Plan Review Details - Permit 17080475
Plan Review Stops For Permit 17080475
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By rgathrig Date 2018-07-10 Time 11:19 Rev Time 0.00
Received By rgathrig Date 2018-07-10 Time 11:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-10-11 Cont ID  
Sent By shill Date 2017-10-11 Time 12:28 Rev Time 0.00
Received By shill Date 2017-10-11 Time 12:28 Sent To  
Notes
2017-10-11 12:28:33PASSED W/REDLINE RE: POCKET DOORS
 PROVISO - FLOORING UNDERLAYMENT TEST REPORTS TO BE
 SUBMITTED PRIOR TO INSTALLATION (STC, IIC, FLAME
 SPREAD)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-09-14 Cont ID  
Sent By jwitmer Date 2017-09-14 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2017-09-14 Time 08:12 Sent To  
Notes
2017-10-06 14:25:322014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080475
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 8C
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: THURSDAY SEPT. 14/2017 / FRI. OCT. 06/ 2017
 ACTION: DENIED
  
 1A) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN BOTH OF THESE DOORS AS SHOWN
 IN THE OPEN POSITION MEASURE 2.50 FT. FAIR HOUSING
 REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 FBC-
 ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN, PLEASE PROVIDE WHAT TYPE OF
 HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE
 FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE
 THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE MASTER BEDROOM CLOSETS, PLEASE PROVIDE
 WHAT TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET
 DOORS CANNOT BE FULLY RECESSED HARDWARE HAS TO BE
 ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO BEDROOM 2 & BEDROOM 3, PLEASE PROVIDE WHAT
 TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS
 CANNOT BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE
 FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1F) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1G) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS
 DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242-_15-A6-66-8C FLOOR FINISHES. BLDG TYPE:
 TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56B, A6.13B &
 A7.55B AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED
 REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE
 PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN
 THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2017-10-02 15:17:50W. P. B. REVISION: 17080125 CORRECTED NOTES!
 W. P. B. PERMIT: 15111020 NOT: 15050292/ FOUNDATION
 PERMIT
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 9B
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: MON. OCT. 02/2017
 ACTION: DENIED
  
 1) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B &
 U05B) LEADING INTO THE MASTER BATH HIS & HERS. THE
 DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT.
 FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014
 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).
  
 1B) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U04B &
 U05B) LEADING INTO THE MASTER BATHROOMS HIS & HER
 BATHROOMS. PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE
 INSTALLED ON THE POCKET DOORS CANNOT BE FULLY RECESSED
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W &
 U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. THE
 DOORS AS SHOWN IN THE OPEN POSITION MEASURE 2.50 FT.
 FAIR HOUSING REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014
 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).
  
 1D) SHEET 126-18-A2-90-9B SHOWS (2 POCKET DOORS U05W &
 U05V) LEADING INTO BOTH HIS AND HER MASTER CLOSETS. .
 PLEASE PROVIDE WHAT TYPE OF HANDLES WILL BE INSTALLED
 ON THE POCKET DOORS CANNOT BE FULLY RECESSED HARDWARE
 HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND
 MOBILITY. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-18-A2-90-9B PLEASE BE AWARE ALL OF THE
 EXTERIOR SLIDING GLASS DOORS WILL NEED TO MEET THE 32
 INCHES CLEAR AND THE HARDWARE HAS TO BE ACCESSIBLE FOR
 PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 208-18-A6-25-9B FLOOR FINISHES WOOD FLOORS AND
 TILE FLOORS. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2014)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 2D) THE PLAN DOES NOT SAY IF THE WOOD FLOORS ARE GOING
 TO HAVE AN UNDERLAYMENT ONLY. IF THE FLOORS ARE GOING
 TO USE WOOD SLEEPERS AND THEN COMPLIANCE WILL BE
 REQUIRED UNDER 2010 FBC-B:
 805.1.1 SUBFLOOR CONSTRUCTION.
 FLOOR SLEEPERS, BUCKS AND NAILING BLOCKS SHALL NOT BE
 CONSTRUCTED OF COMBUSTIBLE MATERIALS, UNLESS THE SPACE
 BETWEEN THE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY AND
 THE FLOORING IS EITHER SOLIDLY FILLED WITH
 NONCOMBUSTIBLE MATERIALS OR FIREBLOCKED IN ACCORDANCE
 WITH SECTION 718, AND PROVIDED THAT SUCH OPEN SPACES
 SHALL NOT EXTEND UNDER OR THROUGH PERMANENT PARTITIONS
 OR WALLS.
  
 805.1.2 WOOD FINISH FLOORING.
 WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED
 DIRECTLY TO THE EMBEDDED OR FIREBLOCKED WOOD SLEEPERS
 AND SHALL BE PERMITTED WHERE CEMENTED DIRECTLY TO THE
 TOP SURFACE OF FIRE-RESISTANCE-RATED FLOOR ASSEMBLIES
 OR DIRECTLY TO A WOOD SUBFLOOR ATTACHED TO SLEEPERS AS
 PROVIDED FOR IN SECTION 805.1.1.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56A, A6.13A &
 A7.55A WITH ADDED REFERENCED NOTES BUT THESE SHEETS ARE
 NOT IN THE PERMIT PACKAGE. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. SUBMIT IF THEY ARE PART OF THIS
 REVISION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2017-09-14 10:49:282014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 17080475
 W. P. B. PERMIT: 15111020
 ADD: 1100 S. FLAGLER DR. SUITE: UNIT 8C
 CONT: SUFFOLK
 TEL: 561-407-496-3168 ED HANRATTY
 E-MAIL: NO E-MAIL ADDRESS/ USING OLD FORM, NEW FORM HAS
 E-MAIL ADDRESS REQUIREMENTS,
 WE PREFER TO COMMUNICATE BY E-MAIL TO HAVE A WRITTEN
 RECORD.
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 SUBJECT TO FAIR HOUSING!
  
 1ST REVIEW
 DATE: THURSDAY SEPT. 14/2017
 ACTION: DENIED
  
 1A) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN BOTH OF THESE DOORS AS SHOWN
 IN THE OPEN POSITION MEASURE 2.50 FT. FAIR HOUSING
 REQUIRES A CLEAR WIDTH OF 32 INCHES. 2014 FBC-
 ACCESSIBILITY/ FAIR HOUSING SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE KITCHEN, PLEASE PROVIDE WHAT TYPE OF
 HANDLES WILL BE INSTALLED ON THE POCKET DOORS CANNOT BE
 FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE
 THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1C) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1B) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO THE MASTER BEDROOM CLOSETS, PLEASE PROVIDE
 WHAT TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET
 DOORS CANNOT BE FULLY RECESSED HARDWARE HAS TO BE
 ACCESSIBLE FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205(C)(2)(2).FIGURE 1( C ).
  
 1E) SHEET 126-15-A2-90-8C SHOWS (2) POCKET DOORS
 LEADING INTO BEDROOM 2 & BEDROOM 3, PLEASE PROVIDE WHAT
 TYPE OF HANDLES WILL BE INSTALLED ON THE POCKET DOORS
 CANNOT BE FULLY RECESSED HARDWARE HAS TO BE ACCESSIBLE
 FOR PEOPLE THAT HAVE LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 1F) SHEET 126-15-A2-90-8C SHOWS (4 POCKET DOORS LEADING
 INTO THE MASTER BEDROOM CLOSETS & HIS & HERS MASTER
 BATH ALL OF THESE DOORS AS SHOWN IN THE OPEN POSITION
 MEASURE 2.50 FT. FAIR HOUSING REQUIRES A CLEAR WIDTH OF
 32 INCHES. 2014 FBC- ACCESSIBILITY/ FAIR HOUSING
 SECTION 100.205.(C)(2)(2).
  
 1G) PLEASE BE AWARE ALL OF THE EXTERIOR SLIDING GLASS
 DOORS WILL NEED TO MEET THE 32 INCHES CLEAR AND THE
 HARDWARE HAS TO BE ACCESSIBLE FOR PEOPLE THAT HAVE
 LIMITED HAND MOBILITY.
 2014 FBC- ACCESSIBILITY/ FAIR HOUSING SECTION
 100.205.(C)(2)(2).FIGURE 1( C ).
  
 2) SHEET 242-_15-A6-66-8C FLOOR FINISHES. BLDG TYPE:
 TYPE I/ TYPE II FLOOR INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING OR
 PROVIDE TESTING FOR THE THICKNESS FOR THE SLAB AND IF
 THERE IS A DROP CEILING WITH OR WITHOUT INSULATION:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) THE NARRATIVE LIST SHEETS A0.01C, A2.56B, A6.13B &
 A7.55B AS CUSTOM UNIT SUPPLEMENTAL INDEX AND ADDED
 REFERENCE NOTES, BUT THESE SHEETS ARE NOT PART OF THE
 PLAN SET SUBMITTED? THEN WHY ARE THESE SHEETS LISTED IN
 THE INDEX FOR THIS UNIT? 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-09-15 Cont ID  
Sent By jleahy Date 2017-09-15 Time 14:50 Rev Time 0.00
Received By jleahy Date 2017-09-15 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-30 Cont ID  
Sent By pleduc Date 2017-08-30 Time   Rev Time 0.00
Received By pleduc Date 2017-08-30 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-27 Cont ID  
Sent By cpuell Date 2017-10-27 Time 10:05 Rev Time 0.00
Received By cpuell Date 2017-10-06 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-09-26 Cont ID  
Sent By cpuell Date 2017-09-26 Time 14:44 Rev Time 0.00
Received By cpuell Date 2017-08-28 Time 18:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-26 Cont ID  
Sent By ccole Date 2017-10-26 Time 14:26 Rev Time 0.00
Received By ccole Date 2017-10-23 Time 12:43 Sent To  
Notes
2017-10-26 14:26:41MECHANICAL PROVISO:
 PRIOR TO ISSUANCE OF CO, THE DESIGN PROFESSIONAL OF
 RECORD SHALL CERTIFY THE APPLICATION OF THE INTUMESCENT
 PAINT ON THE AC CLOSET DOORS.
 CCOLE- 10/26/17
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-09-18 Cont ID  
Sent By ccole Date 2017-09-18 Time 15:29 Rev Time 0.00
Received By ccole Date 2017-09-18 Time 15:16 Sent To  
Notes
2017-09-18 15:30:511ST REVIEW FBC-2010 MECHANICAL, WPB AMENDMENTS TO THE
 FBC.
 REVISION #17080495
 MASTER PERMIT #15111020
 THE BRISTOL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CLOSET DOORS UO5G & UO5K MUST BE
 NON-COMBUSTIBLE- SECTION 602.2.1. THE DOOR SCHEDULE ON
 THE MASTER SHEET A8.12 INDICATES WOOD DOORS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 COOKING APPLIANCE IN THE KITCHEN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTION 623.1- 623.5 FBC-10 FUEL
 GAS.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 EXHAUST VENTILATION HOOD AND EXHAUST DUCT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS WITH APPROVAL STAMP AND
 SIGNATURE BY THE EOR- SECTIONS 505.1 AND 505.2.
  
 4) SHEET M2.90- 8C: PLEASE LABEL THE ROOMS ON THE
 REVISED PLAN.
  
 5) SHOW THE LOCATIONS OF THE RETURN OPENINGS AT THE
 PERIMETER COVES AND PROVIDE A DETAIL. PLEASE NOTE THAT
 ALL AIR SUPPLIED TO A MASTER SUITE MUST BE RETURNED-
 SECTION 601.5 (3).
  
 6) PROVIDE SUBDUCT INSTALLATION DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-09-15 Cont ID  
Sent By gjohnson Date 2017-09-15 Time 17:23 Rev Time 0.00
Received By gjohnson Date 2017-09-15 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2017-10-27 Cont ID  
Sent By cpuell Date 2017-10-27 Time 10:05 Rev Time 0.00
Received By cpuell Date 2017-10-27 Time 10:05 Sent To  
Notes
2017-10-11 12:29:5410/11/17 A SHEETS OK (SH)
  
  
2017-09-18 15:31:45MECH DIG/SIG GOOD/CCOLE-9/18/17


Account Summary | Usage Policy | Privacy Policy