Plan Review Details - Permit 17080255
Plan Review Stops For Permit 17080255
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-18 Cont ID  
Sent By tklarge Date 2017-08-18 Time 14:17 Rev Time 0.00
Received By tklarge Date 2017-08-17 Time 05:37 Sent To  
Notes
2017-08-16 15:02:53RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-08 Cont ID  
Sent By tklarge Date 2017-08-08 Time 03:06 Rev Time 0.00
Received By tklarge Date 2017-08-08 Time 02:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-18 Cont ID  
Sent By tklarge Date 2017-08-18 Time 14:17 Rev Time 0.00
Received By tklarge Date 2017-08-17 Time 05:56 Sent To  
Notes
2017-08-17 05:56:42APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-08 Cont ID  
Sent By tklarge Date 2017-08-08 Time 03:05 Rev Time 0.00
Received By tklarge Date 2017-08-08 Time 02:58 Sent To  
Notes
2017-08-08 03:05:54THE 975XL IS NOT A LEAD FREE DEVICE. BACKFLOW DEVICES
 SHALL BE LEAD FREE PER 2014 FBC-PLUMBING SEC.605.2.1
 AND THE CITY OF WPB CROSS - CONNECTION CONTROL MANUAL.
 THE SUBMITTED SPECIFICATION SHEET DOES NOT STATE THAT
 THE DEVICE IS LEAD FREE. SUBMIT TWO COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS SHOWING THAT THE DEVICE
 IS LEAD FREE.
 **NOTE** THE 975 XL2 IS A LEAD FREE DEVICE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  