Plan Review Details - Permit 17080677
Plan Review Stops For Permit 17080677
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By cthroop Date 2018-11-13 Time 08:26 Rev Time 0.00
Received By cthroop Date 2018-11-10 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-02-16 Cont ID  
Sent By cthroop Date 2018-02-16 Time 07:53 Rev Time 0.00
Received By cthroop Date 2018-02-15 Time 09:42 Sent To  
Notes
2018-02-16 07:58:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
 2. PROVIDE PRODUCT APPROVALS FOR NEW EXTERIOR DOORS.
 3. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 BBQ GRILL.
 4. NEW COMMENT - NOA 13-0419.04 FOR ASPHALT SHINGLES
 HAS EXPIRED. PROVIDE CURRENT NOA OR FL PRODUCT APPROVAL
 FOR NEW ROOFING PRODUCTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By cthroop Date 2017-09-14 Time 15:20 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 07:27 Sent To M
Notes
2017-09-14 15:25:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SOILS REPORT.
 2. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 3. PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR
 BBQ GRILL.
 4. PROVIDE PRODUCT APPROVALS FOR NEW EXTERIOR DOORS.
  
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-12 Cont ID  
Sent By jpearson Date 2018-10-12 Time 14:49 Rev Time 0.00
Received By jpearson Date 2018-10-12 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-02-09 Cont ID  
Sent By jpearson Date 2018-02-09 Time 15:07 Rev Time 0.00
Received By jpearson Date 2018-02-09 Time 15:07 Sent To  
Notes
2018-02-09 15:06:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. SEE NEW
 COMMENT THAT FOLLOWS THE ORIGINAL COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. PROVIDE SPEC SHEET FOR EXISTING METER CAN SHOWING
 DOUBLE LUG COMPATIBLE. DESCRIBE METHOD OF DOUBLE LUG
 TAP. FBC 107.2.1, NEC 110.3 (PLAN SHOWS A TAP FROM THE
 200 AMP DISCONNECT TO BE INSTALLED. WHAT IS THE METHOD
 OF THIS TAP? MOST 200 AMP DISCONNECTS HAVE A LUG RATED
 FOR A SINGLE WIRE, NOT FOR TWO AS SHOWN IN RISER.
 PROVIDE CLARIFICATION AND/OR CORRECT.)
 6. CORRECTED.
 7. CORRECTED.
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER FOR PANEL A AT THE NEW BUILDING. NEC
 225.31, 225.32 (THE MOUNTING LOCATION OF THE DISCONNECT
 THAT WAS ADDED FOR THIS IS NOT SHOWN ON POWER PLAN.
 SHOW LOCATION OF DISCONNECT SO RISER AND POWER PLAN
 MATCH. FBC 107.2.1)
 9. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE3607.3 (NOTE ON PLAN STATES THIS IS NOT REQUIRED PER
 FIGURE 250.87, WHICH DOES NOT EXIST. THIS IS REQUIRED,
 PROVIDE AS PREVIOUSLY REQUESTED. SEE EXHIBIT 250.19 IN
 THE NEC HANDBOOK FOR FURTHER CLARIFICATION.)
 10. CORRECTED.
 11. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE3903.3 (A SWITCH SHOULD BE LOCATED AT EACH GRADE
 LEVEL ACCESS, ONE IS MISSING.)
 12. CORRECTED.
  
 NEW COMMENT:
  
 13. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By jpearson Date 2017-08-29 Time 15:24 Rev Time 0.00
Received By jpearson Date 2017-08-29 Time 15:24 Sent To  
Notes
2017-08-29 15:24:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE # 1 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE4002.14
 2. NOTE # 11 STATES THAT LIGHTING IN CLOTHES CLOSETS
 SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH DOESN?T EXIST.
 PROVIDE CORRECTION. NEC 410.16; FBC RE4003.12
 3. SEVERAL ELECTRICAL NOTES REFER TO EXISTING
 INSTALLATION, BUT THE PERMIT APPLICATION STATES THIS IS
 A NEW BUILDING. REMOVE ANY NOTES NOT PERTAINING TO THIS
 JOB. FBC 107.2.1
 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. NEC 250.94; FBC RE3609.3
 5. PROVIDE SPEC SHEET FOR EXISTING METER CAN SHOWING
 DOUBLE LUG COMPATIBLE. DESCRIBE METHOD OF DOUBLE LUG
 TAP. FBC 107.2.1, NEC 110.3
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 7. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, LOCATION OF MAIN DISCONNECTS AND
 LABELING FOR THOSE DISCONNECTS, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 INTERIOR PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30 FBC RE3706.1, RE3608.1,
 RE3609.3; FBC 107.2.1
 8. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER FOR PANEL A AT THE NEW BUILDING. NEC
 225.31, 225.32
 9. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE3607.3
 10. ADDRESS PANEL A LOCATION. OVERCURRENT PROTECTION
 DEVICES ARE NOT PERMITTED IN THE VICINITY OF EASILY
 IGNITABLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 240.24(D); FBC
 RE3705.7
 11. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B),
 FBC RE3903.3
 12. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-10-31 Cont ID  
Sent By jesmith Date 2018-10-31 Time 16:01 Rev Time 0.00
Received By jesmith Date 2018-10-31 Time 12:48 Sent To  
Notes
2018-10-31 16:01:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012
 5TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW:
 GAS PIPING COMMENTS: DENIED
  
 1. RE: WPB FBC 107.2.1; MANUFACTURER?S SPECIFICATION
 SHEETS REQUIRED SUBMITTALS
 A) NG LINE REGULATOR (MP)
 ? PROVIDE ONE SPEC SHEET TO ACCOMPANY EACH APPLIANCE
 INCLUSIVE OF EXISTING POOL HEATER, NOTING INDOOR OR
 OUTDOOR APPLICATION AND SPECIFY CORRECT VENT LIMITING
 DEVICE OR VENT PROTECTOR AS REQUIRED BY APPLICATION.
 B) TANKLESS WATER HEATER
 ? RINNAI RL75E IS NOT FOR INDOOR INSTALLATION
 1) SUBMIT A UNIT FOR INDOOR USE
 2) PROVIDE DETAIL AND MANUFACTURER?S RECOMMENDED VENT
 TERMINATION KIT SPEC
 3) IDENTIFY RUSKIN LOUVER AS 12 X 18 COMBUSTION AIR
 VENT
 4) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 C) BBQ GRILL
 ? SALES BROCHURE IS NOT ADEQUATE
 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT.
 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 D) EXISTING EQUIPMENT
 ? POOL HEATER
 1) PROVIDE MANUFACTURER?S SPEC SHEET FOR UNIT.
 2) PROVIDE SPEC SHEET FOR LINE REGULATOR AS REQUIRED BY
 APPLICATION
 2. REVISE THE GAS PIPING RISER DIAGRAM THAT SHOWS THE
 TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE INCLUSIVE OF THE EXISTING POOL HEATER, THE
 RUN FROM THE NEW APPLIANCES BACK TO THE INTERSECTION
 WITH THE BRANCH TO THE EXISTING POOL HEATER, THE RUN
 FROM THAT INTERSECTION TO THE UPGRADED REGULATOR AND
 METER AND THE DISTANCE OF THE LONGEST LENGTH OF PIPING
 FROM THE POINT OF DELIVERY TO THE MOST REMOTE OUTLET
 INCLUSIVE OF THE EXISTING POOL HEATER AND THE LOAD OF
 THE SECTION.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 ADDITIONAL NOTES; DOES NOT APPLY TO PERMIT APPLICATION
  
 1. CITY RECORDS SHOW .5LB GAS ON EXISTING SYSTEM.
 PROVIDE AFFIDAVIT OF GAS PIPING TEST TO INCLUDE OF
 EXISTING SYSTEM FOR FINAL INSPECTION IN ACCORDANCE WITH
 FBC FG 406 TO INSURE IT IS 2PSI CAPABLE.
 2. THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION.
 FGC SEC.305.1, FBC-RES.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 08:15 Rev Time 0.00
Received By gjohnson Date 2018-02-15 Time 08:15 Sent To  
Notes
2018-02-15 09:08:322ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS ARE NOT COMPLIED WITH
 IN ORDER TO EXPEDITE THE APPROVAL OF THIS PLAN I
 SUGGEST A MEETING BE SCHEDULED TO GO OVER COMMENTS
 BEFORE THE NEXT RESUBMITTAL.
  
 CITY RECORDS SHOW MUILT PERMITS ISSUED FOR .5LB GAS ON
 MAIN HOME.
  
 PARTIALLY COMPLIED 1) LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC.
 G2413. SHOW BTU LOAD ON THE GAS RISER.
  
 2ND REQUEST 2) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
  
 2ND REQUEST 5) THE PLANS INDICATE AN EXISTING GAS
 METER. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 THE GAS OR PLUMBING CONTRACTOR CANNOT TIE INTO THE GAS
 UTILITIES LINE ONLY THE GAS UTILITIES COMPANY CAN DO
 THAT WHICH IS FLORIDA PUBLIC UTILITIES. IF YOU HAVE FPU
 INSTALL A NEW METER WITH A 2PSI REGULATOR SHOW IT ON
 THE RISER ALONG WITH THE DISTANCE FROM THE METER TO THE
 FURTHEST APPLIANCE SHOWN ON THE RISER.
 REMOVE NOTE #4 FROM SCOPE OF WORK.
  
 2ND REQUEST 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 2ND REQUEST 7) SHOW THE DISTANCE FROM THE 2 PSI
 REGULATOR TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL
 GAS TABLE 402.4 (28) FOR THE PROPER PIPE SIZE AND BTU
 LOAD.
  
 NEW COMMENTS:
  
 1. SHOW ON THE GAS RISER THE TRANSITION FROM PE PIPE TO
 TYPE OF PIPING BEFORE INTERRING BUILDING FOR THE
 TANKLESS HEATER. PE PIPING CANNOT RUN IN OR UNDER THE
 BUILDING. PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENT FOR WATER HEATER PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU 505.
  
 3. THE 10 X10 OPENING FOR COMBUSTION AIR SHALL COMPLY
 WITH FBC MECH. 401.5 PROVIDE MANUFACTURE SPECS AND
 PRODUCT APPROVAL. PER WPB AMEND TO FBC 107.2.1
  
 4. SHOW TYPE OF PIPE AND PRESSURE ON THE RISER. PER WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 07:22 Rev Time 0.00
Received By thunt Date 2017-08-29 Time 07:15 Sent To  
Notes
2017-08-29 07:22:101ST REVIEW DENIED
  
 CITY RECORDS SHOW MUILT PERMITS ISSUED FOR .5LB GAS ON
 MAIN HOME.
  
 1) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413
  
 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 3 )SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FGC
 SEC.304.9.3 OR FBCR G2407.9.3.
  
 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4
  
 5) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1.
  
 7) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLE 402.4
 (28) FOR THE PROPER PIPE SIZE AND BTU LOAD.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-01-30 Cont ID  
Sent By fmittner Date 2018-01-30 Time 11:17 Rev Time 0.00
Received By fmittner Date 2018-01-30 Time 11:17 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By fmittner Date 2017-08-18 Time 10:22 Rev Time 0.00
Received By fmittner Date 2017-08-18 Time 10:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-13 Cont ID  
Sent By cthroop Date 2018-11-13 Time 08:26 Rev Time 0.00
Received By cthroop Date 2018-10-05 Time 14:40 Sent To  
Notes
2018-10-09 14:40:36R04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-02-16 Cont ID  
Sent By cthroop Date 2018-02-16 Time 07:53 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 11:25 Sent To I
Notes
2018-01-24 11:26:00R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-15 Cont ID  
Sent By hmoser Date 2017-09-15 Time 10:24 Rev Time 0.00
Received By hmoser Date 2017-08-14 Time 12:28 Sent To  
Notes
2017-08-15 12:28:59R15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By cthroop Date 2017-09-14 Time 15:18 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 07:28 Sent To  
Notes
2017-09-14 15:19:48BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-01-31 Cont ID  
Sent By hmoser Date 2018-01-31 Time 11:00 Rev Time 0.00
Received By hmoser Date 2018-01-31 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-15 Cont ID  
Sent By hmoser Date 2017-09-15 Time 10:24 Rev Time 0.00
Received By hmoser Date 2017-09-15 Time 10:21 Sent To  
Notes
2017-09-15 10:24:36PLAN DENIED
 PROVIDE CAN SIZE ON PLANS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-31 Cont ID  
Sent By jesmith Date 2018-10-31 Time 16:21 Rev Time 0.00
Received By jesmith Date 2018-10-31 Time 16:19 Sent To  
Notes
2018-10-31 16:21:41APPROVED
 PROVISO
  
 GAS TANKLESS WATER HEATER SPEC AND DETAIL TO BE
 SUBMITTED AND APPROVED UNDER GAS PERMIT.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-02-15 Cont ID  
Sent By gjohnson Date 2018-02-15 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2018-02-14 Time 11:07 Sent To  
Notes
2018-02-15 09:09:35SHALL COMPLY WITH GAS COMMENTS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-29 Cont ID  
Sent By thunt Date 2017-08-29 Time 07:13 Rev Time 0.00
Received By thunt Date 2017-08-28 Time 15:24 Sent To  
Notes
2017-08-29 07:15:26PROVIDE OUTSIDE SHOWER DETAIL SHOWING HOW YOU PLAN ON
 STOPPING STORM WATER FROM ENTERING SEWER SYSTEM FPC
 1101.3
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-09-14 Cont ID  
Sent By cthroop Date 2017-09-14 Time 15:18 Rev Time 0.00
Received By cthroop Date 2017-09-14 Time 08:49 Sent To  
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2019-06-11 Cont ID  
Sent By spalmer Date 2019-06-11 Time 10:31 Rev Time 0.00
Received By spalmer Date 2019-06-11 Time 10:31 Sent To  
Notes
2019-06-11 10:32:26APPLICATION HAS BEEN EXTENDED 90 DAYS PER ROBERT BROWN

Review Stop Z ZONING
Rev No 2 Status P Date 2018-01-30 Cont ID  
Sent By fmittner Date 2018-01-30 Time 11:17 Rev Time 0.00
Received By fmittner Date 2018-01-30 Time 11:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-18 Cont ID  
Sent By fmittner Date 2017-08-18 Time 10:22 Rev Time 0.00
Received By fmittner Date 2017-08-18 Time 10:22 Sent To  
Notes
***NONE***