Plan Review Details - Permit 17080458
Plan Review Stops For Permit 17080458
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-09-05 Cont ID  
Sent By cthroop Date 2017-09-05 Time 16:08 Rev Time 0.00
Received By cthroop Date 2017-09-05 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-28 Cont ID  
Sent By cthroop Date 2017-08-28 Time 10:32 Rev Time 0.00
Received By cthroop Date 2017-08-28 Time 10:10 Sent To  
Notes
2017-08-28 10:50:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN CALCULATIONS SUBMITTED WITH CHRISTIAN
 LANGLEY'S COPIED SIGNATURE ARE NOT ACCEPTABLE.
 2. DIGITAL SIGNATURES ARE ONLY APPLICABLE WITH
 DIGITALLY SUBMITTED PLANS. THESE PLANS HAVE NOT BEEN
 DIGITALLY SUBMITTED FOR REVIEW.
 3. THE SUBMITTED DOCUMENTS WITH MR. LANGLEY'S SIGNATURE
 ARE A FACSIMILE AND CANNOT BE USED.
 4. PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 SEALS
 (1) ONLY THE FOLLOWING SEALS ARE AUTHORIZED TO BE USED
 PURSUANT TO FLORIDA STATUTES ? 471.025;
 (A) WET SEALS: A WET SEAL IS ANY SEAL PHYSICALLY
 APPLIED TO A PRINTED DOCUMENT CAPABLE OF LEAVING A
 PERMANENT INK REPRESENTATION OR OTHER FORM OF OPAQUE
 PERMANENT IMPRESSION ON THE PRINTED DOCUMENT THAT
 COMPLIES WITH SUBSECTION 61G15-23.002(2), F.A.C.;
 (B) EMBOSSING SEALS: AN EMBOSSING SEAL IS ANY SEAL
 PHYSICALLY APPLIED TO A PRINTED DOCUMENT CAPABLE OF
 LEAVING A PERMANENT CRIMPED REPRESENTATION OR OTHER
 FORM OF PERMANENT RAISED IMPRESSION ON THE PRINTED
 DOCUMENT THAT COMPLIES WITH SUBSECTION 61G15-23.002(2),
 F.A.C.; OR
 (C) DIGITALLY CREATED SEALS: A DIGITALLY CREATED SEAL
 IS ANY SEAL CREATED AS PART OF THE DOCUMENT AND NOT
 PHYSICALLY APPLIED THAT IS AN OPAQUE PERMANENT
 REPRESENTATION THAT COMPLIES WITH SUBSECTION
 61G15-23.002(2), F.A.C.
 (2) WET SEALS, EMBOSSING SEALS AND DIGITALLY CREATED
 SEALS SHALL BE A MINIMUM OF 1-7/8 INCHES IN DIAMETER
 AND SHALL BE OF A DESIGN SIMILAR TO THOSE SET FORTH IN
 SUBSECTIONS (A), (B) AND (C) BELOW.
 (A) THE SEAL MUST CONTAIN THE LICENSEE?S GIVEN NAME,
 THE LICENSEE?S LICENSE NUMBER IMMEDIATELY PRECEDED BY
 THE DESIGNATION ?NO?, THE WORDS ?PROFESSIONAL ENGINEER?
 AND THE WORDS ?STATE OF FLORIDA? SIMILAR TO THAT
 DEPICTED HERE:
 (B) IF THE SEAL IS FOR A TEMPORARY LICENSE IT MUST ALSO
 CONTAIN THE WORDS ?TEMPORARY LICENSE? AND THE DATE THAT
 THE LICENSE EXPIRES IN THE FORM OF ?MONTH ? DAY ? YEAR?
 IMMEDIATELY PRECEDED BY THE WORD ?EXPIRES? SIMILAR TO
 THAT DEPICTED HERE:
 (C) FOR PROFESSIONAL ENGINEERS WHO ARE IN GOOD STANDING
 UNDER BOTH CHAPTERS 471 AND 472, F.S., A SEAL SIMILAR
 TO THAT DEPICTED HERE MAY BE USED.
 (D) SEALS MAY CONTAIN AN ABBREVIATED FORM OF THE
 LICENSEE?S GIVEN NAME OR A COMBINATION OF INITIALS
 REPRESENTING THE LICENSEE?S GIVEN NAME PROVIDED THE
 SURNAME LISTED WITH THE BOARD APPEARS ON THE SEAL AND
 IN THE SIGNATURE.
 RULEMAKING AUTHORITY 471.025, 471.033(2) FS. LAW
 IMPLEMENTED 471.025, 471.033(1)(A) FS. HISTORY-NEW
 1-8-80, AMENDED 1-20-85, FORMERLY 21H-23.02, AMENDED
 5-14-86, FORMERLY 21H-23.002, AMENDED 11-15-94,
 8-18-98, 2-3-00, 2-22-01, 2-5-04, 1-31-08, 5-6-09,
 11-3-15.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF FLORIDA STATUTES ?
 471.025, AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By rmcdouga Date 2017-08-22 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2017-08-22 Time 18:35 Sent To  
Notes
2017-08-22 18:45:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESIGN CALCULATIONS AND DRAWINGS ARE REQUIRED TO
 HAVE THE FLORIDA ENGINEER'S SEAL AND ORIGINAL
 HANDWRITTEN SIGNATURE, COPIES OR OTHER FACSIMILES ARE
 NOT ACCEPTABLE. FAC 61G15 - 23.002 DIGITAL SIGNATURES
 ARE ONLY ACCEPTABLE FOR ELECTRONICALLY TRANSMITTED
 PLANS AND DOCUMENTS.
  
 2) THE VALUE FOR THIS WORK APPEARS LOW, SUBMIT A COPY
 OF THE SIGNED CONTRACT FOR THE SIGN AND THE
 INSTALLATION. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-09-05 Cont ID  
Sent By cthroop Date 2017-09-05 Time 16:08 Rev Time 0.00
Received By cthroop Date 2017-08-29 Time 11:23 Sent To  
Notes
2017-08-30 11:23:47RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-28 Cont ID  
Sent By cthroop Date 2017-08-28 Time 10:32 Rev Time 0.00
Received By cthroop Date 2017-08-23 Time 11:32 Sent To  
Notes
2017-08-24 11:32:20RESUB ROUTED TO KMARTIN VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-22 Cont ID  
Sent By rmcdouga Date 2017-08-22 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2017-08-09 Time 13:22 Sent To  
Notes
2017-08-10 13:22:34ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2017-08-31 Cont ID  
Sent By   Date 2017-08-31 Time   Rev Time 0.00
Received By kmartin Date 2017-08-31 Time 15:25 Sent To B
Notes
2017-08-30 15:42:11ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 2 Status P Date 2017-08-25 Cont ID  
Sent By   Date 2017-08-25 Time   Rev Time 0.00
Received By kmartin Date 2017-08-25 Time 10:57 Sent To B
Notes
2017-08-24 14:23:08ROUTED TO KEVIN MARTIN

Review Stop Z ZONING
Rev No 1 Status F Date 2017-08-22 Cont ID  
Sent By   Date 2017-08-22 Time   Rev Time 0.00
Received By kmartin Date 2017-08-22 Time 15:37 Sent To B
Notes
2017-08-22 15:38:25PLEASE PROVIDE LEGIBLE MEASUREMENTS ON SIGN DETAILS.
 FOR MORE INFORMATION, PLEASE CONTACT KEVIN MARTIN
 -URBAN DESIGN PLANNER AT [email protected].
2017-08-10 17:07:16ROUTED TO KEVIN MARTIN