Plan Review Details - Permit 17080681
Plan Review Stops For Permit 17080681
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date   Cont ID  
Sent By jwitmer Date   Time 17:29 Rev Time 0.00
Received By jwitmer Date 2017-08-23 Time 16:06 Sent To  
Notes
2017-08-23 17:25:41BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080681
 W. P. B. PERMIT: 16090560
 ADD: 600 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-267-1309
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 23/2017
 ACTION: BUILDING PROVISO
  
 1) THE M1.0 SHEET NOTE FOR A/C CONDENSER STAND NOTE
 INDICATES FOR REFERENCE ONLY. THE STRUCTURAL
 ATTACHMENTS TO THE ROOF AND THE CONDENSING UNIT STAND
 TO BE VERIFIED BY A STRUCTURAL AND OR SPECIALTY
 ENGINEER.
  
 2) PART OF THE PROVISO AT PERMIT ISSUANCE WAS DEFERRED
 SUBMITTALS LISTED IN THAT GROUP IS PRE-ENGINEERED A/C
 STANDS. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-22 Cont ID  
Sent By jpearson Date 2017-08-22 Time 11:19 Rev Time 0.00
Received By jpearson Date 2017-08-22 Time 11:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By wjolin Date 2017-08-18 Time 14:26 Rev Time 0.00
Received By wjolin Date 2017-08-18 Time 11:29 Sent To  
Notes
2017-08-18 13:18:15 
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-30 Cont ID  
Sent By cpuell Date 2017-08-30 Time 11:47 Rev Time 0.00
Received By cpuell Date 2017-08-14 Time 10:51 Sent To  
Notes
2017-08-15 11:01:54C18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-08-29 Cont ID  
Sent By ccole Date 2017-08-29 Time 10:30 Rev Time 0.00
Received By ccole Date 2017-08-29 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-08-24 Cont ID  
Sent By gjohnson Date 2017-08-24 Time 16:49 Rev Time 0.00
Received By thunt Date 2017-08-24 Time 16:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-30 Cont ID  
Sent By eschneid Date 2017-08-30 Time 09:18 Rev Time 0.50
Received By eschneid Date 2017-08-30 Time 09:17 Sent To PC
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved