Plan Review Details - Permit 17080529
Plan Review Stops For Permit 17080529
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-01-22 Cont ID  
Sent By shill Date 2018-01-22 Time 06:37 Rev Time 0.00
Received By shill Date 2018-01-22 Time 06:37 Sent To  
Notes
2018-01-22 06:38:20PROVISO
 SEPARATE PERMITS REQUIRED FOR MEDGAS, FIRE SPRINKLER,
 FIRE ALARM
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-12-13 Cont ID  
Sent By jwitmer Date 2017-12-13 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2017-12-13 Time 13:33 Sent To  
Notes
2017-12-13 16:35:582014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17070529
 ADD: 400 S. AUSTRALIAN AVE. SUITE: 6TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-914-9848
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 13/ 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) THE COVERSHEET INDICATES THE FIRE SPRINKLERS ARE
 GOING TO BE A DESIGN BUILD SYSTEM. EVEN THOUGH THIS
 TENANT SPACE IS NOT GOING TO BE CONSIDERED AN
 AMBULATORY CARE FACILITY, THIS BUILDING IS A HIGHRISE
 BUILDING.
  
 IN THE 2014 FBC-B 403.3 AUTOMATIC SPRINKLER SYSTEM,
 HIGH RISE. 903.2.11.3 BUILDINGS THREE STORIES OR MORE
 IN HEIGHT. ANY BUILDING WHICH IS OF THREE STORIES OR
 MORE IN HEIGHT SHALL BE EQUIPPED WITH AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH
 SECTION 903.1.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.3.1.2 NO PERMIT MAY BE ISSUED FOR
 ANY BUILDING CONSTRUCTION, ERECTION, ALTERATION,
 MODIFICATION, REPAIR, OR ADDITION UNLESS THE APPLICANT
 FOR SUCH PERMIT PROVIDES TO THE
 ENFORCING AGENCY WHICH ISSUES THE PERMIT ANY OF THE
 FOLLOWING DOCUMENTS WHICH APPLY TO THE CONSTRUCTION FOR
 WHICH THE PERMIT IS TO BE ISSUED AND WHICH SHALL BE
 PREPARED BY OR UNDER THE DIRECTION OF AN ENGINEER
 REGISTERED UNDER CHAPTER 471, FLORIDA STATUTES:
 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR
 ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH
 CONTAINS 50 OR MORE SPRINKLER HEADS. A CONTRACTOR I,
 CONTRACTOR II OR CONTRACTOR IV, CERTIFIED UNDER SECTION
 633.521, FLORIDA STATUTES, MAY DESIGN A FIRE SPRINKLER
 SYSTEM OF 49 OR FEWER HEADS AND MAY DESIGN THE
 ALTERATION OF AN EXISTING FIRE SPRINKLER SYSTEM IF THE
 ALTERATION CONSISTS OF THE RELOCATION, ADDITION OR
 DELETION OF NOT MORE THAN 49 HEADS, NOTWITHSTANDING THE
 SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 4-6) COMPLIED.
  
 7) NEW COMMENT. A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES ARE REQUIRED FOR A MEDICAL GAS PERMIT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.3.1.2 NO PERMIT MAY BE ISSUED FOR
 ANY BUILDING CONSTRUCTION, ERECTION, ALTERATION,
 MODIFICATION, REPAIR, OR ADDITION UNLESS THE APPLICANT
 FOR SUCH PERMIT PROVIDES TO THE
 ENFORCING AGENCY WHICH ISSUES THE PERMIT ANY OF THE
 FOLLOWING DOCUMENTS WHICH APPLY TO THE CONSTRUCTION FOR
 WHICH THE PERMIT IS TO BE ISSUED AND WHICH SHALL BE
 PREPARED BY OR UNDER THE DIRECTION OF AN ENGINEER
 REGISTERED UNDER CHAPTER 471, FLORIDA STATUTES:
 3. ANY SPECIALIZED MECHANICAL, ELECTRICAL, OR PLUMBING
 DOCUMENT FOR ANY NEW BUILDING OR ADDITION WHICH
 INCLUDES A MEDICAL GAS, OXYGEN, STEAM, VACUUM, TOXIC
 AIR FILTRATION, HALON, OR FIRE DETECTION AND ALARM
 SYSTEM WHICH COSTS MORE THAN $5,000.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-24 Cont ID  
Sent By jwitmer Date 2017-08-24 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2017-08-24 Time 09:16 Sent To  
Notes
2017-08-24 14:30:392014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080529
 ADD: 400 S AUSTRALIAN AVE. / SUITE: 6TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-914-9848
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUGUST 10/ 2017
 ACTION: DENIED
  
 1) THE COVERSHEET STATES THAT THE OCCUPANCY IS A
 BUSINESS OCCUPANCY, AND GOES FURTHER UNDER THE USE
 DISCLOSURE STATEMENT THAT SEDATED PATIENTS ARE NOT
 RENDERED UNCONSCIOUS. IN VIEWING THE MSDS SHEETS FOR
 NITROUS OXIDE- INHALATION. MAY CAUSE EXCITATION,
 DIZZINESS, DROWSINESS, POOR COORDINATION, AND NARCOSIS
 ( NARCOSIS PRODUCES A STATE SIMILAR TO DRUNKENNESS).
  
 THE P03 SHEET SHOWS 9 CUBICLES THAT HAVE BOTH OXYGEN
 AND NITROUS OXIDE PIPED INTO EACH UNIT. THE 2014 FBC-B
 MAKES THE DISTENSION BETWEEN A BUSINESS OCCUPANCY AND
 AMBULATORY CARE FACILITY WHEN THERE IS A POTENTIAL FOR
 FOUR OR MORE CARE RECIPIENTS ARE TO BE INCAPABLE OF
 SELF-PRESERVATION AT ANY TIME, WHETHER RENDERED
 INCAPABLE BY STAFF OR STAFF ACCEPTED RESPONSIBILITY FOR
 A CARE RECIPIENT ALREADY INCAPABLE, THIS MAKES THE
 TENANT SPACE A AMBULATORY CARE FACILITY. COVERED UNDER
 THE 2014 FBC-B 422.1- 422.7.
  
 1A) 422.2 SEPARATION. AMBULATORY CARE FACILITIES WHERE
 THE POTENTIAL FOR FOUR OR MORE CARE RECIPIENTS ARE TO
 BE INCAPABLE OF SELF-PRESERVATION AT ANY TIME, WHETHER
 RENDERED INCAPABLE BY STAFF OR STAFF ACCEPTED
 RESPONSIBILITY FOR A CARE RECIPIENT ALREADY INCAPABLE,
 SHALL BE SEPARATED FROM ADJACENT SPACES, CORRIDORS OR
 TENANTS WITH A FIRE PARTITION INSTALLED IN ACCORDANCE
 WITH SECTION 708.
  
 1B) 422.3 SMOKE COMPARTMENTS. NOT APPLICABLE, THE
 FACILITY IS NOT LARGER THAN 10,000 SQ. FT.
  
 1C) SHOW COMPLIANCE. 422.4 REFUGE AREA. NOT LESS THAN
 30 NET SQUARE FEET (2.8 M2) FOR EACH NONAMBULATORY CARE
 RECIPIENT SHALL BE PROVIDED WITHIN THE AGGREGATE AREA
 OF CORRIDORS, CARE RECIPIENT ROOMS, TREATMENT ROOMS,
 LOUNGE OR DINING AREAS AND OTHER LOW-HAZARD AREAS
 WITHIN EACH SMOKE COMPARTMENT. EACH OCCUPANT OF AN
 AMBULATORY CARE FACILITY SHALL BE PROVIDED WITH ACCESS
 TO A REFUGE AREA WITHOUT PASSING THROUGH OR UTILIZING
 ADJACENT TENANT SPACES.
  
 1D) 422.5 INDEPENDENT EGRESS. NOT APPLICABLE.
  
 1E) SHOW COMPLIANCE. FBC-B 422.6 AUTOMATIC SPRINKLER
 SYSTEMS. AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED
 FOR AMBULATORY CARE FACILITIES IN ACCORDANCE WITH
 SECTION 903.2.2.
 FBC-B 903.2.2 AMBULATORY CARE FACILITIES. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED THROUGHOUT THE
 ENTIRE FLOOR CONTAINING AN AMBULATORY CARE FACILITY
 WHERE EITHER OF THE FOLLOWING CONDITIONS EXIST AT ANY
 TIME:
 1. FOUR OR MORE CARE RECIPIENTS ARE INCAPABLE OF
 SELF-PRESERVATION, WHETHER RENDERED INCAPABLE BY STAFF
 OR STAFF HAS ACCEPTED RESPONSIBILITY FOR CARE
 RECIPIENTS ALREADY INCAPABLE.
 2. ONE OR MORE CARE RECIPIENTS THAT ARE INCAPABLE OF
 SELF-PRESERVATION ARE LOCATED AT OTHER THAN THE LEVEL
 OF EXIT DISCHARGE SERVING SUCH A FACILITY.
  
 1F) SHOW COMPLIANCE. FBC-B 422.7 FIRE ALARM SYSTEMS. A
 FIRE ALARM SYSTEM SHALL BE PROVIDED FOR AMBULATORY CARE
 FACILITIES IN ACCORDANCE WITH SECTION 907.2.2.
  
 2) THE COVERSHEET INDICATES THE FIRE SPRINKLERS ARE
 GOING TO BE A DESIGN BUILD SYSTEM. PLEASE NOTE THE
 FBC-B UNDER SECTIONS 422.6 AND 903.2.2 BOTH REQUIRE
 FIRE SPRINKLER PLANS BEFORE PERMIT ISSUANCE. THE SAME
 IS REQUIRED FOR FIRE ALARM. BOTH FIRE SPRINKLER AND
 FIRE ALARM REQUIRE A SEPARATE PERMIT.
  
 3) SHEET A103 SHOWS THE ROOM 641 TO BE A 1 HOUR FIRE
 RATED ROOM WHICH CONTAINS THE VARIOUS BOTTLED GASSES.
 PLEASE PROVIDE THE MSDS SHEETS FOR NITROUS OXIDE &
 OXYGEN. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) P301 SHOW THERE TO BE 4 CYLINDERS WITHIN THE ROOM.
 P003 INDICATES NITROUS OXIDE, OXYGEN AND AIR. PLEASE
 PROVIDE THE QUANTITY OF CYLINDERS OF EACH GAS, SIZE OF
 CYLINDER IN CUBIC FEET TO SEE IF THE QUANTITIES OF GAS
 MEET THE REQUIREMENTS FOR CONTROL AREAS UNDER FBC-B
 TABLE 307.1(1).
  
 5) DATE 9/14/17 IN DISCUSSING THE MECHANICAL SHEET M101
 WITH OUR MECHANICAL REVIEWER CHRIS COLE, THIS SHEET
 SHOWS EXHAUST AIR BEING BROUGHT INTO THE 2 HOUR RATED
 STAIR VESSTIBULE. THE REQUIREMENT FOR SMOKEPROOF
 ENCLOSURES IS FOUND IN FBC-B 1022.10. THIS ALSO BRINGS
 US TO 909.20 SMOKEPROOF ENCLOSUES AND
 909.20.2VCONSTRUCTION. THERE IS A QUESTION OF WHICH
 CODE REQUIREMENTS ARE BEING MET 909.20.3.3. VESTIBULE
 VENTILATION OR 909.20.4 MECHANICAL VENTILATION
 ALTERNATIVE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-02-06 Cont ID  
Sent By jpearson Date 2018-02-06 Time 09:38 Rev Time 0.00
Received By jpearson Date 2018-02-06 Time 09:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-27 Cont ID  
Sent By jpearson Date 2017-12-27 Time 07:53 Rev Time 0.00
Received By jpearson Date 2017-12-27 Time 07:52 Sent To  
Notes
2017-12-27 07:52:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSES
 SATISFACTORILY EXCEPT NUMBER 3 SHOWN BELOW. THE PERMIT
 APPLICATION WAS SUBMITTED DURING THE TIME THAT THE 2014
 FLORIDA BUILDING CODE IS IN EFFECT, WHICH REFERENCES
 THE 2011 NEC. PROVIDE CORRECTION TO SHOW THE DESIGN IS
 TO THE 2011 NEC.
  
 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION
 SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD
 INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC
 PREFACE, NEC 517.13
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By jpearson Date 2017-09-13 Time 11:21 Rev Time 0.00
Received By jpearson Date 2017-09-13 Time 11:21 Sent To  
Notes
2017-09-13 11:21:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANELS TO CONFIRM AIC RATING IS
 ADEQUATE. NEC 110.10
 2. PROVIDE A BLOCK NOTE WHERE APPLICABLE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR LOW VOLTAGE SYSTEMS, FIRE ALARM, CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, WALK-IN COOLERS,
 HOODS, ETC. FBC 105.1
 3. NOTE 1 ON SHEET E-1 STATES ELECTRICAL INSTALLATION
 SHALL BE PER 2014 NEC, WHICH IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. AREAS COVERED BY NEC 517.13 SHOULD
 INCLUDE CONSULTATION AND OBSERVATION ROOMS. FBC
 PREFACE, NEC 517.13
 4. NOTE 4 ON SHEET E-1 STATES THAT ISOLATED GROUND
 RECEPTACLES SHOULD BE USED. NEC 517.16 PROHIBITS THE
 USE OF IG RECEPTACLES. PROVIDE CORRECTION. NEC 517.16
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1. CODE REQUIRES CONTROL AS
 FOLLOWS: AT LEAST 50% OF ALL 125-VOLT 15 AND 20 AMP
 RECEPTACLES IN ALL PRIVATE OFFICES, CONFERENCE ROOMS,
 ROOMS USED PRIMARILY FOR PRINTING AND/OR COPYING
 FUNCTIONS, BREAK ROOMS, CLASSROOMS, AND INDIVIDUAL
 WORKSTATIONS.
 6. IF OCCUPANCY IS CLASSIFIED AS AMBULATORY CARE
 FACILITY PER THE BUILDING COMMENTS, PROVIDE ALTERNATE
 POWER SOURCE REQUIRED. NEC 517.45
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-01-24 Cont ID  
Sent By pleduc Date 2018-01-24 Time   Rev Time 0.00
Received By pleduc Date 2018-01-24 Time 11:01 Sent To  
Notes
2018-01-24 13:50:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL EACH BE DONE UNDER SEPARATE SHOP DRAWINGS
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-12-12 Cont ID  
Sent By wjolin Date 2017-12-12 Time 14:10 Rev Time 0.00
Received By wjolin Date 2017-12-12 Time 14:01 Sent To  
Notes
2017-12-12 14:10:10400 SOUTH AUSTRALIAN AVENUE - 6TH FLOOR
 PERMIT #17080529
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT - NO DRAWINGS SUBMITTED. ENGINEERED FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE OF A GENERAL
 BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 REPEAT COMMENT - NO DRAWINGS SUBMITTED. ENGINEERED FIRE
 ALARM CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A GENERAL
 BUILDING PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-08-18 Cont ID  
Sent By wjolin Date 2017-08-18 Time 14:27 Rev Time 0.00
Received By wjolin Date 2017-08-18 Time 14:27 Sent To  
Notes
2017-08-18 14:27:16400 SOUTH AUSTRALIAN AVENUE - 6TH FLOOR
 PERMIT #17080529
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE OCCUPANCY IS INDICATED AS BUSINESS; HOWEVER,
 AMUBLATORY HEALTH CARE APPEARS TO BE MORE APPROPRIATE
 PER THE FLORIDA FIRE PREVENTION CODE. FOUR OR MORE
 PATIENTS UNDER THE INFLUENCE OF SEDATIVES WOULD CHANGE
 THE OCCUPANCY FROM BUSINESS TO AMBULATORY CAR. THIS IS
 SUPPORTED BY NFPA 101 HANDBOOK STATING, "A DENTIST
 ADMINISTERS GENERAL ANESTHESIA TO
 NOT MORE THAN THREE PATIENTS SIMULTANEOUSLY, THE
 DENTIST?S OFFICE WOULD BE CLASSIFIED AS A BUSINESS
 OCCUPANCY. IF THE DENTIST EXPANDS THE SIMULTANEOUS
 ADMINISTRATION OF GENERAL ANESTHESIA TO A FOURTH
 PATIENT, THEN THE MORE STRINGENT REQUIREMENTS FOR
 AMBULATORY HEALTH CARE OCCUPANCIES WOULD APPLY."
 AMBULATORY HEALTH CARE OCCUPANCY: AN OCCUPANCY USED TO
 PROVIDE SERVICES OR TREATMENT SIMULTANEOUSLY TO FOUR OR
 MORE PATIENTS THAT PROVIDES, ON AN OUTPATIENT BASIS,
 ONE OR MORE OF THE FOLLOWING: (1) TREATMENT FOR
 PATIENTS THAT RENDERS THE PATIENTS INCAPABLE OF TAKING
 ACTION FOR SELFPRESERVATION UNDER EMERGENCY CONDITIONS
 WITHOUT THE ASSISTANCE OF OTHERS.
  
 SHEET E-2: AN ADDITIONAL EXIT SIGN IS NEEDED ON THE
 OTHER SIDE OF CORRIDOR DOOR #605.
  
 SHEET M101: EXHAUST FAN 1 & 2 APPEAR TO BE DISCHARGING
 INTO THE EXIT STAIR VESTIBULE.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 ENGINEERED FIRE ALARM CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. PER FBC SECTION
 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-02-08 Time   Rev Time 0.00
Received By cpuell Date 2018-01-18 Time 17:43 Sent To  
Notes
2018-01-22 17:44:41C25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-05 Cont ID  
Sent By gjohnson Date 2018-01-05 Time 12:18 Rev Time 0.00
Received By gjohnson Date 2017-12-01 Time 14:50 Sent To  
Notes
2017-12-04 14:50:33C17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-10-18 Cont ID  
Sent By tklarge Date 2017-10-18 Time 09:02 Rev Time 0.00
Received By tklarge Date 2017-08-10 Time 14:17 Sent To  
Notes
2017-08-14 14:17:39C17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-02-08 Cont ID  
Sent By ccole Date 2018-02-08 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-02-07 Time 07:16 Sent To I
Notes
2018-02-08 16:17:04MECHANICAL PROVISO:
  
 A REVISION TO THE PLANS IS REQUIRE TO PROVIDE A
 HAZARDOUS EXHAUST SYSTEM FOR THE LAB ROOMS.
 THE REVISION SHALL BE SUBMITTED AND APPROVED PRIOR TO
 1ST INSPECTION.
  
 CCOLE-2/8/18
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-12-20 Cont ID  
Sent By ccole Date 2017-12-20 Time 16:43 Rev Time 0.00
Received By ccole Date 2017-12-20 Time 15:06 Sent To  
Notes
2017-12-20 16:45:572ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17080529
 12/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO COMMENT #2 FROM THE 1ST REVIEW, THE
 ARCHITECT IS STATING IN THE RESPONSE NARRATIVE THAT THE
 LAB ROOMS IN THE TENANT SPACE DO NOT HAVE TO MEET THE
 REQUIREMENTS OF TABLE 403.3. PLEASE SEE SECTION 403.3
 WHICH STATES: "VENTILATION RATES FOR OCCUPANCIES NOT
 REPRESENTED IN TABLE 403.3 SHALL BE THOSE FOR A LISTED
 OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN TERMS
  
 OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS". ALTHOUGH LABS ARE NOT LISTED
 UNDER OFFICE OCCUPANCY, THEY ARE LISTED UNDER EDUCATION
 WHICH IS THE MOST SIMILAR OCCUPANCY SHOWN IN THE TABLE.
 PLEASE NOTE THAT THE EXISTENCE OF A LAB AS AN ACCESSORY
 SPACE IN A BUSINESS OCCUPANCY IS NOT PROHIBITED BY THE
 CODE-
  
 SEE SECTION 508 FBC-14 BUILDING. REVISE THE PLANS TO
 SHOW THE REQUIRED EXHAUST SYSTEMS, AND PROVIDE A
 NARRATIVE THAT DETAILS THE PROCEDURES THAT ARE
 PERFORMED IN THE LABS, AND WHAT EQUIPMENT AND MATERIALS
 ARE USED IN THOSE PROCEDURES. REFER TO TABLE 403.3 FOR
 LAB VENTILATION RATES- 10 CFM FOR OCCUPANTS PLUS 0.18
 CFMS PER SQ. FT. AND 1.0 CFM EXHAUST AIRFLOW RATE.
 PLEASE REVISE
  
 THE VENTILATION SCHEDULE ON SHEET MP001.
  
 2) IN RESPONSE TO COMMENT #5 FROM THE 1ST REVIEW
 CONCERNING THE RESTROOM AND GAS STORAGE ROOM EXHAUST,
 THE ARCHITECT IS STATING THAT THE GAS EXHAUST FAN
 (EF-2) IS DISCHARGING TO THE OUTDOORS, HOWEVER THE PLAN
 APPEARS TO STILL INDICATE THE EF-2 FAN ON THE INTERIOR
 WALL OF THE VESTIBULE. USING OUR GIS PROGRAM I HAVE
 LOOKED AT ACTUAL PHOTOS OF THE BUILDING AND I AM NOT
 SEEING HOW
  
 THE FAN LOCATED AS SHOWN ON THE PLAN IS ON AN EXTERIOR
 WALL. FURTHER, IF THIS FAN WAS LOCATED ON AN EXTERIOR
 WALL AT THE 6TH FLOOR LEVEL, HOW WOULD ACCESS BE
 PROVIDED TO SERVICE THE FAN AS REQUIRED BY CODE SECTION
 306.1. ADDITIONALLY PLEASE NOTE THE FAN WOULD HAVE TO
 BE WIND RESISTANT AND PROTECTED FROM IMPACT PER SECTION
 1609 FBC-14 BUILDING AND RULE 9N-3 FAC. CONCERNING
  
 THE LOCATION OF THE RESTOOM EXHAUST DISCHARGE, THE
 REVISED PLAN IS SHOWING AN 18"X 30" EXHAUST GRILL
 LOCATED IN A SOFFIT. AGAIN, I HAVE LOOKED AT THE PHOTOS
 AND NOT SEEING HOW THIS INSTALLATION WOULD BE
 ACCOMPLISHED. PLEASE PROVIDE PLAN SECTIONS AND DETAILS
 TO CLEARLY SHOW EACH OF THESE NEW EXHAUST TERMINATIONS.
  
 3) COMMENT #11 FROM THE 1ST REVIEW PARTIALLY COMPLIED
 WITH. AC CALCULATIONS FOR WSHP'S 7, 8, 9, 10, 11 NOT
 PROVIDED. PLEASE ADD THE EFFICIENCY RATINGS (SEER) TO
 THE EQUIPMENT SCHEDULE ON SHEET M001.
  
 4) SHEET M101: SHOW HOW O/A IS BEING PROVIDED TO THE
 WSHP-11 SYSTEM.
  
 5) M201: IT APPEARS THAT CONDENSATE FROM THE HEAT PUMPS
 WILL BE DRAINING INTO THE CITY SANITARY SYSTEM WHICH IS
 PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-13 Cont ID  
Sent By ccole Date 2017-09-13 Time 17:46 Rev Time 0.00
Received By ccole Date 2017-09-13 Time 16:26 Sent To  
Notes
2017-09-13 17:56:491ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17080529
 9/13/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OCCUPANCY CLASSIFICATION OF BUSINESS ASSIGNED TO
 THE PROPOSED TENANT BUILD-OUT IS BEING QUESTIONED BY
 THE BUILDING AND FIRE DEPT. PLANS EXAMINERS. THE
 MECHANICAL PLANS AND SYSTEMS ARE BEING REVIEWED IN
 ACCORDANCE WITH THE FBC-14 MECHANICAL AND REFERENCED
 STANDARDS NFPA 99, AND ASHRAE 170- 2010. PLEASE NOTE
 THAT ADDITIONAL COMMENTS MAY OCCUR, OR
  
 COMMENTS MAY BE RETRACTED BASED ON THE DESIGN
 PROFESSIONALS CORRECTED PLANS AND RESPONSES.
  
 2) SHEET MP001: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE TECH LAB, DESIGN LAB, AND WET LAB
 IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
  
 3) MP001: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE DENTAL GAS STORAGE ROOM- SEE SECTION 502.9.1
 FBC-14 MECHANICAL. PLEASE NOTE THAT ADDITIONAL
 REQUIREMENTS FOR MEDICAL GAS EXHAUST SYSTEMS ARE FOUND
 IN SECTION 9.3.1.1 NFPA 99, AND SECTION 6 ASHRAE
 170-2010. PLEASE REFER TO SECTION 9.3.6.5.3.2 NFPA 99
 FOR EXHAUST VENTILATION RATE BASED ON THE QUANTITY OF
  
 GAS TO BE STORED.
  
 4) MP001: REFER TO TABLE 7-1 ASHRAE 170-2010 AND
 PROVIDE A DESIGN PARAMETER SCHEDULE ON THE PLAN FOR ALL
 ROOMS AND SPACES. THE SCHEDULE SHALL INDICATE PRESSURE
 RELATIONSHIPS TO ADJACENT AREAS, MINIMUM OUTDOOR ACH,
 TOTAL ACH ETC.
  
 5) M101: THE EXHAUST FROM EF-1 & EF-2 SHALL DISCHARGE
 TO THE EXTERIOR OF THE BUILDING PER SECTION 501.3
 FBC-14 MECHANICAL. IT APPEARS TO BE DISCHARGING INTO A
 STAIR VESTIBULE- SEE BUILDING AND FIRE COMMENTS.
  
 6) M101: IT APPEARS THAT MAKEUP AIR FOR THE EXHAUST IN
 THE STORAGE ROOM IS THROUGH A FIRE-DAMPERED OPENING
 INTO THE MECHANICAL ROOM. PLEASE SHOW COMPLIANCE WITH
 SECTIONS 5.1.3.3.1.5 NFPA 99 FOR ADJACENT ROOM
 COMMUNICATION RESTRICTIONS, AND 9.3.6.5.3.7 FOR MAKEUP
 AIR REQUIRERMENTS.
  
 7) M101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE FIRE
 DAMPER AND A SEQUENCE OF OPERATION. CLARIFY HOW WILL
 THIS DAMPER FUNCTION IN AN ALARM SITUATION.
  
 8) INDICATE THE TOTAL QUANTITIES OF NITROUS OXIDE AND
 OXYGEN TO BE STORED IN THE ROOM- SECTION 5.1.3.3.1.7
 NFPA 99. REFER TO SECTION 502.9.1 FBC-14 MECHANICAL:
 THE EXHAUST VENT FOR THE STORAGE ROOM MAY BE REQUIRED
 TO BE ENCLOSED IN A MINIMUM 1HR FIRE-RATED SHAFT
 ENCLOSURE FROM THE STORAGE ROOM TO THE EXTERIOR. NOTE 3
 ON SHEET M101 INDICATES THE DUCT IS TO BE WRAPPED WITH
  
 3M FIRE BARRIER WRAP. THE SPECIFICATIONS FOR THE FIRE
 WRAP MUST SHOW COMPATIBILTY FOR THIS TYPE OF SYSTEM
 APPLICATION, AND BE SUBMITTED FOR REVIEW WITH APPROVAL
 STAMPS BY THE ENGINEER OF RECORD.
  
 9) INDICATE HOW THE MED GAS TANKS WILL BE SECURED AND
 PROTECTED FORM DAMAGE- SECTION 5.1.3.3.2 NFPA 99.
  
 10) SHOW LOCATIONS OF RELIEF VALVES AND RELIEF PIPING
 VENTS IN THE STORAGE ROOM AND WHERE THE VENT PIPING IS
 TERMINATING- SECTION 5.1.3.3.3.2.
  
 11) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL THE MED
 GAS SYSTEM EQUIPMENT, THE COMPRESSOR, AND THE VACUUM
 WITH APPROVAL STAMPS BY THE EOR- SECTION 107.2.1 WPB
 AMENDMENTS.
  
 12) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE
 NEW WSHP SYSTEMS- SECTION 312.1. FBC-14 MECHANICAL.
  
 13) M101: A SMOKE DETECTOR IS REQUIRED IN THE
 MECHANICAL ROOM IN COMPLIANCE WITH SECTION 606.2.2
 FBC-14 MECHANICAL.
  
 14) M101: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 15) PROVIDE AIR BALANCE CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-23 Cont ID  
Sent By gjohnson Date 2018-01-23 Time 12:46 Rev Time 0.00
Received By gjohnson Date 2018-01-23 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-01-05 Cont ID  
Sent By gjohnson Date 2018-01-05 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2018-01-02 Time 14:52 Sent To  
Notes
2018-01-05 09:42:572ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED. TO
 EXPEDITE APPROVAL I SUGGEST A MEETING TO GO OVER
 COMMENTS SEE MY CONNECT INFO BELOW.
  
 PARTIALLY COMPLIED 3) INDICATE HOW THE MED GAS TANKS
 WILL BE SECURED AND PROTECTED FORM DAMAGE- SECTION
 5.1.3.3.2(7) NFPA 99. PLEASE PROVIDE MANUFACTURE
 SPECIFICATION SHEETS FOR CYLINDER BRACKETS AND A DETAIL
 SHOWING HOW THEY WILL BE SECURED TO THE WALL . PER WPB
 AMEND TO FBC 107.2.1
  
 PARTIALLY COMPLIED 16) SHT. A1.6 - CLARIFY THE ACRONYMS
 "LDV" AND "HDV" ON THE VACUUM SYSTEM. IS THE LOW DUTY
 AND HIGH DUTY THE SAME AS LOW PERSSURE AND HIGH
 PRESSURE PLEASE CLARIFY ON PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 PARTIALLY COMPLIED 17) SHT. A1.7 - SUBMIT A MINIMUM OF
 TWO COPIES OF THE MANUFACTURER'S PRE-INSTALLATION GUIDE
 FOR THE VACUUM PIPING SYSTEM TO BE PROVIDED BY A HENRY
 SCHEIN EQUIPMENT SALES SPECIALIST AS REFERENCED IN THE
 FIRST NOTE IN THE VACUUM SYSTEM NOTES ON THIS DRAWING
 PAGE. WPB AMEND. TO FBC SEC.107.2.1. NO SPECS PROVIDED.
 PLEASE SPECIFY ON PLAN EXACTLY WHAT TYPE OF PIPE AND
 FITTINGS WILL BE USED FOR VACUUM SYSTEM. RIGHT NOW IT
 SAYS USE PVC , EXPERT WHERE PROHIBITED, THE CEILING IS
 INDICATED AS AN AIR PLENUM, CLARIFY ONE TYPE OF PIPE.
 PER WPB AMEND TO FBC 107.2.1
  
 PARTIALLY COMPLIED 25) A BACKFLOW PREVENTER IS REQUIRED
 ON THE WATER SUPPLY AT THE BEVERAGE COUNTER AND ICE
 MAKER. 2014 FBC-PLUMBING SEC.608.16.10. SHOW ON RISER
 DIAGRAM AND PROVIDE SCHEDULE FOR BACFLOW DEVISE AND AIR
 HAMMER ARRESTORS. PER WPB AMEND TO FBC 107.2.1
  
 PARTIALLY COMPLIED 26) A WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED ON THE WATER
 DISTRIBUTION SYSTEM.2014 FBC-PLUMBING SEC. 604.9. SHOW
 ON RISER DIAGRAM AND PROVIDE SCHEDULE FOR BACFLOW
 DEVISE AND AIR HAMMER ARRESTORS. PER WPB AMEND TO FBC
 107.2.1
  
 PARTIALLY COMPLIED 27) SHT. P001 - NOTE #16 REFERS TO
 SHT. A1.6 FOR A DETAIL OF A SEDIMENT TRAP. THERE IS NO
 DETAIL ON SHT. A1.6. PLAN SHOWS PT MANUFACTURE SPECS
 SHOWS BT PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PARTIALLY COMPLIED 29) THE HOT WATER RECIRCULATION
 SYSTEM SHALL COMPLY WITH THE 2014 FBC-PLUMBING
 SEC.607.5 FOR THE REQUIRED PIPE INSULATION. PLACE NOTE
 ON PLUMBING SHEETS REFERRING TO MECHANICAL SPEC-AND
 SHEET NUMBER. PER WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. SHT. P003 SHOWS 2 TYPE "N" TANKS, 114 LB AND 200CF.
 SHT. P301 NOTE #11 SHOWS 2 TYPE "G" TANKS OX.@ 251CF,
 21LB AND NO.@ 498CF, 57LB PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 2. SHT. P301 THE EXHAUSTS FROM A VACUUM PUMP SERVING A
 VACUUM (FLUID SUCTION) SYSTEM SHALL DISCHARGE
 SEPARATELY TO OPEN AIR ABOVE THE ROOF. PER FBC PL 713.6
  
 3. SHT.P301 NOTE #10 IS NOT SHOWN ON THE FLOOR PLAN
 PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. P201 # 9+10 ARE SHOWN ON FLOOR PLAN BUT THERE
 NOT SHOWN ON THE NOTES PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 5. SHT. P201 WHAT IS #7 ON THE FLOOR PLAN IT DOES NOT
 MATCH THE NOTE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. THE WASHING MACHINE SHALL HAVE A 3" BRANCH DRAIN.
 PER FBC PL 406.2
  
 7. THE WASHING MACHINE SHALL DISCHARGE THROUGH A LINT
 TRAP. PER FBC PL 1003.6
  
 8. THE DRAIN FROM THE VACUUM PUMP TANKS SHALL CONNECT
 DIRECTLY TO THE SANITARY SYSTEM NO INDIRECT WASTE.
 PROVIDE DETAIL FOR DRAINAGE CONNECTION OF VACUUM
 SYSTEM. PER FBC PL 713.7 AND WPB AMEND TO FBC 107.2.1
  
 9. THE FLOOR DRAINS AND FLOOR SINK ARE REQUIRED TO HAVE
 TRAP PRIMER VALVES. PER FBC PL 1002.4
  
 10. SHT. P001 IN THE SCHEDULE GT-1 IS NOT SHOWN ON PLAN
 WHAT IS THIS USED FOR PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 11. SHT. P101 NOTE #3 THE 2" HUB DRAIN FOR THE VISTA
 FILTER SYSTEM IS NOT SHOWN ON THE RISER DIAGRAM NEITHER
 IS THE TRAP FOR THE VACUUM SYSTEM DRAIN. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P003 ON THE MED GAS RISER IT SHOWS A HIGH
 PRESSURE VACUUM PUMP PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 13. SHT. A1.7 ON THE SCHEDULE IT SHOWS 13, 13A, 13B,
 13C, AND 15A CONNECTING TO NATURAL GAS WHICH STATES NOT
 USED. PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 14. SHT. A1.7 PLEASE PROVIDE DRAWINGS BY HENRY SCHIEN
 OR REMOVE NOTE FROM PLAN. PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-10-18 Cont ID  
Sent By tklarge Date 2017-10-18 Time 09:02 Rev Time 0.00
Received By tklarge Date 2017-09-20 Time 10:02 Sent To  
Notes
2017-10-12 05:36:151) THE OCCUPANCY CLASSIFICATION OF BUSINESS ASSIGNED TO
 THE PROPOSED TENANT BUILD-OUT IS BEING QUESTIONED BY
 THE BUILDING AND FIRE DEPT. PLANS EXAMINERS. PLEASE
 NOTE THAT ADDITIONAL COMMENTS MAY OCCUR, OR
 COMMENTS MAY BE RETRACTED BASED ON THE DESIGN
 PROFESSIONALS CORRECTED PLANS AND RESPONSES.
 2) SHT. P301 - PROVIDE THE QUANTITY OF EACH CYLINDER OF
 EACH GAS AND THE CAPACITY OF EACH CYLINDER IN CUBIC
 FEET,
 3) INDICATE HOW THE MED GAS TANKS WILL BE SECURED AND
 PROTECTED FORM DAMAGE- SECTION 5.1.3.3.2 NFPA 99.
 4) SHOW LOCATIONS OF RELIEF VALVES AND RELIEF PIPING
 VENTS IN THE STORAGE ROOM AND WHERE THE VENT PIPING IS
 TERMINATING- NFPA 99 SECTION 5.1.3.3.3..
 5) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL THE
 MEDICAL GAS SYSTEM EQUIPMENT, THE AIR COMPRESSOR, AND
 THE VACUUM PUMP WITH APPROVAL STAMPS BY THE EOR-
 SECTION 107.2.1 WPB AMENDMENTS.
 6) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 BOTTLED WATER DISPENSING STATION. THIS MAY HAVE TO
 COMPLY WITH THE 2014 FBC-ACCESSIBILITY CODE.
 7) THE ARCHITECT'S SEAL AND SIGNATURE ON THE DEMO AND
 ARCHITECTURAL PAGES APPEAR TO BE A COPY OF AN ORIGINAL
 SEAL AND SIGNATURE. COMPLY WITH F.A.C. 61G1-16.001.
 8) SUBMIT A PIPING RISER DIAGRAM FOR THE WATER PIPING
 SYSTEM(S) INCLUDING ANY WATER FILTRATION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 9) SUBMIT A PIPING RISER DIAGRAM FOR THE ENTIRE MEDICAL
 GAS SYSTEM ( OXYGEN, NITROUS OXIDE) AND THE AIR AND
 VACUUM SYSTEM.WPB AMEND. TO FBC SEC. 107.3.5.1.3. THE
 MEDICAL GAS, AIR AND VACUUM SYSTEMS SHALL COMPLY WITH
 NFPA 99-12.
 10) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE EMERGENCY EYE WASH UNITS.THE
 EYEWASH STATION SHALL COMPLY WITH 2014 FBC-PLUMBING
 SEC.411.1 AND ISEA Z358.1. TEMPERED WATER SHALL BE
 SUPPLIED TO THE EYEWASH. 2014 FBC-PLUMBING SEC.607.1.
 11) *** SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION MANUAL FOR THE AIR
 COMPRESSOR AND VACUUM PUMPS.THIS EQUIPMENT SHALL COMPLY
 WITH THE REQUIREMENTS OF NFPA 99, SECS.
 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE STERILIZATION CABINET. WPB
 AMEND. TO FBC SEC. 107.2.1.
 13) SHT.A3.9 - DETAIL # 2 - PROVIDE AN EXPANDED DETAIL
 OF THE VISTA CLEAR CABINET.THE DETAIL AND THE PRINT IS
 SMALL AND VERY HARD TO READ. WPB AMEND. TO FBC SEC.
 107.2.1.ALSO, SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THIS CABINET.
 14) PROVIDE TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION MANUALS FOR THE DENTAL
 CHAIRS. WPB AMEND. TO FBC SEC. 107.2.1.
 15) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS & INSTALLATION MANUALS FOR ALL DENTAL
 EQUIPMENT THAT EMPLOYS A WATER OR DRAIN CONNECTION TO
 THE APPLIANCE/EQUIPMENT.WPB AMEND. TO FBC SEC. 107.2.1.
 16) SHT. A1.6 - CLARIFY THE ACRONYMNS "LDV" AND "HDV"
 ON THE VACUUM SYSTEM.
 17) SHT. A1.7 - SUBMIT A MINIMUM OF TWO COPIES OF THE
 MANUFACTURER'S PRE-INSTALLATION GUIDE FOR THE VACUUM
 PIPING SYSTEM TO BE PROVIDED BY A HENRY SCHEIN
 EQUIPMENT SALES SPECIALIST AS REFERENCED IN THE FIRST
 NOTE IN THE VACUUM SYSTEM NOTES ON THIS DRAWING PAGE.
 WPB AMEND. TO FBC SEC.107.2.1.
 18) SUBMIT TWO COPIES OF THE MEDICAL GAS SYSTEM
 DRAWINGS FROM HENRY SCHEIN.THESE DRAWINGS ARE REQUIRED
 TO BEAR THE SEAL AND SIGNATURE OF AN ENGINEER LICENSED
 IN THE STATE OF FLORIDA PER THE WPB AMEND. TO THE FBC
 SEC.105.3.1.2 (3), F.S. 471.
 19) SHT.A2.4 - DETAIL # 2 - THE SPACING OF THE GRAB BAR
 BEHIND THE WATER CLOSET SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SEC. 604.5.2.IF THE GRAB IS LOCATED A
 MAXIMUM OF ONE FOOT FROM THE SIDE WALL, THEN THERE WILL
 NOT BE THE REQUIRED MINIMUM OF 12 INCHES EXTENDING FROM
 THE CENTERLINE OF THE WATER CLOSET ON ONE SIDE. THE
 USUAL MAXIMUM DDISTANCE IS 6 INCHES. CLARIFY. SHOW THE
 RREQUIRED 12 INCHES AND 24 INCHES ON THE DETAIL.
 20) SHT. A3.3 - FIVE PERCENT OR A MINIMUM OF ONE OF THE
 SINKS IN THE DUAL USE ROOMS SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SECS.212.3 & 606.
 21) SHT. A2.4 - DETAILS #3, #5 & #8 SHOW A VERTICAL
 GRAB BAR.ALTHOUGH THIS IS NOT A REQUIRED GRAB BAR, THE
 2014 FBC- ACCESSIBILITY SEC.609.4 REQUIRES GRAB BARS TO
 BE INSTALLED IN A HORIZONTAL POSITION. CLARIFY.
 22) SHT. A2.4 - DETAIL #4 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES (LXW) FOR THE LAVATORY AND
 WATER CLOSET ON THE PLANS. COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.604.3 & 606.2.
 24) STERILIZATION APPARTUS, WATER FILTERS, TANKS AND
 OTHER APPLIANCES THAT HANDLE OR TREAT POTABLE WATER
 SHALL BE PROTECTED AGAINST CONTAMINATION PER 2014
 FBC-PLUMBING SEC.608.3, 608.3.1. A BACKFLOW PREVENTER
 IS REQUIRED ON THESE TYPES OF EQUIPMENT.
 25) A BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 SUPPLY AT THE BEVERAGE COUNTER AND ICE MAKER. 2014
 FBC-PLUMBING SEC.608.16.10.
 26) A WATER HAMMER ARRESTOR CONFORMING TO ASSE 1010
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED ON THE WATER DISTRIBUTION SYSTEM.2014
 FBC-PLUMBING SEC. 604.9.
 27) SHT. P001 - NOTE #16 REFERS TO SHT. A1.6 FOR A
 DETAIL OF A SEDIMENT TRAP. THERE IS NO DETAIL ON SHT.
 A1.6. CLARIFY.
 28) SHT. E-3 NOTES THE ELECTRIC WATER HEATER AS 30
 GALLONS AND SHT. P001 NOTES THE WATER HEATER AS 65
 GALLONS. CLARIFY.
 29) THE HOT WATER RECIRCULATION SYSTEM SHALL COMPLY
 WITH THE 2014 FBC-PLUMBING SEC.607.5 FOR THE REQUIRED
 PIPE INSULATION.
 30) SHT. P002 - BOTTOM FED WATER HEATERS SHALL BE
 EQUIPPED WWITH A VACUUM RELIEF VALVE PER 2014
 FBC-PLUMBING SEC. 504.2.
 31) SHT. P201 - NOTE #1 INDICATES A NEW 1 1/2 " COLD
 WATER CONNECTION TO AN EXISTING 1 1/4 " COLD WATER
 LINE. SUBMIT VERIFICATION THAT THE EXISTING 1 1/4"
 CCOLD WATER LINE WILL SUPPLY THE REQUIRED FLOW AND
 PRESSURES FOR THIS SYSTEM. 2014 FBC-PLUMBING
 SEC.604.3.**
 **NOTE** - ADDITIONAL REVIEW COMMENTS MAY BE GENERATED
 UPON RESUBMITTAL AND RE-REVIEW OF THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved