Plan Review Details - Permit 17080496
Plan Review Stops For Permit 17080496
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-02-22 Cont ID  
Sent By jwitmer Date 2018-02-22 Time 08:23 Rev Time 0.00
Received By jwitmer Date 2018-02-22 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-12-18 Cont ID  
Sent By jwitmer Date 2017-12-18 Time   Rev Time  
Received By jwitmer Date 2017-12-18 Time 09:01 Sent To  
Notes
2017-12-18 14:45:572014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17080496 POOL
 W. P. B. PRIME : 16040755 STRUCTURAL./ 16070715 25
 STORY MIXED USE
 ADD: 214 S. ROSEMARY AVE.
 CONT: CERTIFIED POOLS MECHANICS 1, INC.
 TEL: 239-292-9096 / ANDREA CASTRO
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MONDAY, DECEMBER 18, 2017
 ACTION: DENIED
  
 1) PLEASE NOTE THE ORIGINAL PERMIT APPLICATION DOES NOT
 HAVE EITHER OF THE OWNERS SIGNATURE (NOTARIZED) NOR THE
 CONTRACTOR SIGNATURE (NOTARIZED).
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 105.3 APPLICATION FOR PERMIT. TO OBTAIN
 A PERMIT, THE APPLICANT SHALL FIRST FILE AN APPLICATION
 THEREFORE IN WRITING ON A FORM FURNISHED BY THE
 DEPARTMENT FOR THAT PURPOSE.
  
 2) THE COVERSHEET HAS 4 REQUEST AS PART OF THEIR
 APPROVAL. ONE IS THAT OF THE STRUCTURAL ENGINEER TO
 REVIEW THE SUBMITTED PLANS AND APPLY THEIR SHOP DRAWING
 STAMP OF APPROVAL.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER (POOL
 ENGINEER) SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 3) SHEET 011_A312 LEVEL 12 AMENITY, SHEET 008_A100 SITE
 PLAN, PROJECT INFORMATION, OR NON OF THE POOL PLANS
 SUBMITTED SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE FOR POOL LIFTS REQUIRED BY
 SECTION 1009.2 OR SLOPED ENTRIES REQUIRED BY THE
 ACCESSIBILITY CODE SECTION 1009.3. THE POOL PLANS DOES
 NOT STATE IF THE AMENITIES DECK IS COVERED UNDER THE
 2014 ACCESSIBILITY CODE OR IF THE POOL DECK IS TO BE
 COVERED UNDER FAIR HOUSING ONLY.
 PLEASE REVIEW THE FLORIDA BUILDING COMMISSION
 DECLARATORY STATEMENT DS 2013-011. FLORIDA DECLARATORY
 STATEMENT 2013-011COMMUNITIY POOLS THAT ARE ASSOCIATED
 WITH A PRIVATE RESIDENTIAL COMMUNITY AND ARE LIMITED TO
 THE EXCLUSIVE USE OF RESIDENTS AND THEIR GUESTS ARE NOT
 COVERED BY THE ADA ACCESSIBILITY REQUIREMENTS, ON THE
 OTHER HAND, IF A SWIMMING POOL/ CLUB LOCATED IN A
 RESIDENTIAL COMMUNITY IS MADE AVAILABLE TO THE PUBLIC
 FOR RENTAL USE, IT IS COVERED UNDER TITLE III OF THE
 ADA. IF A COMMUNITY POOL IS OWNED OR OPERATED BY A
 STATE OR LOCAL GOVERNMENT ENTITY, IT IS COVERED BY
 TITLE II OF THE ADA, WHICH REQUIRES PROGRAM
 ACCESSIBILITY.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-03-06 Cont ID  
Sent By jpearson Date 2018-03-06 Time 09:47 Rev Time 0.00
Received By jpearson Date 2018-03-06 Time 09:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-12-27 Cont ID  
Sent By jpearson Date 2017-12-27 Time 11:06 Rev Time 0.00
Received By jpearson Date 2017-12-27 Time 11:06 Sent To  
Notes
2017-12-27 11:06:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THIS APPLICATION IS FOR THE POOL, HOWEVER, I DO NOT
 SEE ELECTRICAL PLANS FOR THE POOL OR POOL EQUIPMENT.
 THE PLAN PROVIDED APPEARS TO BE REVISIONS TO THE
 DIFFERENT LEVELS, WHICH SHOULD BE SUBMITTED AS A
 REVISION. PROVIDE POOL ELECTRICAL PLAN FOR REVIEW,
 SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. FS
 481.229; FBC 107.2.1, 107.3.5
 2. NO VALUE IS LISTED ON PERMIT APPLICATION. THE VALUE
 OF A POOL IS NOT INCLUDED IN THE MASTER PERMIT. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-12-08 Cont ID  
Sent By pleduc Date 2017-12-08 Time   Rev Time 0.00
Received By pleduc Date 2017-12-08 Time 15:09 Sent To  
Notes
2017-12-08 15:33:00THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) POOL CHEMICALS SHALL BE STORED PER MANUFACTURES
 REQUIERMENTS AND PER HAZARD SEPARATION AND QUANITITY
 STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By tklarge Date 2018-01-25 Time 06:46 Rev Time 0.00
Received By tklarge Date 2018-01-25 Time 06:46 Sent To  
Notes
2018-01-25 06:47:27A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT
 REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB
 AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-03-12 Cont ID  
Sent By lmarchan Date 2018-03-12 Time 09:43 Rev Time 0.00
Received By lmarchan Date 2018-02-16 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-01-25 Cont ID  
Sent By lmarchan Date 2018-01-25 Time 14:22 Rev Time 0.00
Received By lmarchan Date 2017-12-07 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-03-12 Cont ID  
Sent By tklarge Date 2018-03-12 Time 06:55 Rev Time 0.00
Received By tklarge Date 2018-03-12 Time 05:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-01-25 Cont ID  
Sent By tklarge Date 2018-01-25 Time 14:01 Rev Time 0.00
Received By tklarge Date 2018-01-16 Time 06:17 Sent To  
Notes
2018-01-25 06:43:401) SUBMIT A COPY OF THE OPERATING PERMIT APPLICATION
 FROM THE DEPARTMENT OF HEALTH FOR THE POOL IN
 ACCORDANCE WITH FL. STATUTES 514.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN COVERS. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 POOL HEATERS. THE GAS HEATERS SHALL MEET THE
 REQUIREMENTS OF THE 2014 FBC-ENERGY SEC. C404.7.1 &
 TABLE C404.2.
 4) CP4.0 - SHOW THE DISTANCE FROM FINISH SLAB/DECK TO
 THE HEIGHT OF THE POOL CHAIN LEVER FOR THE SHOWER.THE
 MAXIMUM HEIGHT OF THE PULL LEVER MAY HAVE TO COMPLY
 WITH THE FAC.MAX. HEIGHT WOULD BE 48 INCHES ABOVE
 FINISH SLAB/DECK.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-01-25 Cont ID  
Sent By tklarge Date 2018-01-25 Time 14:20 Rev Time 0.00
Received By tklarge Date 2018-01-25 Time 14:20 Sent To  
Notes
2018-01-25 14:21:08SIGNATURE ON ALL SHEETS APPEAR TO BE VALID.T.LARGE

Review Stop Z ZONING
Rev No 1 Status N Date 2018-01-02 Cont ID  
Sent By AA Date 2018-01-02 Time 08:49 Rev Time 0.00
Received By aaponte Date 2018-01-02 Time 08:49 Sent To  
Notes
***NONE***