Plan Review Details - Permit 17080211
Plan Review Stops For Permit 17080211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 18:43 Rev Time 0.00
Received By shill Date 2018-07-07 Time 18:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-09 Cont ID  
Sent By shill Date 2018-06-09 Time 19:24 Rev Time 0.00
Received By shill Date 2018-06-09 Time 19:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-14 Cont ID  
Sent By shill Date 2017-08-14 Time 16:17 Rev Time 0.00
Received By shill Date 2017-08-14 Time 15:53 Sent To  
Notes
2017-08-14 16:17:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLAN LACKS A SIGNIFICANT AMOUNT OF INFORMATION SUCH
 AS OCCUPANCY CLASSIFICATION, LIFE SAFETY PLAN (TRAVEL
 DISTANCES, EXITS, COMMON PATH OF TRAVEL, ETC.),
 OCCUPANT LOAD, COMPLIANCE WITH FBC ACCESSIBILITY. AS A
 BUILDING PLAN WAS NOT PROVIDED, A COMPLETE REVIEW
 CANNOT BE DONE AT THIS TIME. SOME INFORMATION ON THE
 PLAN IS NOT CLEAR.
  
 FOR INSTANCE, GENERAL NOTES STATES THAT OCCUPANCY TYPE
 IS R1, BUT APPLICATION STATES A HAIR SALON IS PROPOSED.
 IS THIS A CHANGE OF OCCUPANCY?
  
 SOME NOTES ARE NOT CLEAR AS TO MEANING; "ALL CONTRACTOR
 TREAD, SHALL PROVIDE THEIR INFORMATION AND SIGN THEIR
 DRAWING."
  
 FBC 107, PROVIDE AN ARCHITECTURAL QUALITY PLAN PREPARED
 BY A LICENSED DESIGN PROFESSIONAL, FS 471, 481. AN
 ELECTRICAL CONTRACTOR DESIGNED THE ELECTRICAL PORTION,
 A PLUMBING CONTRACTOR (PARTIALLY) DESIGNED THE PLUMBING
 PORTION (BUT NO ACCESSIBILITY INFORMATION PROVIDED).
 SOMETHING WHICH IS LABELED "WALL DETAIL DNS" IS ON THE
 PLAN BUT NOT CLEAR WHETHER THE PLUMBING CONTRACTOR OR
 THE ELECTRICAL CONTRACTOR IS DESIGNING THIS WORK.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-15 Cont ID  
Sent By jpearson Date 2018-06-15 Time 10:34 Rev Time 0.00
Received By jpearson Date 2018-06-15 Time 10:24 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-08-14 Cont ID  
Sent By jpearson Date 2017-08-14 Time 11:06 Rev Time 0.00
Received By jpearson Date 2017-08-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-31 Cont ID  
Sent By pleduc Date 2018-05-31 Time   Rev Time 0.00
Received By pleduc Date 2018-05-31 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-14 Cont ID  
Sent By pleduc Date 2017-08-14 Time   Rev Time 0.00
Received By pleduc Date 2017-08-11 Time 15:05 Sent To  
Notes
2017-08-14 10:02:40THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE APPEARS TO BE NEW AREAS THAT MAY NOT BE
 PROTECTED BY THE EXISTING FIRE SPRINKLERS. PLEASE HAVE
 THE PROPOSED WORK REVIEWED BY A FIRE SPRINKLER
 CONTRACTOR FRO PROPER CODE PROTECTION COVERAGE.
  
 THE AREA SHALL ALSO BE REVIEWED BY A FIRE INSPECTOR ON
 ANY FIRE INSPECTION. NOT HAVING PROPER FIRE SPRINKLER
 PROTECTION SHALL RESULT IN A FAILED FIRE FINAL.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 09:28 Rev Time 0.00
Received By shill Date 2018-07-10 Time 10:53 Sent To  
Notes
2018-07-12 10:53:48IMPACT FEES ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-10 Cont ID  
Sent By gjohnson Date 2018-07-10 Time 10:39 Rev Time 0.00
Received By gjohnson Date 2018-06-22 Time 15:11 Sent To  
Notes
2018-07-07 18:45:19TO GJ DESK
  
  
2018-06-25 15:11:37B23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-15 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-25 Time 10:24 Sent To  
Notes
2018-05-30 10:24:52B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-21 Cont ID  
Sent By cpuell Date 2017-08-21 Time 19:05 Rev Time 0.00
Received By cpuell Date 2017-08-03 Time 15:29 Sent To  
Notes
2017-08-04 15:29:38B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2018-07-14 Cont ID  
Sent By shill Date 2018-07-14 Time 09:28 Rev Time 0.00
Received By shill Date 2018-07-14 Time 09:28 Sent To  
Notes
2018-07-14 09:28:38$0 DUE
 NO MU NUMBER ON PLAN, BUT PLAN IS STAMPED
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-07-07 Cont ID  
Sent By shill Date 2018-07-07 Time 18:43 Rev Time 0.00
Received By shill Date 2018-07-07 Time 18:43 Sent To  
Notes
2018-07-07 18:43:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-08-28 Cont ID  
Sent By shill Date 2017-08-14 Time 06:24 Rev Time 0.00
Received By shill Date 2017-08-14 Time 06:24 Sent To  
Notes
2017-08-28 06:25:18SEE BUILDING REVIEW
 IMPACT FEE REVIEW BY PALM BEACH COUNTY MAY BE REQUIRED
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-07-02 Cont ID  
Sent By ccole Date 2018-07-02 Time 13:28 Rev Time 0.00
Received By ccole Date 2018-06-29 Time 17:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-06-05 Cont ID  
Sent By ccole Date 2018-06-05 Time 17:10 Rev Time 0.00
Received By ccole Date 2018-06-05 Time 16:51 Sent To  
Notes
2018-06-05 17:36:071ST REVIEW FBC-2017 MECHANICAL
 PERMIT #17080211
 6/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW VRF SYSTEM- SECTION C403.2.1 FBC EC.
  
 2) SHEET M-1: REFER TO SECTION 501.4 FBC M AND INDICATE
 HOW COMPLIANCE WILL BE MET FOR PRESSURE EQUALIZATION.
 WILL THE EXHAUST BE LINKED TO THE OUTDOOR AIR SYSTEM?
 THE PLANS APPEAR TO INDICATE A MANUAL SWITCH FOR THE
 FAN. PLEASE PROVIDE AN AIR BALANCE CALCULATION.
  
 3) M-1: SHEET PROVIDE AN ACCESS PANEL FOR THE INLINE
 FAN- SECTION 306.1 FBC M.
  
 4) M-1: EXHAUST VENTILATION IS REQUIRED FOR THE SHOWER
 ROOM- TABLE 403.3.1
  
 5) M-1: PROVIDE WINDLOAD ENGINEERING FOR INSTALLATION
 OF THE CONDENSER AND CONDENSER STAND- SECTION 301.15
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-08-16 Cont ID  
Sent By ccole Date 2017-08-16 Time 10:22 Rev Time 0.00
Received By ccole Date 2017-08-16 Time 07:40 Sent To  
Notes
2017-08-16 10:28:071ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17080211
 8/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE HAIR SALON REQUIRES EXHAUST VENTILATION AT A
 RATE OF 0.60 CFMS PER SQ. FT., AND THE RECIRCULATION OF
 ANY AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3
 AND FOOTNOTE B. PLEASE PROVIDE A SYSTEM THAT MEETS
 COMPLIANCE.
  
 2) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE A SCOPE OF WORK FOR MECHANICAL ON THE PLAN
 WITH CORRESPONDING DRAWINGS AND DETAILS. SHOW ALL
 ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 4) THE BUILDING PLANS EXAMINER IS REQUIRING CODE
 COMPLIANT PLANS DONE BY A LICENSED ARCHITECT WHICH WILL
 CLARIFY WHETHER THE PROPOSED PROJECT IS A CHANGE OF
 OCCUPANCY OR CHANGE OF USE FROM THE PREVIOUS OCCUPANCY.
 BASED ON THOSE COMMENTS, THE MECHANICAL REVIEW IS
 STOPPED AT THIS TIME UNTIL NEW PLANS ARE RESUBMITTED
 FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-07-10 Cont ID  
Sent By gjohnson Date 2018-07-10 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2018-07-10 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-06-14 Cont ID  
Sent By gjohnson Date 2018-06-14 Time 17:39 Rev Time 0.00
Received By gjohnson Date 2018-06-14 Time 12:46 Sent To  
Notes
2018-06-14 18:13:491ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. AT LEAST ONE OF THE WORK SINKS SHALL COMPLY WITH FBC
 ACC 212.3 , 606
  
 2. WHAT SINK IS THE WATER HEATER DRAIN PAN DISCHARGING
 INTO PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE 2 COPIES OF THE MANUFACTURE SPECIFICATIONS
 OF THE WET TABLE IN THE VICHY SHOWER AND THE HAIR
 WASHING CHAIR SINK ONLY ONE WAS PROVIDED ALSO THE
 SHOWER VALVE. PER WPB AMEND TO FBC 107.2.1
  
 4. THE HAIR WASH SINK SHALL BE EQUIPPED WITH A VACUUM
 BREAKER. PER FBC PL 608.2
  
 5. ALL VALVES SHALL COMPLY WITH NSF 372 LEAD FREE . PER
 FBC PL 605.2.1
  
 6. SHT. P-3 DETAIL I THE SHOWER LINER SHALL BE PITCHED
 TO TH DRAIN. PER FBC PL 417.5.2
  
 7. THE LAVATORY IN THE BATHROOM SHALL COMPLY WITH
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.PER FBC PL 416.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-08-21 Cont ID  
Sent By thunt Date 2017-08-21 Time 13:06 Rev Time 0.00
Received By thunt Date 2017-08-18 Time 16:26 Sent To  
Notes
2017-08-21 13:05:421) CHANGE OF OCCUPANCY REQUIRES PER FBC 1012.8 AND
 1006.1 RESTROOM TO COMPLY FULLY WITH ALL OF CHAPTER 6
 OF THE FBC 2014 ACCESSIBILITY
 2) PLAN LACKS SIGNIFICANT AMOUNT OF INFORMATION TO
 COMPLETE A THOUROUGH REVIEW AT THIS TIME. PROVIDE LOAD
 AND BATHROOM DETAIL
  
 TIM HUNT
 PLUMBING INSPECTOR / PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6696
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved