Plan Review Stops For Permit 17080183 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2017-08-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-08-16 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-08-16 |
Time |
07:00 |
Sent To |
|
|
Notes |
2017-08-16 07:04:29 | ****PROVISOS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | ISSUED AT APPLICANT'S RISK | | | | SPECIAL INSPECTOR AGREEMENT FOR PERMIT 16030369 | | APPLICABLE FOR THIS PROJECT | | | | RESISTANCE TO WIND LOAD (INFILL OF OPENINGS) APPLICABLE | | TO THIS PERMIT BASED ON PLANS SUBMITTED WITH PERMIT | | 16030369. IF NOT APPLICABLE, ARCHITECT OR ENGINEER IS | | TO PROVIDE A LETTER OF EXPLANATION. | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-08-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-08-14 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-08-14 |
Time |
15:29 |
Sent To |
|
|
Notes |
2017-08-14 15:29:38 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. FBC B 1014.3, REVISE PLAN TO SHOW WORST CASE COMMON | | PATH OF TRAVEL. THIS IS TO BE MEASURED FROM THE | | FARTHEST POINT IN THE SOUTH END UNITS TO THE PROPOSED | | NEW EXIT STAIR (WHICH NOW BECOMES THE FIRST PLACE WHERE | | THE OCCUPANT HAS A CHOICE OF TWO EXITS). | | | | 2. COMPLIANCE WITH FBC 1609 NOT CLEAR. HAS THE 2 HOUR | | EXTERIOR WALL (UL U308) BEEN EVALUATED FOR RESISTANCE | | TO WIND LOADS? I WAS UNABLE TO FIND A DECLARATION OF | | WIND DESIGN CRITERIA. STRUCTURAL PAGES APPEAR TO BE FOR | | THE STAIR ONLY. PLEASE REVISE PLAN TO INCLUDE WIND | | DESIGN CRITERIA OR CLARIFY. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-08-24 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-08-24 |
Time |
07:51 |
Sent To |
|
|
Notes |
2017-08-24 10:07:38 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PLEASE SUBMIT AS A DEFERRED SUBMITTAL THE FOLLOWING | | ITEMS PRIOR TO THE FINAL INSPECTION . | | | | SHEET E0.1 MISSING FROM SET. | | | | PANEL SCHEDULE(S) 408.58 | | | | PLANS WITH CIRCUIT NUMBERS | | | | CUT SHEETS FOR THE FIXTURES USED. 110.3 | | | | BACK UP FOR THE LIGHTING IN STAIRWELLS IN ACCORDANCE | | WITH 7.9.2.1. OF NFPA 101 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-08-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-08-14 |
Time |
06:39 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-08-14 |
Time |
07:50 |
Sent To |
|
|
Notes |
2017-08-14 06:46:57 | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | NFPA 70 2011 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | SHEETS E.1.1 THRU E2.2 STATE TO SEE NOTES AND LEGENDS | | ON PAGE E0.1 WHICH IS NOT INCLUDED WITH THESE DRAWINGS. | | | | FIXTURE SCHEDULE OR TYPE TO BE USED IN STAIRWAY AND | | LANDINGS. | | | | MOUNTING HEIGHT OF FIXTURES ON WALLS (MIN. 80") | | | | IS THE LIGHTING ON AN EMMERGENCY CIRCUTI? | | | | BRANCH CIRCUIT NUMBERS AND/OR SOURCE REQUIRED TO BE ON | | PLANS. | | | | PANEL SCHEDULES. | | | | LIFE SAFETY 101 REQUIRES EMERGENCY BACK UP 90 MINUTES | | FOR EGRESS LIGHTING 7.9.2.1. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-08-23 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-08-23 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-08-22 |
Time |
16:07 |
Sent To |
|
|
Notes |
2017-08-22 16:13:15 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | IN AN EFFORT TO CONTINUE TO MOVE THIS PLAN FORWARD, | | THIS PLAN IS APPROVED FOR THE DESIGN AND INSTALL OF THE | | STAIRS ONLY. | | | | THERE IS A CONCERN RELATED TO THE GLASS BLOCKS AS | | INFILL. | | | | | | 1) SHEET A 3.10 - THERE ARE INDICATIONS OF GLASS BLOCKS | | AS INFILL TO OPENINGS INA 2 HOUR RATED STAIRWELL. THERE | | ARE NO INDICATIONS THAT THE GLASS BLOCKS SYSTEM SHOWING | | A LISTING/DESIGN STANDARD MEETING THE 2 HOUR WALL. | | | | PLEASE CLARIFY AND PROVIDE LISTED DETAILS PRIOR TO | | INSTALL OF ANY GLASS BLOCK THAT MEET THE RATING | | REQUIREMENTS. | | | | | | 2) PROVIDE RIVISION SHEETS AS NECASSARY. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-08-25 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2017-08-25 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-08-03 |
Time |
16:08 |
Sent To |
|
|
Notes |
2017-08-24 16:24:26 | TO LMARCHANT FOR PROCESSING | 2017-08-07 16:08:18 | C08 |
|
|
Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
Rev No |
1 |
Status |
P |
Date |
2017-08-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-08-16 |
Time |
07:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-08-16 |
Time |
07:21 |
Sent To |
|
|
Notes |
2017-08-16 07:21:58 | SEE 16030369 | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2017-08-24 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2017-08-24 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2017-08-24 |
Time |
16:13 |
Sent To |
|
|
Notes |
2017-08-24 16:24:06 | STAFF RECOMMENDS RETAINING THE OPENINGS SIZE AND | | UTILIZING FIRE RETARDANT WIRE GLASS INSTEAD OF THE | | PROPOSED GLASS BLOCK. |
|
|