT SCHEDULE: PROVIDE THE KW
 CAPACITIES OF THE AIR HANDLER HEAT STRIPS AND THE TOTAL
 SUPPLY CFMS OF EACH SYSTEM.
  
 4) M-2: THE OUTSIDE AIR INLETS APPEAR TO BE WITHIN THE
 REQUIRED 10' CLEARANCE SPACE TO THE ADJACENT OPEN
 PARKING AREA- SEE SECTION 401.4 AND CORRECT.
  
 5) M-1: THE REQUESTED WIND LOAD ENGINEERING AND NOA FOR
 THE AC STANDS WAS NOT PROVIDED. PROVIDE ON THE PLAN THE
 WIND DESIGN CRITERIA USED TO DETERMNINE THE DESIGN
 PRESSURES AND TIE DOWN REQUIREMENTS- SEESECTION 301.15
 FBC-14 MECH. & 1609 FBC-14 BUILDING.
  
 6) PROVIDE THE MIAMI-DADE NOAS OR FLORIDA PRODUCT
 APPROVALS FOR THE ROOF STANDS AND LOUVERS- RULE 9N-3
 FAC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By ccole Date 2017-08-30 Time 09:36 Rev Time 0.00
Received By ccole Date 2017-08-30 Time 07:36 Sent To  
Notes
2017-08-30 10:23:261ST REVIEW FBC-2014 MECHANICAL , EXISTING BUILDING,
 ENERGY CONSERVATION.
 PERMIT #17080793
 8/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION
 AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR
 THE CHANGE OF OCCUPANCY FROM M TO A-2. SEE SECTION
 C401.2 FOR COMPLIANCE PATH INFORMATION.
  
 2) SUBMIT COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT.
 PLEASE NOTE THE ILLEGIBLE CALCULATION COPIED AND PASTED
 ON SHEET M-2 APPEARS TO HAVE BEEN PERFORMED USING
 MANUAL J FOR RESIDENTIAL SYSTEMS- NOT ACCEPTABLE- SEE
 ABOVE.
  
 3) THE M-1 PLAN AND THE EQUIPMENT SCHEDULE ARE
 INDICATING THE NEW AC SYSTEMS TO BE SPLIT-SYSTEMS,
 HOWEVER THEY ARE LABELED AS RTU'S ON THE LAYOUT PLAN-
 PLEASE CORRECT.
  
 4) M-2: PLEASE INDICATE THE SUPPLY AND RETURN CFMS AT
 EACH DIFFUSER AND GRILL SHOWN ON THE LAYOUT PLAN.
  
 5) M-2: SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE SHOW THE LOCATIONS ON THE PLAN. PLEASE NOTE THAT
 AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S
 SPECIFICATIONS INDICATE SYSTEMS ARE NOT CAPABLE OF
 PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 6) M-2: INDICATE HOW OUTDOOR AIR IS BEING PROVIDED TO
 THE NEW AIR HANDLERS, AND COMPLY WITH SECTION
 C403.2.4.4. FOR REQUIRED DAMPER.
  
 7) M-2: PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SMACNA STANDARDS.
  
 8) M-2: PROVIDE CONDENSATE DISPOSAL PLANS AND DETAILS
 PER SECTION 307.
  
 9) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE CONDENSERS AND THEIR DISTANCES FROM THE ROOF
 EDGES. PLEASE PROVIDE ADDITIONAL CLEARANCE DISTANCE
 MEASUREMENTS FOR O/A INTAKES TO EXHAUST AND VENT
 OPENINGS- SEE SECTIONS 304.11 AND 401.4.
  
 10) PROVIDE A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA
 FOR THE CONDENSER STAND WITH REVIEW STAMP BY THE
 ENGINEER OF RECORD. THE EOR SHALL CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL APPLICABLE INSTALLATION DETAILS AND
 DESIGN PRESSURES SHOWN IN THE DOCUMENT, AND ALSO
 PROVIDE THE WIND DESIGN CRITERIA ON THE PLAN- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-21 Cont ID  
Sent By gjohnson Date 2017-10-21 Time 10:06 Rev Time 0.00
Received By gjohnson Date 2017-10-21 Time 10:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-10-03 Cont ID  
Sent By gjohnson Date 2017-10-03 Time 14:00 Rev Time 0.00
Received By gjohnson Date 2017-10-03 Time 12:46 Sent To  
Notes
2017-10-03 14:22:132ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES
 SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS
 TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE
 WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN
 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND
 THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER
 FBC PL 405.3.5 URINAL STILL SHOWN ON ADA DETAIL AND
 NOTES. SHT.A-1 + P-2 PLEASE REMOVE
  
 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S.
 PER FBC ACC 606.2
  
 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE
 IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1 AAV STILL SHOWN IN MIDDLE OF FLOOR
 ON BRANCH DRAIN FOR SERVICE SINK NOT A REQUIRED VENT
  
 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT
 LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY
 WATER METER. PER WPB UTILITIES PLEASE SHOW BACKFLOW
 NEXT TO METER ON RISER AND FLOOR PLAN.
  
 NEW COMMENTS:
  
 1. PLEASE LABEL FLORIDA ACCESSIBILITY CODE NOTES ON
 SHT. P-1. PER WPB AMEND TO FBC 107.2.1
  
 2. SHUT OFF VALVES ARE REQUIRED ON EACH DROP ON WATER
 PIPING. PER FBC PL 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS: 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE
 IN OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY
 RESIDENTIAL OCCUPANCIES.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By gjohnson Date 2017-08-28 Time 11:20 Rev Time 0.00
Received By gjohnson Date 2017-08-25 Time 10:41 Sent To  
Notes
2017-08-28 11:22:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE MASTER PERMIT APPLICATION INDICATES A DEMO
 PERMIT FOR FUTURE RENOVATION THE PLUMBING SUB PERMIT IS
 FOR A RENOVATION PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 2. SHT. C-1 THE SCOPE OF WORK STATES DIVIDE BUILDING
 INTO 4 OFFICE SPACES BUT THE PLAN ONLY SHOWS 1 BAR
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. C-1 THE PROJECT-DATA SHOWS EXISTING BUILDING
 AREA AS 2364 SF THE SCOPE OF WORK SHOWS EXISTING
 BUILDING AS 2114 SF AND THE OCCUPANT LOAD SHOWS A TOTAL
 OF 1972 SF PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. C-3 THE OCCUPANT LOAD IS STATED AT 102 PEOPLE
 THE PLUMBING FIXTURE REQUIRED SHOWS OCCUPANT LOAD AT 36
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. WITH A OCCUPANT LOAD OF 102 THE PLUMBING FIXTURE
 REQUIRED ARE 2 WC AND 2 LAVATORY'S FOR WOMEN AND THE
 SAME FOR MEN. PER FBC PL TABLE 403.1
  
 6. EACH URINAL UTILIZED BY THE PUBLIC OR EMPLOYEES
 SHALL OCCUPY A SEPARATE AREA WITH WALLS OR PARTITIONS
 TO PROVIDE PRIVACY. THE WALLS OR PARTITIONS SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE. THE WALLS OR PARTITIONS SHALL EXTEND FROM THE
 WALL SURFACE AT EACH SIDE OF THE URINAL NOT LESS THAN
 18 INCHES OR TO A POINT NOT LESS THAN 6 INCHES BEYOND
 THE OUTERMOST FRONT LIP OF THE URINAL MEASURED FROM THE
 FINISHED BACKWALL SURFACE, WHICHEVER IS GREATER. PER
 FBC PL 405.3.5
  
 7. SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE LAVATORY'S.
 PER FBC ACC 606.2
  
 8. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES (380 MM) MINIMUM AND 48 INCHES-MAXIMUM ABOVE THE
 FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
 PER FBC ACC 604.7 DISPENSERS.
  
 9. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT. PER FBC ACC 604.4
  
 10. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 11. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 12. GRAB BARS SHALL BE MEASURED FROM FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 13. TOILET COMPARTMENT DOORS, INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH 404 EXCEPT THAT IF THE APPROACH IS TO
 THE LATCH SIDE OF THE COMPARTMENT DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE COMPARTMENT AND ANY
 OBSTRUCTION SHALL BE 42 INCHES (1065 MM) MINIMUM. DOORS
 SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE
 WALL OR PARTITION FARTHEST FROM THE WATER CLOSET. WHERE
 LOCATED IN THE FRONT PARTITION, THE DOOR OPENING SHALL
 BE 4 INCHES (100 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED
 IN THE SIDE WALL OR PARTITION, THE DOOR OPENING SHALL
 BE 4 INCHES (100 MM) MAXIMUM FROM THE FRONT PARTITION.
 THE DOOR SHALL BE SELF-CLOSING. A DOOR PULL COMPLYING
 WITH 404.2.7 SHALL BE PLACED ON BOTH SIDES OF THE DOOR
 NEAR THE LATCH. TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. PER
 FBC ACC 604.8.1.2
  
 14. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 15. THE AAV VALVES THAT ARE SHOWN ON RISER APPEAR TO BE
 IN THE MIDDLE OF THE FLOORS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 16. THE BRANCH DRAIN FOR FUTURE IS SHOWN IN DIFFERENT
 LOCATION ON THE RISER AND FLOOR PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 17. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR
 TANKLESS WATER HEATER. PER WPB AMEND TO FBC 107.2.1
  
 18. PLEASE PROVIDE HOT AND COLD WATER RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 19. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 20. A SEPARATE PERMIT IS REQUIRED FOR BACKFLOW PLEASE
 SHOW NOT ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 21. THE BACKFLOW ASSEMBLY SHALL BE LOCATED AT CITY
 WATER METER. PER WPB UTILITIES
  
 22. PLEASE SHOW CONDENSATE DRAINS FOR AC AND COOLER.
 PER WPB AMEND TO FBC 107.2.1
  
 23. SHT. C-1 THE SCOPE OF WORK UNDER PLUMBING CALLS OUT
 A WATER FOUNTAIN NONE IS SHOWN ON PLAN PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  