Plan Review Details - Permit 17080713
Plan Review Stops For Permit 17080713
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-10-05 Cont ID  
Sent By tklarge Date 2017-10-05 Time 11:25 Rev Time 0.00
Received By tklarge Date 2017-10-05 Time 11:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-09-28 Cont ID  
Sent By tklarge Date 2017-09-28 Time 12:25 Rev Time 0.00
Received By tklarge Date 2017-09-20 Time 10:38 Sent To  
Notes
2017-09-25 10:38:18RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-21 Cont ID  
Sent By tklarge Date 2017-08-21 Time 11:05 Rev Time 0.00
Received By tklarge Date 2017-08-15 Time 15:01 Sent To  
Notes
2017-08-16 15:01:46PLUMB<5K

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-10-05 Cont ID  
Sent By tklarge Date 2017-10-05 Time 11:25 Rev Time 0.00
Received By tklarge Date 2017-10-05 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-09-28 Cont ID  
Sent By tklarge Date 2017-09-28 Time 12:25 Rev Time 0.00
Received By tklarge Date 2017-09-28 Time 09:59 Sent To  
Notes
2017-09-28 10:18:301) THE GREASE TRAP CALCULATIONS FROM MESSLER &
 ASSOCIATES REFER TO AN 80 GALLON GREASE TRAP BUT THE
 SPECIFICATIONS ARE FOR A 75 GPM UNIT. CLARIFY.IF AN 80
 GPM UNIT IS REQUIRED YOU CANNOT INSTALL A 75 GPM UNIT.
 2) THE HAND SINK IN THE SERVICE AREA HAS BEEN RELOCATED
 BUT IT IS NOT SHOWN ON THE DOMESTIC PLUMBING RISER OR
 KITCHEN WASTE RISER. CLARIFY.
 3) THE KITCHEN WASTE RISER SHOWS A VENT WITH NO FIXTURE
 ON IT THAT IS NOW A FLAT, DRY VENT AND IN VIOLATION OF
 2014 FBC-PLUMBING SEC.905.3.
 4) A SERVICE SINK, NOT A LAUNDRY SINK IS REQD. PER THE
 2014 FBC -PLUMBING TABLE 403.1.
 5) A VENT IS REQD. ON THE SERVICE SINK. 2014 FBC -
 PLUMBING SEC.901.2, 901.2.1.
 6) IS THERE A DRAIN ON THE STEAM TABLE TO THE SANITARY
 SYSTEM? CLARIFY. IF SO, SHOW THE DRAIN AND SIZE OF
 DRAIN ON THE PLUMBING RISER. WASTE WATER TEMPERATURE
 DISCHARGED TO THE SANITARY SYSTEM SHALL NOT EXCEED 140
 DEGREES. 2014 FBC-PLUMBING SEC.803.1.
 7) A CLEAR FLOOR SPACE OF 60 INCHES WIDE MINIMUM
 MEASURED BY 56 INCHES DEEP MINIMUM SHALL BE PROVIDED
 FOR THE WATER CLOSET PER 2014 FBC-ACCESS. SEC.604.3.1.
 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED
 WITHIN THE REQUIRED WATER CLOSET CLEARANCE. YOUR
 DIMENSIONS ON THE PLANS ARE REVERSED. YOU SHOW 60
 INCHES DEEP AND 56 INCHES WIDE. REVISE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
 NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED
 DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE
 SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT
 #16041117). SUBMIT A SEPARATE ADDITIONAL REVISION FOR
 THE NOTED CHANGES TO THE PLUMBING PLAN. REFER TO
 COMMENTS # 2, 3,4,5,6,7,
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By tklarge Date 2017-08-21 Time 11:04 Rev Time 0.00
Received By tklarge Date 2017-08-21 Time 09:38 Sent To  
Notes
2017-08-21 09:53:191) GREASE TRAP SIZING DETAILS - THE BOTTOM OF THE
 SIZING DETAILS FROM THE GREASE MONKEY SIZING SUMMARY
 PAGE HAVE BEEN CUT OFF. SUBMIT THE SIZING DETAILS THAT
 SHOW ALL CRITERIA/CALCULATIONS. WPB AMEND. TO FBC SEC.
 107.2.1, 2014 FBC-PLUMBING SEC. 1003.2.
 2) SHT. 3 OF 3 - THE KITCHEN WASTE RISER STILL SHOWS AN
 EXISTING GREASE INTERCEPTOR. SUBMIT A REVISED KITCHEN
 WASTE RISER DIAGRAM SHOWING THE GB GREASE TRAP..WPB
 AMEND. TP FBC SEC. 107.3.5.1.3.
 3) SHT. 2 OF 3 OF THE REVISED PLANS SHOWS A MOP SINK IN
 THE STORAGE ROOM NEXT TO THE RESTROOM WHICH WAS NOT ON
 THE ORIGINAL PLANS. SUBMIT A REVISED SANITARY AND WATER
 RISER DIAGRAM THAT SHOWS THE MOP SINK. WPB AMEND TO FBC
 SEC. 107.2.1.
 4) THE SINK THAT HAS BEEN RELOCATED FROM THE KITCHEN
 AREA TO NEAR THE JUICE BAR SHALL BE VENTED ON THE
 PLUMBING RISER. 2014 FBC-PLUMBING SEC.901.2.1.
 5) SHT. 3 OF 3 - SHOW THE WIDTH AND LENGTH OF THE
 TOILET ROOM. THE PLANS SHOW THE LAVATORY IN THE TOILET
 ROOM RELOCATED ADJACENT TO THE WATER CLOSET. A CLEAR
 FLOOR SPACE 60 INCHES WIDE MINIMUM BY 56 INCHES DEEP
 MINIMUM SHALL BE PROVIDED FOR THE WATER CLOSET. NO
 OTHER FIXTURES OR OBSTRUCTION SHALL BE LOCATED WITHIN
 THE REQUIRED WATER CLOSET CLEARANCE PER THE 2014
 FBC-ACCESS. SEC.604.3.2.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GREASE
 TRAP TO BE INSTALLED. 2014 FBC-PLUMBING SEC. 1003.2.
  
 NOTE: THE PERMIT FOR THE INTERCEPTOR CANNOT BE APPROVED
 DUE TO THE DEFICIENCIES AND CHANGES NOTED ON THE
 SUBMIITED PLANS FROM THE APPROVED MASTER PLANS (PERMIT
 #16041117). SUBMIT A SEPARATE REVISION FOR THE NOTED
 CHANGES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  