Plan Review Details - Permit 17080183
Plan Review Stops For Permit 17080183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-08-16 Cont ID  
Sent By shill Date 2017-08-16 Time 07:00 Rev Time 0.00
Received By shill Date 2017-08-16 Time 07:00 Sent To  
Notes
2017-08-16 07:04:29****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 ISSUED AT APPLICANT'S RISK
  
 SPECIAL INSPECTOR AGREEMENT FOR PERMIT 16030369
 APPLICABLE FOR THIS PROJECT
  
 RESISTANCE TO WIND LOAD (INFILL OF OPENINGS) APPLICABLE
 TO THIS PERMIT BASED ON PLANS SUBMITTED WITH PERMIT
 16030369. IF NOT APPLICABLE, ARCHITECT OR ENGINEER IS
 TO PROVIDE A LETTER OF EXPLANATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-08-14 Cont ID  
Sent By shill Date 2017-08-14 Time 15:29 Rev Time 0.00
Received By shill Date 2017-08-14 Time 15:29 Sent To  
Notes
2017-08-14 15:29:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC B 1014.3, REVISE PLAN TO SHOW WORST CASE COMMON
 PATH OF TRAVEL. THIS IS TO BE MEASURED FROM THE
 FARTHEST POINT IN THE SOUTH END UNITS TO THE PROPOSED
 NEW EXIT STAIR (WHICH NOW BECOMES THE FIRST PLACE WHERE
 THE OCCUPANT HAS A CHOICE OF TWO EXITS).
  
 2. COMPLIANCE WITH FBC 1609 NOT CLEAR. HAS THE 2 HOUR
 EXTERIOR WALL (UL U308) BEEN EVALUATED FOR RESISTANCE
 TO WIND LOADS? I WAS UNABLE TO FIND A DECLARATION OF
 WIND DESIGN CRITERIA. STRUCTURAL PAGES APPEAR TO BE FOR
 THE STAIR ONLY. PLEASE REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA OR CLARIFY.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-24 Cont ID  
Sent By jleahy Date 2017-08-24 Time 10:07 Rev Time 0.00
Received By jleahy Date 2017-08-24 Time 07:51 Sent To  
Notes
2017-08-24 10:07:38FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE SUBMIT AS A DEFERRED SUBMITTAL THE FOLLOWING
 ITEMS PRIOR TO THE FINAL INSPECTION .
  
 SHEET E0.1 MISSING FROM SET.
  
 PANEL SCHEDULE(S) 408.58
  
 PLANS WITH CIRCUIT NUMBERS
  
 CUT SHEETS FOR THE FIXTURES USED. 110.3
  
 BACK UP FOR THE LIGHTING IN STAIRWELLS IN ACCORDANCE
 WITH 7.9.2.1. OF NFPA 101

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-08-14 Cont ID  
Sent By jleahy Date 2017-08-14 Time 06:39 Rev Time 0.00
Received By jleahy Date 2017-08-14 Time 07:50 Sent To  
Notes
2017-08-14 06:46:57FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SHEETS E.1.1 THRU E2.2 STATE TO SEE NOTES AND LEGENDS
 ON PAGE E0.1 WHICH IS NOT INCLUDED WITH THESE DRAWINGS.
  
 FIXTURE SCHEDULE OR TYPE TO BE USED IN STAIRWAY AND
 LANDINGS.
  
 MOUNTING HEIGHT OF FIXTURES ON WALLS (MIN. 80")
  
 IS THE LIGHTING ON AN EMMERGENCY CIRCUTI?
  
 BRANCH CIRCUIT NUMBERS AND/OR SOURCE REQUIRED TO BE ON
 PLANS.
  
 PANEL SCHEDULES.
  
 LIFE SAFETY 101 REQUIRES EMERGENCY BACK UP 90 MINUTES
 FOR EGRESS LIGHTING 7.9.2.1.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-08-23 Cont ID  
Sent By pleduc Date 2017-08-23 Time   Rev Time 0.00
Received By pleduc Date 2017-08-22 Time 16:07 Sent To  
Notes
2017-08-22 16:13:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 IN AN EFFORT TO CONTINUE TO MOVE THIS PLAN FORWARD,
 THIS PLAN IS APPROVED FOR THE DESIGN AND INSTALL OF THE
 STAIRS ONLY.
  
 THERE IS A CONCERN RELATED TO THE GLASS BLOCKS AS
 INFILL.
  
  
 1) SHEET A 3.10 - THERE ARE INDICATIONS OF GLASS BLOCKS
 AS INFILL TO OPENINGS INA 2 HOUR RATED STAIRWELL. THERE
 ARE NO INDICATIONS THAT THE GLASS BLOCKS SYSTEM SHOWING
 A LISTING/DESIGN STANDARD MEETING THE 2 HOUR WALL.
  
 PLEASE CLARIFY AND PROVIDE LISTED DETAILS PRIOR TO
 INSTALL OF ANY GLASS BLOCK THAT MEET THE RATING
 REQUIREMENTS.
  
  
 2) PROVIDE RIVISION SHEETS AS NECASSARY.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-08-25 Cont ID  
Sent By cpuell Date 2017-08-25 Time 16:45 Rev Time 0.00
Received By cpuell Date 2017-08-03 Time 16:08 Sent To  
Notes
2017-08-24 16:24:26TO LMARCHANT FOR PROCESSING
2017-08-07 16:08:18C08

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2017-08-16 Cont ID  
Sent By shill Date 2017-08-16 Time 07:21 Rev Time 0.00
Received By shill Date 2017-08-16 Time 07:21 Sent To  
Notes
2017-08-16 07:21:58SEE 16030369
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-08-24 Cont ID  
Sent By aaponte Date 2017-08-24 Time 16:15 Rev Time 0.00
Received By aaponte Date 2017-08-24 Time 16:13 Sent To  
Notes
2017-08-24 16:24:06STAFF RECOMMENDS RETAINING THE OPENINGS SIZE AND
 UTILIZING FIRE RETARDANT WIRE GLASS INSTEAD OF THE
 PROPOSED GLASS BLOCK.