Plan Review Details - Permit 17080780
Plan Review Stops For Permit 17080780
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2018-02-06 Time   Rev Time 0.00
Received By   Date 2018-02-06 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-12 Cont ID  
Sent By jwitmer Date 2018-01-12 Time 17:01 Rev Time 0.00
Received By jwitmer Date 2018-01-12 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jwitmer Date 2017-09-06 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2017-09-06 Time 10:57 Sent To  
Notes
2017-09-06 12:54:552014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080780
 ADD: 4317 NORTHSHORE DR.
 CONT: BUILT SOLID CONSTRUCTION
 TEL: 561-333-2593
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 06/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THE ADDITIONAL SQUARE FOOTAGE OF AN
 ADJACENT TENANT SPACE WILL BE CONSIDERED A CHANGE IN
 OCCUPANCY, PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 2014 FBC-EXIST. BUILD. CODE. 1001.3.1 PARTIAL CHANGE OF
 OCCUPANCY CLASSIFICATION. WHERE A PORTION OF AN
 EXISTING BUILDING IS CHANGED TO A NEW OCCUPANCY
 CLASSIFICATION, SECTION 1012 SHALL APPLY. PLEASE UPDATE
 PLANS AS SUCH.
  
 2) PLEASE NOTE WITH THIS BEING A CHANGE OF OCCUPANCY
 THE DESIGNER OF RECORD MUST MEET THE REQUIREMENTS OF
 1012.1.1.2 CHANGE OF OCCUPANCY CLASSIFICATION WITH
 SEPARATION. THE ORIGINAL PERMIT # 13050463 COMMENT (1A)
 REQUIRED OCCUPANCY SEPARATION WITH A 2 HR. FIRE RATED
 FIRE BARRIER( FBC-B TABLE 503 DAYCARE- BUSINESS) ON
 EACH SIDE OF THE TENANT SPACE. THE SUBMITTED SET OF
 PLANS STILL SHOWS A ONE HOUR FIRE SEPARATION WALL.
 PROVIDE THE WALL ASSEMBLY, COMPOSITION OF THIS WALL.
  
 3) IN THE NEW AREA WHERE THE TENANT SEPARATION OCCURS
 THE PLANS INDICATE AN ASSEMBLY OCCUPANCY AND BLOCK WALL
 CONSTRUCTION. PLEASE PROVIDE THE ASSEMBLY FOR THIS WALL
 FOR A REQUIRED 2 HR. FIRE BARRIER FOR ASSEMBLY TO A I-4
 OCCUPANCY. UNDER THE 2014 FBC-B THERE IS NO DAYCARE
 OCCUPANCY, YOU WILL SEE UNDER AN I-4 OCCUPANCY DAYCARES
 ARE LISTED.
  
 4) PLEASE PROVIDE THE TOTAL AMOUNT OF CHILDREN AND AGES
 OF THE CHILDREN. PLEASE BE SPECIFIC AS HOW MANY
 CHILDREN THERE WILL BE ATTENDING BETWEEN THE AGES OF
 0-2 YEARS OLD AND 2-11.
 2014 FBC-B 308.6.1. CHILDREN BETWEEN THE AGES OF 0-2
 YEARS OLD ARE CONSIDERED EDUCATIONAL AND THE OCCUPANT
 LOAD IS TAKEN AT 20 SQ. FT./ CHILD. THE DAYCARE (I-4)
 OCCUPANCY IS TAKEN AT 35 SQ. FT. / CHILD. SEE TABLE
 1004.1.2.
  
 5) THE DESIGNER OF RECORD ALSO NEEDS TO PROVIDE
 OCCUPANCY SEPARATION BETWEEN THE 0-2 YEAR OLDS
 (EDUCATIONAL) AND THE I-4 (DAYCARE) 2-11 YEAR OLDS AS
 PER TABLE 1004.1.2 AND OPENING PROTECTIVES IN
 COMPLIANCE WITH FBC-B TABLE 716.5.
  
 6) SHEET 1. PLEASE SHOW COMPLIANCE WITH FBC-B 466.3
 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK SHALL BE
 DESIGNED TO PERMIT OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE IN AN EMERGENCY. THE OPENING DEVICE SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
 7) SHEET 1. THIS FACILITY IS NO LONGER ONE SINGLE ROOM.
 PLEASE SHOW COMPLIANCE WITH FBC-B 466.7 DETECTION AND
 ALARM SYSTEMS. DAY CARE OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 907
 AND THIS SECTION.
  
 8) SHEET 1. PLEASE SHOW COMPLIANCE WITH FBC-B:
 2014 FBC-B 466.10.5 SMOKE DETECTION SYSTEMS.
 466.10.5.3 SINGLE-STATION SMOKE ALARMS SHALL BE POWERED
 BY THE BUILDING ELECTRICAL SYSTEM.
 466.10.5.4 SINGLE-STATION SMOKE ALARMS SHALL BE
 PROVIDED IN ALL ROOMS USED FOR SLEEPING.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-15 Cont ID  
Sent By jpearson Date 2018-02-15 Time 15:53 Rev Time 0.00
Received By jpearson Date 2018-02-15 Time 15:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By jpearson Date 2018-01-22 Time 08:29 Rev Time 0.00
Received By jpearson Date 2018-01-22 Time 07:53 Sent To  
Notes
2018-01-22 08:29:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER SECTION C101.4.4 OF THE FBC ENERGY CONSERVATION,
 WHEN A CHANGE OF OCCUPANCY OCCURS, THE INSTALLED
 LIGHTING MUST COMPLY WITH FBC ENERGY CONSERVATION,
 SECTION C405.5. PROVIDE CHART OF INTERIOR LIGHTING
 POWER ALLOWANCES EXPRESSED IN WATTAGE PER THE FBC
 ENERGY COSERVATION IN RELATION TO THE WATTAGE OF THE
 CONNECTED INTERIOR LIGHTING TO COMPLY WITH CODE. FBC EC
 405.5.2
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 3. PLAN STATES THERE ARE NO CHANGES TO THE ELECTRICAL
 SYSTEM, BUT NEW ELECTRICAL WORK IS SHOWN. REMOVE
 CONFLICTING STATEMENT. FBC 107.2.1
 4. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
 5. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. FBC EC 405.2.2,
 405.2.2.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-11 Cont ID  
Sent By jpearson Date 2017-09-11 Time 15:58 Rev Time 0.00
Received By jpearson Date 2017-09-11 Time 15:58 Sent To  
Notes
2017-09-11 15:58:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. FBC 107.2.1,
 107.3.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-02-05 Cont ID  
Sent By pleduc Date 2018-02-05 Time   Rev Time 0.00
Received By pleduc Date 2018-02-05 Time 10:33 Sent To  
Notes
2018-02-05 11:48:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE KEY/DEVICE TO UNLOCK THE BATHROOM DOORS SHALL BE
 WITH STAFF AT ALL TIMES PER NFPA 101.
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-01-11 Cont ID  
Sent By pleduc Date 2018-01-11 Time   Rev Time 0.00
Received By pleduc Date 2018-01-10 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-30 Cont ID  
Sent By pleduc Date 2017-08-30 Time   Rev Time 0.00
Received By pleduc Date 2017-08-29 Time 17:26 Sent To  
Notes
2017-08-30 10:30:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY,
  
 PER NFPA 101, CHAPTER 16, NEW DAY-CARE OCCUPANCIES
  
 4.6.11 CHANGE OF USE OR OCCUPANCY CLASSIFICATION. IN
 ANY BUILDING OR STRUCTURE, WHETHER OR NOT A PHYSICAL
 ALTERATION IS NEEDED, A CHANGE FROM ONE USE OR
 OCCUPANCY CLASSIFICATION TO ANOTHER SHALL COMPLY WITH
 4.6.7.
  
 4.6.7 BUILDING REHABILITATION.
 4.6.7.1 REHABILITATION WORK ON EXISTING BUILDINGS SHALL
 BE CLASSIFIED AS ONE OF THE FOLLOWING WORK CATEGORIES
 IN ACCORDANCE WITH 43.2.2.1:
 (1) REPAIR
 (2) RENOVATION
 (3) MODIFICATION
 (4) RECONSTRUCTION
 (5) CHANGE OF USE OR OCCUPANCY CLASSIFICATION
 (6) ADDITION
  
 PLEASE PROVIDE THE PREVIOUS OCCUPANCY AND THE PROPOSED
 NEW ONE PER (5).
  
  
  
 2) WHAT IS THE SCOPE OF THIS DAY-CARE, PLEASE PROVIDE
 THE CLASSIFICATION OF OCCUPANCY
  
 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4.
 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PART-DAY
 PRESCHOOLS, KINDERGARTENS, AND OTHER SCHOOLS WHOSE
 PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH THE
 CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE,
 SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 14.
  
 PLEASE PROVIDE A BRIEF SCOPE OF THE FUNCTION OF THIS
 DAYCARE.
  
  
 3) A FIRE ALARM IS NOT INDICATED ANYWHERE ON THIS PLAN,
 EXISTING OR PROPOSED.
  
 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN
 DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST
 ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE
 OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE
 WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE WITH SECTION 9.6.
  
 PLEASE PROVIDE AN APPLICABLE NOTE TO INSTALL A FIRE
 ALARM
  
  
 4) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR
 SIZE OR HARDWARE TO THE BATHROOM.
  
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR
 FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE
 READILY ACCESSIBLE TO THE STAFF.
  
 PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF
 HARDWARE.
  
  
 5) THERE IS NO DOOR SCHEDULE INDICATING EXISTING DOOR
 SIZES OR EXIT HARDWARE TO THE TWO EXIT DOORS OF THE NEW
 SPACE.
  
 16.2.2.2 DOORS.
 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED
 TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE,
 PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE
 DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS
 OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE BUILDING WHEN IT IS LOCKED.
  
 PLEASE PROVIDE A DOOR SCHEDULE AND/OR THE TYPE OF
 HARDWARE
  
  
  
  
 6) THERE IS NO EXIT SIGN OVER THE REAR DOOR. THIS DOOR
 IS A REQUIRED EXIT THAT IS REQUIRED TO BE MARKED.
  
 16.2.4.2 NOT LESS THAN TWO SEPARATE EXITS SHALL BE IN
 ACCORDANCE WITH BOTH OF THE FOLLOWING CRITERIA:
 (1) THEY SHALL BE PROVIDED ON EVERY STORY.
 (2) THEY SHALL BE ACCESSIBLE FROM EVERY PART OF EVERY
 STORY AND MEZZANINE; HOWEVER, EXIT ACCESS TRAVEL SHALL
 BE PERMITTED TO BE COMMON FOR THE DISTANCE PERMITTED AS
 COMMON PATH OF TRAVEL BY 16.2.5.3.
  
 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PLEASE PROVIDE EXIT SIGNAGE
  
  
  
 7) THERE ARE NO EMERGENCY LIGHTS INDICATED IN THE
 COMMON AREAS.
  
 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 IN THE
 FOLLOWING AREAS:
 (1) INTERIOR STAIRS AND CORRIDORS
 (2) ASSEMBLY USE SPACES
 (3) FLEXIBLE AND OPEN PLAN BUILDINGS
 (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS
 (5) SHOPS AND LABORATORIES
  
 PLEASE PROVIDE FOR THE REQUIRED EMERGENCY LIGHTING.
  
  
  
 8) THERE IS AN ASSEMBLY SPACE INDICATED NEXT TO THE
 PROPOSED DAYCARE EXPANSION AREA. THERE IS NO FIRE RATED
 SEPARATION INDICATED FOR THIS ESIXTING WALL.
  
 6.1.14.4 SEPARATED OCCUPANCIES.
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE
 COMPLETELY SEPARATED FROM OTHER OCCUPANCIES
 BY FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN
 6.1.14.4.2, 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE
 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING SEPARATIONS.
 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS
 3-HOUR FIRE RESISTANCE?RATED, 2-HOUR FIRE
 RESISTANCE?RATED, OR 1-HOUR FIRE RESISTANCE?RATED AND
 SHALL MEET THE REQUIREMENTS OF CHAPTER 8.
 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED
 IN TABLE
 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE
 PERMITTED TO BE REDUCED BY 1 HOUR, BUT IN NO CASE SHALL
 IT BE REDUCED TO LESS THAN 1 HOUR, WHERE THE BUILDING
 IS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1) AND
 SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED
 BY THE DOUBLE-DAGGER FOOTNOTE IN THE TABLE.
  
 6.1.14.4.4 OCCUPANCY SEPARATION SHALL BE VERTICAL,
 HORIZONTAL, OR BOTH OR, WHEN NECESSARY, OF SUCH OTHER
 FORM AS REQUIRED TO PROVIDE COMPLETE SEPARATION BETWEEN
 OCCUPANCY DIVISIONS IN THE BUILDING.
  
 PLEASE PROVIDE THE REQUIRED SEPARATION AND WALL
 DETAILS.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-03-01 Time 06:45 Rev Time 0.00
Received By lmarchan Date 2018-02-26 Time 10:46 Sent To  
Notes
2018-02-27 10:46:30RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 17:38 Rev Time 0.00
Received By gjohnson Date 2018-02-02 Time 15:02 Sent To  
Notes
2018-02-02 15:02:18B12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 16:13 Rev Time 0.00
Received By gjohnson Date 2018-01-08 Time 13:53 Sent To  
Notes
2018-01-09 13:53:46B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-19 Cont ID  
Sent By cpuell Date 2017-09-19 Time 15:18 Rev Time 0.00
Received By cpuell Date 2017-08-25 Time 11:35 Sent To  
Notes
2017-08-25 11:37:11B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2018-03-01 Cont ID  
Sent By jwitmer Date 2018-03-01 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2018-03-01 Time 06:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-06 Cont ID  
Sent By jwitmer Date 2017-09-06 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2017-09-06 Time 10:57 Sent To  
Notes
2017-09-06 12:55:28IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 17:37 Rev Time 0.00
Received By gjohnson Date 2018-02-15 Time 17:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-22 Cont ID  
Sent By gjohnson Date 2018-01-22 Time 16:09 Rev Time 0.00
Received By gjohnson Date 2018-01-22 Time 16:09 Sent To  
Notes
2018-01-22 16:13:102ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 1. THE VALUATION OF THE THE JOB IS LOW PLEASE PROVIDE A
 SIGNED PROPOSAL OF WORK OR CONTRACT. PER WPB AEND TO
 FBC 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-09-19 Cont ID  
Sent By thunt Date 2017-09-19 Time 14:20 Rev Time 0.00
Received By thunt Date 2017-09-18 Time 13:47 Sent To  
Notes
2017-09-19 14:20:141ST PLUMBING REVIEW 9/19/17-DENIED
  
 A COMPREHENSIVE REVIEW CANNOT BE PERFORMED AT THIS TIME
 DUE TO LACK OF INFORMATION FBC 107.3.5
  
 THE VALUATION SEEMS LOW. PROVIDE A BONI FIDE SIGNED
 CONTRACT FOR THE WORK LISTED FBC 109.3
  
 AS THE BUILDING REVIEWER HAS COMMENTED THIS WOULD BE A
 CHANGE OF OCCUPANCY PER FBC SECTION 1012 AND ALL PUBLIC
 AND COMMON AREA BATHROOM FACILITIES WOULD NEED TO FULLY
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY IN FULL. A
 COMPLETE ISOMETRIC DRAWING OF THE SANITARY INCLUDING
 PIPE SIZING WOULD ALSO BE REQUIRED FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  